Date |
Text |
2017-10-05 13:02:33 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL, INDICATING |
| THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI |
| OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH |
| CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2, |
| RE3902 |
| 2. RISER DIAGRAM SHOWS TWO 100 AMP SUB-PANELS FED WITH |
| #8 WIRE. #8 WIRE IS NOT RATED FOR 100 AMPS. PROVIDE |
| CORRECTION. NEC 310.15(B)(16); FBC RE TABLE E3705.1 |
| 3. RISER DIAGRAM SHOWS TWO 100 AMP SUB-PANELS, BUT ONLY |
| ONE IS SHOWN ON POWER PLAN. PROVIDE LOCATION OF ALL |
| SUB-PANELS. FBC 107.2.1 |
| 4. GARAGE DOOR OPENER OUTLET REQUIRES GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE3902.2 |
| 5. PLAN SHOWS 2 DISHWASHERS, BUT I ONLY SEE ONE |
| INCLUDED IN THE LOAD CALCULATION. PROVIDE ACCURATE LOAD |
| CALCULATION. NEC 220; FBC RE3902.3 |
| 6. KITCHEN ISLAND RECEPTACLES REQUIRE GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.6 |
| 7. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF |
| EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1 |
| 8. LIGHTING IN CLOSETS IS SHOWN AS STANDARD RECESS |
| LIGHTS. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY |
| ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS |
| SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE |
| CORRECTION. ALSO, CORRECT NOTE THAT STATES LIGHTING IN |
| CLOSETS TO COMPLY WITH SECTION 4108, THIS SECTION DOES |
| NOT EXIST IN THE NEC . NEC 410.16; FBC RE4003.12; FBC |
| 107.2.1 |
| 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC CE R404.1 |
| 10. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED |
| TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON |
| RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC |
| 107.2.1, FS 471, 481 |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |