2017-03-31 11:41:39RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES) ALONG WITH THE MANUFACTURER AND MODEL NUMBER AS
 REQUIRED BY SEC. R403.6 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 2- ENGINEER OF RECORD TO SPECIFY ON THE A/C PLAN THE
 EQUIPMENT MANUFACTURER AND MODEL NUMBER SPECIFIED ON
 THE EQUIPMENT SIZING CALCULATIONS. SEC. 107.3.5.3(10)
 CITY AMENDMENTS.
  
 3- ENGINEER OF RECORD TO SPECIFY THE CFM'S ON THE A/C
 PLAN. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 4- ENGINEER OF RECORD TO SHOW ON THE A/C PLAN
 COMPLIANCE WITH THE BALANCED RETURN AIR AS REQUIRED BY
 SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  