Plan Review Notes
Plan Review Notes For Permit 17021025
Permit Number 17021025
Review Stop P
Sequence Number 1
Notes
Date Text
2017-03-29 13:45:051) SHT. ALS.1.1 - WHAT TABLE AND WHAT CODE ARE YOU
 DERIVING YOUR SANITARY FIXTURE REQUIREMENTS FROM? TABLE
 403.1 IN THE 2014 FBC-PLUMBING REQUIRES ONE WATER
 CLOSET FOR EVERY 75 MALES AND ONE WATER CLOSET FOR
 EVERY 75 FEMALES, NOT ONE PER 500. THERE IS ALSO AN
 ISSUE WITH THE TABLE ON THE PLANS FOR THE LAVATORIES.
 THE RATIO IS ONE LAVATORY FOR EVERY 200 MALES AND ONE
 LAVATORY FOR EVERY 200 FEMALES. ALSO, THE SPLIT HAS TO
 BE EQUAL, NOT 48 & 49. THE CORRECT NUMBER OF FIXTURES
 HAVE BEEN SUPPLIED BUT CORRECT THE TABLE.WPB AMEND. TO
 FBC SEC. 107.2.1, FBC-PLUMBING SEC. 403.1.
 2) SHT. ALS.1.1 - THE DOORS IN THE TOILET ROOMS SWING
 INTO THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORIES
 WHICH IS PROHIBITED BY 2014 FBC-ACCESS SEC.603.2.3. SEE
 EXCEPTION #2 AND SHOW COMPLIANCE ON THE PLAN.
 3) SHT. A2.01 SHOWS GUTTERS. PROVIDE THE GUTTER SIZES
 AND THE SQUARE FOOT AREA DRAINED BY EACH GUTTER.
 GUTTERS AND DOWNSPOUTS SHALL BE SIZED PER 2014
 FBC-PLUMBING TABLE 1106.6.
 4) SUBMIT A STORM DRAINAGE RISER FOR REVIEW. THE
 RAINFALL RATE SHALL BE BASED ON A 5 INCH PER HOUR
 RAINFALL, NOT 4.5 INCHES.
 5) SHT. A8.02 - DETAIL #2 & #5 - THE MINIMUM VERTICAL
 DISTANCE FOR KNEE CLEARANCE UNDER AN ELEMENT SHALL BE
 27 INCHES PER 2014 FBC-ACCESSIBILITY SEC.306.3.1.
 6) SHT. A8.02 - DETAIL #2 - THE GRAB BAR BEHIND THE
 WATER CLOSET SHALL BE LOCATED PER 2014
 FBC-ACCESSIBILITY SEC.604.5.2 & FIG. 604.5.2.
 7) SHT. A8.02 - DETAIL #3 - THE SIDE WALL GRAB BAR NEXT
 TO THE WATER CLOSET SHALL BE LOCATED PER 2014
 FBC-ACCESS. SEC.604.5.1 & FIG. 604.5.1.
 8) SHT. A8.02 - DETAILS #3 & #4 - THE TOILET PAPER
 DISPENSER SHALL BE LOCATED 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM TO THE CENTERLINE OF THE FIRST TOILET
 PAPER DISPENSER. 2014 FBC-ACCESS SEC.604.7.
 9) SHT. A8.02 - THE HEIGHT OF THE TOILET PAPER
 DISPENSER IS SHOWN AT 1'-7" MAXIMUM AND 2'-0" MINIMUM.
 THIS IS OBVIOUSLY A TYPO ERROR. PLEASE CORRECT.
 10) SUBMIT A CLEAR DETAIL FOR THE HOT WATER
 RECIRCULATING SYSTEM. COMPLY WITH 2014 FBC-PLUMBING
 SEC.607.2.2.
 11) SHT. P0.2 - DETAIL #4 - THE GENERAL NOTES ON THE
 DETAIL REFER TO THE UNIFORM PLUMBING CODE. THE CODE IN
 EFFECT IS THE 2014 FLORIDA BUILDING CODE-PLUMBING.
 PLEASE REVISE THE NOTE.
 12) SHT. P0.2 - DETAIL #1 - PROVIDE INFORMATION AS TO
 HOW THE CONDENSATE STANDS WILL BE ANCHORED TO THE ROOF
 MEMBRANE. WPB AMEND. TO FBC SEC. 107.2.1.
 13) SHT. P0.2 - THE GENERAL NOTES STATE THAT THE GREASE
 INTERCEPTOR IS 1250 GALLON CAPACITY AND THERE IS A NOTE
 IN THE UPPER LEFT CORNER OF THE DETAIL STATING THE IT
 IS 750 GALON. CLARIFY.
 14) SHT. P1.1 - THE GREASE TRAP SIZING FORMULA NOTES 40
 SEATS BUT SHT A1.14 SHOWS MORE THAN 40 SEATS. THE BAR
 AREA SEATS, PATIO AREA AND BANQUET AREAS MUST BE
 INCLUDED IN THE CALCULATIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  