Plan Review Notes For Permit 17020950
Permit Number 17020950
Review Stop E
Sequence Number 1
Notes
Date Text
2017-10-05 13:02:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL, INDICATING
 THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI
 OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH
 CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2,
 RE3902
 2. RISER DIAGRAM SHOWS TWO 100 AMP SUB-PANELS FED WITH
 #8 WIRE. #8 WIRE IS NOT RATED FOR 100 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16); FBC RE TABLE E3705.1
 3. RISER DIAGRAM SHOWS TWO 100 AMP SUB-PANELS, BUT ONLY
 ONE IS SHOWN ON POWER PLAN. PROVIDE LOCATION OF ALL
 SUB-PANELS. FBC 107.2.1
 4. GARAGE DOOR OPENER OUTLET REQUIRES GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE3902.2
 5. PLAN SHOWS 2 DISHWASHERS, BUT I ONLY SEE ONE
 INCLUDED IN THE LOAD CALCULATION. PROVIDE ACCURATE LOAD
 CALCULATION. NEC 220; FBC RE3902.3
 6. KITCHEN ISLAND RECEPTACLES REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.6
 7. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
 8. LIGHTING IN CLOSETS IS SHOWN AS STANDARD RECESS
 LIGHTS. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. ALSO, CORRECT NOTE THAT STATES LIGHTING IN
 CLOSETS TO COMPLY WITH SECTION 4108, THIS SECTION DOES
 NOT EXIST IN THE NEC . NEC 410.16; FBC RE4003.12; FBC
 107.2.1
 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 10. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER