2017-03-01 17:43:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020981
 3/1/17
  
 1) PLEASE ADJUST THE AC COOLING AND HEATING
 CALCULATIONS USING THE SUMMER AND WINTER DRY BULB
 TEMPERATURES LISTRED IN ACCA MANUAL N- 90 DEGREES AND
 47 DEGREES.
  
 2) THE MAIN TRUCKS FOR AHU-1 & 2 APPEAR TO BE
 UNDERSIZED WHEN CHECKING THEM WITH THE TRANE DUCTULATOR
 USING A FRICTION LOSS OF 0.1. CLARIFY HOW THE TRUNKS
 WERE SIZED.
  
 3) INDICATE THE TYPE OF DUCTWORKWORK TO BE INSTALLED
 AND PROVIDE HANGING DETAILS PER SMACNA STANDARDS.
  
 4) EXHAUST VENTILATION IS REQUIRED FOR THE JANITOR'S
 CLOSET- TABLE 6-4 ASHRAE 62-1
  
 5) PROVIDE PROTECTION FOR THE O/A INTAKE OPENINGS IN
 ACCORDANCE WITH SECTION 401.5. IF A LOUVER IS TO BE
 USED, PLEASE SUBMIT A FL. PRODUCT APPROVAL AND/OR A
 MIAMI-DADE NOA.
  
 6) REFER TO SECTION C101.4.5 FBC-14 ENERGY CONSERVATION
 AND PROVIDE COMPLIANCE DOCUMENTATION FOR THE NEW
 CONDITIONED STORAGE ROOM- SEE SECTION C401.2 FOR
 COMPLIANCE PATH INFORMATION.
  