Plan Review Notes
Plan Review Notes For Permit 17020981
Permit Number 17020981
Review Stop P
Sequence Number 1
Notes
Date Text
2017-03-07 15:36:251. A VENT IS REQUIRED DOWN STREAM OF OIL SEPARATOR PER
 FBC PL 901.2 TRAP SEAL PROTECTION.
 THE PLUMBING SYSTEM SHALL BE PROVIDED WITH A SYSTEM OF
 VENT PIPING THAT WILL PERMIT THE ADMISSION OR EMISSION
 OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP SHALL NOT
 BE SUBJECTED TO A PNEUMATIC PRESSURE DIFFERENTIAL OF
 MORE THAN 1 INCH OF WATER COLUMN (249 PA).
  
 901.2.1 VENTING REQUIRED.
 TRAPS AND TRAPPED FIXTURES SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
  
 2. TEMPERED WATER REQUIRED AT LAVATORY'S PER FBC PL
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.