2017-03-29 13:45:05 | 1) SHT. ALS.1.1 - WHAT TABLE AND WHAT CODE ARE YOU |
| DERIVING YOUR SANITARY FIXTURE REQUIREMENTS FROM? TABLE |
| 403.1 IN THE 2014 FBC-PLUMBING REQUIRES ONE WATER |
| CLOSET FOR EVERY 75 MALES AND ONE WATER CLOSET FOR |
| EVERY 75 FEMALES, NOT ONE PER 500. THERE IS ALSO AN |
| ISSUE WITH THE TABLE ON THE PLANS FOR THE LAVATORIES. |
| THE RATIO IS ONE LAVATORY FOR EVERY 200 MALES AND ONE |
| LAVATORY FOR EVERY 200 FEMALES. ALSO, THE SPLIT HAS TO |
| BE EQUAL, NOT 48 & 49. THE CORRECT NUMBER OF FIXTURES |
| HAVE BEEN SUPPLIED BUT CORRECT THE TABLE.WPB AMEND. TO |
| FBC SEC. 107.2.1, FBC-PLUMBING SEC. 403.1. |
| 2) SHT. ALS.1.1 - THE DOORS IN THE TOILET ROOMS SWING |
| INTO THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORIES |
| WHICH IS PROHIBITED BY 2014 FBC-ACCESS SEC.603.2.3. SEE |
| EXCEPTION #2 AND SHOW COMPLIANCE ON THE PLAN. |
| 3) SHT. A2.01 SHOWS GUTTERS. PROVIDE THE GUTTER SIZES |
| AND THE SQUARE FOOT AREA DRAINED BY EACH GUTTER. |
| GUTTERS AND DOWNSPOUTS SHALL BE SIZED PER 2014 |
| FBC-PLUMBING TABLE 1106.6. |
| 4) SUBMIT A STORM DRAINAGE RISER FOR REVIEW. THE |
| RAINFALL RATE SHALL BE BASED ON A 5 INCH PER HOUR |
| RAINFALL, NOT 4.5 INCHES. |
| 5) SHT. A8.02 - DETAIL #2 & #5 - THE MINIMUM VERTICAL |
| DISTANCE FOR KNEE CLEARANCE UNDER AN ELEMENT SHALL BE |
| 27 INCHES PER 2014 FBC-ACCESSIBILITY SEC.306.3.1. |
| 6) SHT. A8.02 - DETAIL #2 - THE GRAB BAR BEHIND THE |
| WATER CLOSET SHALL BE LOCATED PER 2014 |
| FBC-ACCESSIBILITY SEC.604.5.2 & FIG. 604.5.2. |
| 7) SHT. A8.02 - DETAIL #3 - THE SIDE WALL GRAB BAR NEXT |
| TO THE WATER CLOSET SHALL BE LOCATED PER 2014 |
| FBC-ACCESS. SEC.604.5.1 & FIG. 604.5.1. |
| 8) SHT. A8.02 - DETAILS #3 & #4 - THE TOILET PAPER |
| DISPENSER SHALL BE LOCATED 7 INCHES MINIMUM AND 9 |
| INCHES MAXIMUM TO THE CENTERLINE OF THE FIRST TOILET |
| PAPER DISPENSER. 2014 FBC-ACCESS SEC.604.7. |
| 9) SHT. A8.02 - THE HEIGHT OF THE TOILET PAPER |
| DISPENSER IS SHOWN AT 1'-7" MAXIMUM AND 2'-0" MINIMUM. |
| THIS IS OBVIOUSLY A TYPO ERROR. PLEASE CORRECT. |
| 10) SUBMIT A CLEAR DETAIL FOR THE HOT WATER |
| RECIRCULATING SYSTEM. COMPLY WITH 2014 FBC-PLUMBING |
| SEC.607.2.2. |
| 11) SHT. P0.2 - DETAIL #4 - THE GENERAL NOTES ON THE |
| DETAIL REFER TO THE UNIFORM PLUMBING CODE. THE CODE IN |
| EFFECT IS THE 2014 FLORIDA BUILDING CODE-PLUMBING. |
| PLEASE REVISE THE NOTE. |
| 12) SHT. P0.2 - DETAIL #1 - PROVIDE INFORMATION AS TO |
| HOW THE CONDENSATE STANDS WILL BE ANCHORED TO THE ROOF |
| MEMBRANE. WPB AMEND. TO FBC SEC. 107.2.1. |
| 13) SHT. P0.2 - THE GENERAL NOTES STATE THAT THE GREASE |
| INTERCEPTOR IS 1250 GALLON CAPACITY AND THERE IS A NOTE |
| IN THE UPPER LEFT CORNER OF THE DETAIL STATING THE IT |
| IS 750 GALON. CLARIFY. |
| 14) SHT. P1.1 - THE GREASE TRAP SIZING FORMULA NOTES 40 |
| SEATS BUT SHT A1.14 SHOWS MORE THAN 40 SEATS. THE BAR |
| AREA SEATS, PATIO AREA AND BANQUET AREAS MUST BE |
| INCLUDED IN THE CALCULATIONS. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |