2017-02-28 12:56:36 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17021161 |
| 2/28/17 |
| |
| 1) PROVIDE COMPLETE AC EQUIPMENT SCHEDULES FOR SYSTEMS |
| 1 & 2. |
| |
| 2) LABEL SYSTEM THE LOCATION OF SYSTEM #2 ON THE PLANS. |
| |
| 3) PROVIDE AN AC LAYOUT PLAN FOR THE SECOND FLOOR. |
| |
| 4) PROVIDE A RETURN GRILL FOR THE AC SYSTEM IN THE |
| BEDROOM 1 CLOSET. |
| |
| 5) THE SUBMITTED AC CALCULATIONS APPEAR TO BE FOR THE |
| FIRST FLOOR ONLY. PLEASE PROVIDE CALCULATIONS FOR THE |
| SECOND FLOOR- SECTION R403.6.1 FBC-14 ENERGY |
| CONSERVATION. |
| |
| 6) FULL COMPLIANCE WITH THE FBC-14 ENERGY CONSERVATION |
| CODE IS REQUIRED PER SECTION R101.4.5. PLEASE SUBMIT |
| EITHER FORM R402 FOR PRESCRIPTIVE COMPLIANCE OR FORM |
| R405 USING APPROVED SOFTWARE SUCH AS ENERGYGAUGE FOR |
| PERFORMANCE BASED COMPLIANCE. |
| |
| 7) PROVIDE A CONDENSATE DISPOSAL PLAN FOR EACH AIR |
| HANDLER. |
| |
| 8) PROVIDE A DETAIL FOR INSTALLATION OF THE FIRE DAMPER |
| AT THE DUCT PENETRATIONS OF THE FLOOR/CEILING |
| ASSEMBLIES. PLEASE INCLUDE A DETAIL OF THE ACTUAL |
| FLOOR/CEILING ASSEMBLY INCLUDING THE HOURLY |
| FIRE-RATING. |
| |
| 9) AN APPLICATION FOR BUSINESS LICENSING MUST BE |
| SUBMITTED. PLEASE CONTACT RACHELSKLAREW- LICENSE & |
| PERMIT SPECIALIST SUPERVISOR- 561-805-6688. |
| |
| 10) PLEASE NOTE THAT AN INCREASE IN VALUE WILL BE |
| REQUIRED FOR THE ENTIRE SCOPE OF WORK FOR THE PROJECT- |
| SEE SECTION 109.3 WPB AMENDMENTS TO THE FBC. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |