2017-03-17 16:31:13 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #17021161 | | 3/17/17 | | | | COMMENTS # 4, 5, 6, & 7 FROM THE 2ND REVIEW STILL | | EXIST. THE COMMENTS ARE PRINTED AGAIN BELOW- PLEASE | | COMPLY. | | | | 4) AS PREVIOSUSLY REQUESTED IN THE 1ST REVIEW SUBMIT | | ENERGY CALCULATIONS- SEE SECTION R101.2 AND R101.5,1.1 | | FBC-14 ENERGY CONSERVATION | | | | 5) AS PREVIOUSLY REQUESTED PROVIDE CONDENSATE DISPOSAL | | PLANS FOR THE AIR HANDLERS- SECTION M1411.3 & M1411.3.1 | | FBC-14 RESIDENTIAL. | | | | 6) THE NEW 2ND FLOOR AC PLAN APPEARS TO INDICATE AHU-2 | | IS IN THE ATTIC. PLEASE REFER TO SECTION R403.2.4 FBC-1 | | ENERGY CONSERVATION AND SHOW COMPLIAINCE WITH ITEMS | | #1-4, AND BY SUBMITTING DOCUMENTATION OF | | PERFORMANCE-BASED ENERGY CONSERVATION COMPLIANCE IN | | ACCORDANCE WITH SECTION R405. | | | | 7) REFER TO SECTION 607.6.2.1 AND PROVIDE CEILING | | RADIATION DAMPERS FOR THE DUCTS PENETRATING THE | | FIRE-RATED FLOOR/CEILING ASSEMBLY. THE DAMPER SPECS | | SUBMITTED INDICATE THAT THE PRODUCT IS FOR USE IN | | MASONRY OR STUD WALLS, AND CONCRETE FLOORS. THE FLOOR | | ASSEMBLY IS WOOD. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|