2017-03-02 07:38:301ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17021070
 3/2/17
  
 1) SHEET M-2: THE DIFFUSER TAGS AND CFMS ARE MISSING IN
 THE BREAKROOM AND THE TECH ROOM.
  
 2) M-2: THE ORIGINAL APPROVED PLAN INDICATES 1140 CFMS
 OF SUPPLY AIR PROVIDED TO THE TECH ROOM WHICH WOULD
 INDICATE THE TWO 10X10 TA GRILLES ARE UNDERSIZED- SEE
 SECTION 601.5 (2) AND PROVIDE TRANSFER GRILLS SIZED AT
 50 SQ. INCHES PER 100 CFM OF SUPPLY AIR.
  
 3) PLEASE BIND THE PLANS TOGETHER- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  