2017-12-11 09:14:36 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| 2ND ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS |
| BELOW. |
| |
| COMMENTS CORRECTED HAVE BEEN NOTED, REMAINING COMMENTS |
| ARE NOT ADDRESSED SATISFACTORILY. SEE ADDITIONAL |
| COMMENTARY IN PARENTHESES. |
| |
| 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL, INDICATING |
| THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI |
| OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH |
| CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2, |
| RE3902 (THERE IS NO PANEL SCHEDULE FOR THE FUTURE |
| PANEL. ANY FUTURE PANEL WOULD LIKELY OVERLOAD THE |
| SERVICE, SINCE THE PROVIDED LOAD CALCULATION IS AT 182 |
| AMPS ON A 200 AMP SERVICE. PROVIDE PANEL SCHEDULE WITH |
| LOAD, OR REMOVE FROM PLAN. NEC 220; FBC 107.2.1) |
| 2. CORRECTED. |
| 3. RISER DIAGRAM SHOWS TWO 100 AMP SUB-PANELS, BUT ONLY |
| ONE IS SHOWN ON POWER PLAN. PROVIDE LOCATION OF ALL |
| SUB-PANELS. FBC 107.2.1 (PLAN NOW SHOWS AN ATS ADJACENT |
| TO METER AND A 200 AMP PANEL INSIDE THE GARAGE, BUT |
| THIS PANEL IS NOT LABELED. IS THE ATS ALSO A PANEL, OR |
| JUST AN ATS WITH MAIN BREAKER AS SHOWN? WHERE IS PANEL |
| A AND PANEL B? RISER SHOWS ITEMS BEING FED FROM PANEL B |
| THAT ARE LOCATED IN THE PANEL SCHEDULE FOR PANEL A. |
| PLAN IS REQUIRED TO BE ACCURATE. PROVIDE CORRECTIONS. |
| FBC 107.2.1) |
| 4. CORRECTED. |
| 5. CORRECTED. |
| 6.CORRECTED. |
| 7.CORRECTED. |
| 8. CORRECTED. |
| 9. CORRECTED. |
| 10. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED |
| TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON |
| RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC |
| 107.2.1, FS 471, 481 (A LETTER STATING THAT SOMEONE |
| DESIGNED THE PLAN IS NOT SUFFICIENT. THE PLAN MUST BE |
| SIGNED BY THE PERSON RESPONSIBLE FOR THE DESIGN, WITH |
| THAT PERSON'S INFORMATION SHOWN ON PLAN.) |
| 11. NEW COMMENT: RISER SHOWS THE FEED TO PANEL B AS TWO |
| 2/0 AND ONE 1/0 COPPER WIRE. THIS CONDUIT REQUIRES AN |
| EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTIONS. NEC |
| 310.15, 250.120, 122 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |