Plan Review Notes For Permit 17020981 |
Permit Number |
17020981 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-07 15:36:25 | 1. A VENT IS REQUIRED DOWN STREAM OF OIL SEPARATOR PER | | FBC PL 901.2 TRAP SEAL PROTECTION. | | THE PLUMBING SYSTEM SHALL BE PROVIDED WITH A SYSTEM OF | | VENT PIPING THAT WILL PERMIT THE ADMISSION OR EMISSION | | OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP SHALL NOT | | BE SUBJECTED TO A PNEUMATIC PRESSURE DIFFERENTIAL OF | | MORE THAN 1 INCH OF WATER COLUMN (249 PA). | | | | 901.2.1 VENTING REQUIRED. | | TRAPS AND TRAPPED FIXTURES SHALL BE VENTED IN | | ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN | | THIS CHAPTER. | | | | 2. TEMPERED WATER REQUIRED AT LAVATORY'S PER FBC PL | | 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING | | FACILITIES. | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | 1070 OR CSA B125.3. |
|