2017-03-23 17:57:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. ALS1.1 LIFE SAFETY REQUIREMENTS STATES THAT SF AREA
 IS 2367, BUT IT APPEARS THAT AN ADDITION IS PROPOSED.
 REVISE PLAN TO SHOW EXISTING SF AREA, PROPOSED NEW, NEW
 TOTAL; AREA SUMMARY SHOULD INCLUDE BOTH UNDER AIR AND
 OUTDOOR CALCS SEPARATELY, AREA SUMMARY SHOULD INCLUDE
 MEZZANINE, FBC 107, FBC EB CHAPTER 11.
  
 2. ALS1.1 STATES THIS IS A CHANGE OF OCCUPANCY. OUR
 RECORDS APPEAR TO SHOW THE HISTORY OF THIS STRUCTURE AS
 CONSTRUCTED AS A RESTAURANT WITH CONTINUED USE AS A
 RESTAURANT. EITHER REVISE TO REMOVE CHANGE OF OCCUPANCY
 DESIGNATION, OR CLARIFY BY INCLUDING EXISTING OCCUPANCY
 AND SHOW COMPLIANCE WITH THE REQUIREMENTS OF FBC EB
 CHAPTER 10 AS APPLICABLE.
  
 3. THIS APPEARS TO INCLUDE AN ADDITION; REVISE TO
 INCLUDE THIS INFORMATION, FBC EB CHAPTER 11. AN
 ACCURATE PLAN REVIEW WITH CORRECT CODE REFERENCES
 CANNOT BE DONE AT THIS TIME. THEREFORE, A GENERAL PLAN
 REVIEW WILL BE PERFORMED.
  
 4. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107, FBC B TABLE 602, TABLE 705.8.
  
 5. FBC B 1008.2, 1008.1.10, OCCUPANT LOAD THAT THE GATE
 SERVES IS NOT CLEAR. EXIT STRATEGY NOT CLEAR. IT
 APPEARS THAT TWO EXITS ARE REQUIRED, BUT THE REAR EXIT
 DOOR APPEARS TO ROUTE THE OCCUPANT TO THE FRONT EXIT.
  
 REVISE PLAN TO SHOW THE TWO EXITS REQUIRED, CONTINUOUS
 TO THE PUBLIC WAY. IF THE PLAN IS NOT REVISED TO
 INCLUDE THE PATIO GATE AS HAVING PANIC BARS AND
 UTILIZED AS THE SECOND EXIT, SEND THE PROPOSED LIFE
 SAFETY PLAN VIA EMAIL FOR PRELIMINARY REVIEW.
  
 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. PROVIDE A COPY OF THE COST BREAKDOWN FOR THIS JOB.
 VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD, PROFIT,
 DESIGN FEES, EVEN IF PROVIDED BY OTHERS. VALUE APPEARS
 TOO LOW.
  
 7. FBC A 220.1.1, IT APPEARS THAT INTENT IS THAT
 VERTICAL ACCESSIBILITY WILL NOT BE PROVIDED TO THE
 MEZZANINE. REVISE PLAN TO CLARIFY UNDER WHICH EXEMPTION
 THIS FALLS. REVISE PLAN TO CLARIFY THAT THE PROPOSED
 SPACE MEETS ALL OF THE REQUIREMENTS OF SELECTED
 EXEMPTION(S).
  
 8. NO EXIT SIGNS ARE SHOWN IN THE PATIO; REVISE TO ADD,
 FBC 1011.1.
  
 9. FBC 1003.6, SOFT SEATING 101 TO PATIO, FBC B 1003.6,
 IT IS NOT CLEAR IF THE FOLDING DOOR COMPLIES WITH THE
 REQUIREMENTS OF CHAPTER 10. FBC B 1004.5, B 1027.1, IT
 APPEARS THAT THE OCCUPANT, AFTER BEING DIRECTED TO THE
 REAR EXIT DOOR, IS FORCED TO REENTER THE BUILDING.
  
 10. FBC B CHAPTER 2, 505, THE PROPOSED MEZZANINE DOES
 NOT APPEAR TO MEET THE DEFINITION OF A MEZZANINE;
 REVISE.
  
 11. FBC 107, ACCESS TO PROPOSED MEZZANINE, REVISE PLAN
 TO INCORPORATE EXCEPTIONS.
  
 12. FBC A 902, 904, REVISE PLAN TO SHOW COMPLIANCE WITH
 DINING SURFACE REQUIREMENTS.
  
 13. PRODUCT APPROVAL REQUIRED FOR COMPONENTS AND
 CLADDING, INCLUDING THE ROOF HATCH, FBC B 1609. THIS
 MAY BE SUBMITTED AS A REVISION AFTER PERMIT ISSUANCE,
 PRIOR TO INSTALLATION. PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, FBC
 107.
  
 14. ACCESSIBLE ROUTE FROM THE PARKING SPACE TO THE
 ALTERED AREA NOT CLEAR; REVISE PLAN TO CLARIFY, FBC A
 202.3, CHAPTER 4.
  