Plan Review Notes For Permit 17020981 |
Permit Number |
17020981 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-01 17:43:08 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17020981 | | 3/1/17 | | | | 1) PLEASE ADJUST THE AC COOLING AND HEATING | | CALCULATIONS USING THE SUMMER AND WINTER DRY BULB | | TEMPERATURES LISTRED IN ACCA MANUAL N- 90 DEGREES AND | | 47 DEGREES. | | | | 2) THE MAIN TRUCKS FOR AHU-1 & 2 APPEAR TO BE | | UNDERSIZED WHEN CHECKING THEM WITH THE TRANE DUCTULATOR | | USING A FRICTION LOSS OF 0.1. CLARIFY HOW THE TRUNKS | | WERE SIZED. | | | | 3) INDICATE THE TYPE OF DUCTWORKWORK TO BE INSTALLED | | AND PROVIDE HANGING DETAILS PER SMACNA STANDARDS. | | | | 4) EXHAUST VENTILATION IS REQUIRED FOR THE JANITOR'S | | CLOSET- TABLE 6-4 ASHRAE 62-1 | | | | 5) PROVIDE PROTECTION FOR THE O/A INTAKE OPENINGS IN | | ACCORDANCE WITH SECTION 401.5. IF A LOUVER IS TO BE | | USED, PLEASE SUBMIT A FL. PRODUCT APPROVAL AND/OR A | | MIAMI-DADE NOA. | | | | 6) REFER TO SECTION C101.4.5 FBC-14 ENERGY CONSERVATION | | AND PROVIDE COMPLIANCE DOCUMENTATION FOR THE NEW | | CONDITIONED STORAGE ROOM- SEE SECTION C401.2 FOR | | COMPLIANCE PATH INFORMATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|