2017-03-06 17:06:20PLAN DENIED
 1) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 # 2 TRANSFER GRILLS. MISSING RETURN IN UP STARS BEDROOM
 2) AIR HANDLER #2 PLAN SHOWS IN ATTIC NOTES SAY IN
 CLOSET.
 3) IF AIR HANDLER IS IN ATTIC REFER TO SECTION R403.2.4
 FLORIDA ENERGY CODE 2014. SHOW ATTIC ACCESS ON PLAN
 4) PLEAS SHOW BB GRILLS ON DIFFUSER SCHEDULE.
  