2017-03-09 14:29:26 | 3815 SOUTH DIXIE HIGHWAY |
| PERMIT #17021025 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| PROVIDE UL LISTING (OR EQUAL), APPLIANCE SPECIFICATIONS |
| AND INSTALLATION DATA FOR THE SOLID FUEL COOKING |
| EQUIPMENT. DATA SHALL INDICATE IF A SUPPRESSION SYSTEM |
| IS REQUIRED FOR THIS APPLIANCE. |
| |
| INDICATE THE LOCATION, FUEL TYPE AND QUANTITY OF SOLID |
| FUEL TO BE STORED FOR THE COOKING OPERATIONS. |
| |
| SOLID COOKING OPERATIONS AND DESIGN SHALL COMPLY WITH |
| NFPA 96. FOR EXAMPLE: PER SECTION 14.9.2.1. FUEL |
| STORAGE SHALL NOT EXCEED A ONE-DAY SUPPLY WHERE STORAGE |
| IS LOCATED IN THE SAME ROOM AS THE SOLID FUELED |
| APPLIANCE, OR IN THE SAME ROOMS AS THE FUEL-LOADING OR |
| CLEAN-OUT DOORS. |
| |
| ***SECTION14.9.3.7.3 APPLIANCES WITH FIREBOXES OVER 5 |
| CUBIC FEET THE WATER SOURCE SHALL BE A FIXED PIPE WATER |
| SYSTEM WITH A HOSE OF ADEQUATE LENGTH TO REACH THE |
| COMBUSTION AND COOKING CHAMBERS OF THE APPLIANCE. |
| |
| ALL OVEN ASH SHALL BE REMOVED FROM THE ASH COMPARTMENT |
| AT LEAST ONCE PER DAY. THE ASH SHALL BE SPRAYED |
| ADEQUATELY WITH WATER BEFORE REMOVAL TO EXTINGUISH ANY |
| HOT ASH OR CINDERS AND TO CONTROL THE DUST WHEN THE ASH |
| IS MOVED. SECTION 14.9.3.8.1 A HEAVY METAL CONTAINER OR |
| CART (MINIMUM 16 GAUGE) WITH A COVER SHALL BE PROVIDED |
| FOR THE REMOVAL OF ASH. THE ASH REMOVAL CONTAINER OR |
| CART SHALL NOT EXCEED A MAXIMUM OF 20 GAL CAPACITY, |
| SHALL BE ASSIGNED FOR THIS ONE PURPOSE, SHALL BE ABLE |
| TO BE HANDLED EASILY BY ANY EMPLOYEE ASSIGNED THE TASK, |
| AND SHALL PASS EASILY THROUGH ANY PASSAGEWAY TO THE |
| OUTSIDE OF THE BUILDING. THE CONTAINER OR CART SHALL |
| ALWAYS BE COVERED WHEN IT IS BEING MOVED THROUGH THE |
| PREMISES. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| |
| |
| |