2017-10-24 17:03:36 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA |
| (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS |
| A5 WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY |
| OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN |
| ADDITIONAL 12 INCHES OF FREEBOARD REQUIRING THE DESIGN |
| FLOOD ELEVATION (DFE) TO BE 8. 0 FEET. PLEASE NOTE THIS |
| INFORMATION ON YOUR PLANS. |
| |
| A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS |
| REQUIRED AT TIME OF PERMIT APPLICATION. |
| NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS |
| SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NGVD. |
| |
| AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS |
| RECOMMENDED. |
| |
| A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS |
| REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL |
| PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY. |
| |
| 1612.1 GENERAL. |
| WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION |
| 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES |
| AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING |
| SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL |
| DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED |
| AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS |
| AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE |
| THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED |
| WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL |
| APPLY. |
| |
| 1612.4 DESIGN AND CONSTRUCTION. |
| THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES |
| LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH |
| HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF |
| ASCE 7 AND WITH ASCE 24. |
| |
| FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) & |
| R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND |
| STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS |
| COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED |
| TO OR ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE FLOOD |
| DESIGN INFORMATION ON THE PROPOSED SURVEY AND PROVIDE |
| FLOOD ELEVATION CERTIFICATE. |
| |
| G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. |
| FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION |
| SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO |
| THE FOLLOWING: |
| |
| 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY |
| WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS |
| TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF |
| FLOODWATERS. |
| |
| |
| |