2017-03-07 15:02:39 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW |
| VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. |
| 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO |
| INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD |
| MARKINGS; SEE VERBIAGE IN CODE. |
| 3. PLEASE SUBMIT REVISED ELECTRICAL CALCULATIONS AT THE |
| SERVICE AND SHOW THE EXISTING SERVICE CONDUCTOR SIZE. |
| FBC 107.3.5 |
| 4. SHOW ON PANEL SCHEDULE AND FLOOR PLAN THE REQUIRED |
| SHOW WINDOW RECEPTACLES PER NEC 210.62 AND NEC 220.43 |
| 5. PER NEC 600.5 SHOW THE REQUIRED BRANCH CIRCUIT FOR |
| SIGNAGE AND REFLECT ON PANEL SCHEDULE. FBC 107.3.5 |
| 6. PROVIDE AND LABEL THE DRINKING FOUNTAIN WITH GFCI |
| PROTECTION TO BE READILY ACCESSIBLE (AT THE PANEL |
| BOARD). NEC 422.52 |
| 7. LABEL THE RISER DIAGRAM MAINS, 1 OF 4, 2OF 4 TO |
| COMPLY WITH NEC 230.2E, IDENTIFICATION. |
| 8. ADDRESS FIRE, BUILDING AND PLUMBING RELATED TO THE |
| ELECTRICAL SCOPE OF WORK. |
| 9. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| THIS PROJECT. |
| |
| |