2017-02-28 12:56:361ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17021161
 2/28/17
  
 1) PROVIDE COMPLETE AC EQUIPMENT SCHEDULES FOR SYSTEMS
 1 & 2.
  
 2) LABEL SYSTEM THE LOCATION OF SYSTEM #2 ON THE PLANS.
  
 3) PROVIDE AN AC LAYOUT PLAN FOR THE SECOND FLOOR.
  
 4) PROVIDE A RETURN GRILL FOR THE AC SYSTEM IN THE
 BEDROOM 1 CLOSET.
  
 5) THE SUBMITTED AC CALCULATIONS APPEAR TO BE FOR THE
 FIRST FLOOR ONLY. PLEASE PROVIDE CALCULATIONS FOR THE
 SECOND FLOOR- SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION.
  
 6) FULL COMPLIANCE WITH THE FBC-14 ENERGY CONSERVATION
 CODE IS REQUIRED PER SECTION R101.4.5. PLEASE SUBMIT
 EITHER FORM R402 FOR PRESCRIPTIVE COMPLIANCE OR FORM
 R405 USING APPROVED SOFTWARE SUCH AS ENERGYGAUGE FOR
 PERFORMANCE BASED COMPLIANCE.
  
 7) PROVIDE A CONDENSATE DISPOSAL PLAN FOR EACH AIR
 HANDLER.
  
 8) PROVIDE A DETAIL FOR INSTALLATION OF THE FIRE DAMPER
 AT THE DUCT PENETRATIONS OF THE FLOOR/CEILING
 ASSEMBLIES. PLEASE INCLUDE A DETAIL OF THE ACTUAL
 FLOOR/CEILING ASSEMBLY INCLUDING THE HOURLY
 FIRE-RATING.
  
 9) AN APPLICATION FOR BUSINESS LICENSING MUST BE
 SUBMITTED. PLEASE CONTACT RACHELSKLAREW- LICENSE &
 PERMIT SPECIALIST SUPERVISOR- 561-805-6688.
  
 10) PLEASE NOTE THAT AN INCREASE IN VALUE WILL BE
 REQUIRED FOR THE ENTIRE SCOPE OF WORK FOR THE PROJECT-
 SEE SECTION 109.3 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  