2017-03-01 09:58:39 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #17021025 |
| 3/1/17 |
| |
| 1) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATION |
| PER SECTION 202 FBC-14 ENERGY CONSERVATION. REFER TO |
| SECTIONS C101.4.3 AND C401.2 AND SUBMIT A COMPLIANCE |
| REPORT. |
| |
| 2) PLEASE PLACE A NOTE ON THE PLAN INDICATING SEPARATE |
| PERMITS ARE REQUIRED FOR THE HOODS, THE HOOD FIRE |
| SUPPRESSION SYSTEMS, AND THE WALK-IN COOLERS AND |
| FREEZERS. PLEASE NOTE THAT A FLORIDA PRODUCT APPROVAL |
| OR MANUFACTURED BUILDING CERTIFICATION IS REQUIRED FOR |
| THE EXTERIOR WALK-IN BOX. |
| |
| 3) SHEET M1.1: PLEASE LABEL THE RTU'S 1, 2, & 3. |
| |
| 4) M1.1: IT APPEARS THAT THE AMOUNT OF CFMS BEING |
| SUPPLIED ON THE PLAN BY RTU-1 (4110 CFMS) MAY BE |
| EXCEEDING THE UNIT'S DESIGN AIRFLOW SHOWN IN THE |
| SCHEDULE. THIS IS ALSO TRUE OF RTU-3 AT 3900 CFMS |
| |
| 5) MR1.1: PLEASE VERIFY THAT NO MECHANICAL EQUIPMENT |
| REQUIRING SERVICING IS WITHIN 10' OF THE ROOF EDGE |
| UNLESS THE PARAPET WALL AT THAT LOCATION IS MINIMUM 42" |
| HIGH. OTHERWISE A GUARDRAIL WILL BE REQUIRED- SECTION |
| 304.11. |
| |
| 6) INDICATE HOW ACCESS TO THE EQUIPMENT ON THE ROOF IS |
| BEING PROVIDED- SEE SECTION 306.5. |
| |
| 7) THE OUTDOOR AIR SUPPLY FOR THE RTU'S MUST BE |
| EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN |
| THE SYSTEMS OR SPACES ARE NOT IN USE- SECTION |
| C403.2.4.4 FBC-14 ENERGY CONSERVATION. |
| |
| 8) DEMAND CONTROLLED VENTILATION IS REQUIRED IN THE |
| DINING ROOM PER SECTION C403.2.5.1. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |