2017-03-10 12:00:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17021161
 3/10/17
  
 1) THE PLAN SHEETS FOR THE 1ST AND 2ND FLOOR ARE BOTH
 LABELED M.1. PLEASE LABEL THE 2ND FLOOR PLAN SHEET M.2-
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 2) BOTH AC SYSTEMS FOR THE 1ST AND 2ND FLOOR ARE
 DESIGNATED AS SYSTEM #1 IN THE SCHEDULE. PLEASE LABEL
 THE 2ND FLOOR SYSTEM AS SYSTEM #2.
  
 3) PLEASE INDICATE WHICH SETS OF AC CALCULATIONS ARE
 FOR SYSTEM #1 AND FOR AC #2.
  
 4) AS PREVIOSUSLY REQUESTED IN THE 1ST REVIEW SUBMIT
 ENERGY CALCULATIONS- SEE SECTION R101.2 AND R101.5,1.1
 FBC-14 ENERGY CONSERVATION
  
 5) AS PREVIOUSLY REQUESTED PROVIDE CONDENSATE DISPOSAL
 PLANS FOR THE AIR HANDLERS- SECTION M1411.3 & M1411.3.1
 FBC-14 RESIDENTIAL.
  
 6) THE NEW 2ND FLOOR AC PLAN APPEARS TO INDICATE AHU-2
 IS IN THE ATTIC. PLEASE REFER TO SECTION R403.2.4 FBC-1
 ENERGY CONSERVATION AND SHOW COMPLIAINCE WITH ITEMS
 #1-4, AND BY SUBMITTING DOCUMENTATION OF
 PERFORMANCE-BASED ENERGY CONSERVATION COMPLIANCE IN
 ACCORDANCE WITH SECTION R405.
  
 7) REFER TO SECTION 607.6.2.1 AND PROVIDE CEILING
 RADIATION DAMPERS FOR THE DUCTS PENETRATING THE
 FIRE-RATED FLOOR/CEILING ASSEMBLY. THE DAMPER SPECS
 SUBMITTED INDICATE THAT THE PRODUCT IS FOR USE IN
 MASONRY OR STUD WALLS, AND CONCRETE FLOORS. THE FLOOR
 ASSEMBLY IS WOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER