2017-03-07 15:02:39INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS; SEE VERBIAGE IN CODE.
 3. PLEASE SUBMIT REVISED ELECTRICAL CALCULATIONS AT THE
 SERVICE AND SHOW THE EXISTING SERVICE CONDUCTOR SIZE.
 FBC 107.3.5
 4. SHOW ON PANEL SCHEDULE AND FLOOR PLAN THE REQUIRED
 SHOW WINDOW RECEPTACLES PER NEC 210.62 AND NEC 220.43
 5. PER NEC 600.5 SHOW THE REQUIRED BRANCH CIRCUIT FOR
 SIGNAGE AND REFLECT ON PANEL SCHEDULE. FBC 107.3.5
 6. PROVIDE AND LABEL THE DRINKING FOUNTAIN WITH GFCI
 PROTECTION TO BE READILY ACCESSIBLE (AT THE PANEL
 BOARD). NEC 422.52
 7. LABEL THE RISER DIAGRAM MAINS, 1 OF 4, 2OF 4 TO
 COMPLY WITH NEC 230.2E, IDENTIFICATION.
 8. ADDRESS FIRE, BUILDING AND PLUMBING RELATED TO THE
 ELECTRICAL SCOPE OF WORK.
 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  