Plan Review Notes
Plan Review Notes For Permit 17021161
Permit Number 17021161
Review Stop M
Sequence Number 3
Notes
Date Text
2017-03-17 16:31:133RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17021161
 3/17/17
  
 COMMENTS # 4, 5, 6, & 7 FROM THE 2ND REVIEW STILL
 EXIST. THE COMMENTS ARE PRINTED AGAIN BELOW- PLEASE
 COMPLY.
  
 4) AS PREVIOSUSLY REQUESTED IN THE 1ST REVIEW SUBMIT
 ENERGY CALCULATIONS- SEE SECTION R101.2 AND R101.5,1.1
 FBC-14 ENERGY CONSERVATION
  
 5) AS PREVIOUSLY REQUESTED PROVIDE CONDENSATE DISPOSAL
 PLANS FOR THE AIR HANDLERS- SECTION M1411.3 & M1411.3.1
 FBC-14 RESIDENTIAL.
  
 6) THE NEW 2ND FLOOR AC PLAN APPEARS TO INDICATE AHU-2
 IS IN THE ATTIC. PLEASE REFER TO SECTION R403.2.4 FBC-1
 ENERGY CONSERVATION AND SHOW COMPLIAINCE WITH ITEMS
 #1-4, AND BY SUBMITTING DOCUMENTATION OF
 PERFORMANCE-BASED ENERGY CONSERVATION COMPLIANCE IN
 ACCORDANCE WITH SECTION R405.
  
 7) REFER TO SECTION 607.6.2.1 AND PROVIDE CEILING
 RADIATION DAMPERS FOR THE DUCTS PENETRATING THE
 FIRE-RATED FLOOR/CEILING ASSEMBLY. THE DAMPER SPECS
 SUBMITTED INDICATE THAT THE PRODUCT IS FOR USE IN
 MASONRY OR STUD WALLS, AND CONCRETE FLOORS. THE FLOOR
 ASSEMBLY IS WOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER