Plan Review Notes
Plan Review Notes For Permit 17021025
Permit Number 17021025
Review Stop M
Sequence Number 1
Notes
Date Text
2017-03-01 09:58:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17021025
 3/1/17
  
 1) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATION
 PER SECTION 202 FBC-14 ENERGY CONSERVATION. REFER TO
 SECTIONS C101.4.3 AND C401.2 AND SUBMIT A COMPLIANCE
 REPORT.
  
 2) PLEASE PLACE A NOTE ON THE PLAN INDICATING SEPARATE
 PERMITS ARE REQUIRED FOR THE HOODS, THE HOOD FIRE
 SUPPRESSION SYSTEMS, AND THE WALK-IN COOLERS AND
 FREEZERS. PLEASE NOTE THAT A FLORIDA PRODUCT APPROVAL
 OR MANUFACTURED BUILDING CERTIFICATION IS REQUIRED FOR
 THE EXTERIOR WALK-IN BOX.
  
 3) SHEET M1.1: PLEASE LABEL THE RTU'S 1, 2, & 3.
  
 4) M1.1: IT APPEARS THAT THE AMOUNT OF CFMS BEING
 SUPPLIED ON THE PLAN BY RTU-1 (4110 CFMS) MAY BE
 EXCEEDING THE UNIT'S DESIGN AIRFLOW SHOWN IN THE
 SCHEDULE. THIS IS ALSO TRUE OF RTU-3 AT 3900 CFMS
  
 5) MR1.1: PLEASE VERIFY THAT NO MECHANICAL EQUIPMENT
 REQUIRING SERVICING IS WITHIN 10' OF THE ROOF EDGE
 UNLESS THE PARAPET WALL AT THAT LOCATION IS MINIMUM 42"
 HIGH. OTHERWISE A GUARDRAIL WILL BE REQUIRED- SECTION
 304.11.
  
 6) INDICATE HOW ACCESS TO THE EQUIPMENT ON THE ROOF IS
 BEING PROVIDED- SEE SECTION 306.5.
  
 7) THE OUTDOOR AIR SUPPLY FOR THE RTU'S MUST BE
 EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN
 THE SYSTEMS OR SPACES ARE NOT IN USE- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 8) DEMAND CONTROLLED VENTILATION IS REQUIRED IN THE
 DINING ROOM PER SECTION C403.2.5.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  