2017-03-01 16:24:25 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17020920 |
| ADD: 1236 PALM BEACH LAKES BLVD. |
| CONT: H. A. CONTRACTING |
| TEL: 305-591-9818 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. MARCH 01/ 2017 |
| ACTION: DENIED |
| |
| 1) THE LIFE SAFETY PLAN LS-201: |
| 1A) PLEASE SHOW IN THE LIFE SAFETY PLAN EGRESS AISLES |
| SALES DISPLAYS, KIOSK, COUNTERS, STANDS AND CHECK OUT |
| COUNTERS. 1001.4 FIRE SAFETY AND EVACUATION PLANS. FIRE |
| SAFETY AND EVACUATION PLANS SHALL BE PROVIDED FOR ALL |
| OCCUPANCIES AND BUILDINGS WHERE REQUIRED BY THE FLORIDA |
| FIRE PREVENTION CODE. SUCH FIRE SAFETY AND EVACUATION |
| PLANS SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF |
| THE FLORIDA FIRE PREVENTION CODE. |
| |
| 1B) PLEASE PROVIDE COMPLIANCE WITH THE 2014 |
| FBC-ACCESSIBILITY CODE SECTION 206.4.1 PUBLIC |
| ENTRANCES. |
| IN ADDITION TO ENTRANCES REQUIRED BY 206.4.2 THROUGH |
| 206.4.9, AT LEAST 60 PERCENT OF ALL PUBLIC ENTRANCES |
| SHALL COMPLY WITH 404. |
| BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND EXITS OF |
| BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS WITH THE |
| GENERAL PUBLIC THAT ARE EXISTING, UNDER CONSTRUCTION, |
| OR UNDER CONTRACT FOR CONSTRUCTION WHICH WOULD PREVENT |
| A PERSON FROM USING SUCH ENTRANCES OR EXITS SHALL BE |
| REMOVED. |
| NEITHER ENTRY IS A CODE COMPLIANT ACCESSIBLE ENTRY, 2 |
| ARE REQUIRED. |
| |
| 1C) THE PERMIT APPLICATION INDICATES THE VALUE OF |
| PROPOSED WORK UNDER THIS PERMIT IS $50,000.00. |
| DISPROPORTIONATE COST WOULD REQUIRE UP TO $10,000.00 |
| DOLLARS OF VALUE TO BE SPENT IN THIS ORDER. |
| 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 2) ACCESS. CODE 904.1. CHECK-OUT AISLES AND SALES AND |
| SERVICE COUNTERS SHALL COMPLY WITH THE APPLICABLE |
| REQUIREMENTS OF 904. |
| |
| 904.2 APPROACH. ALL PORTIONS OF COUNTERS REQUIRED TO |
| COMPLY WITH 904 SHALL BE LOCATED ADJACENT TO A WALKING |
| SURFACE COMPLYING WITH 403. |
| |
| 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND |
| SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. |
| THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND |
| THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP. |
| |
| 3) SHEET D-201 IN THE NOTES 1 & 3 BOTH INDICATE THE |
| REMOVAL OF WINDOW AND EXTERIOR DOORS. PLEASE PROVIDE |
| COMPLIANCE WITH: 2014 FBC-B 1609.1.2 PROTECTION OF |
| OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| |
| 4) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 5) SHEET S-001 INDICATES THE STRUCTURAL COMPONENTS FOR |
| THE NEW EXTERIOR DOOR OPENINGS, BUT THE PLANS ARE |
| SILENT AS TO WHAT STRUCTURAL REQUIREMENTS ARE REQUIRED |
| FOR UNDER THE WINDOWS SILLS, BOND BEAMS, BLOCK WORK AND |
| RE-ENFORCING STEEL WILL BE REQUIRED. THIS IS PART OF |
| THE MWFRS (MAIN WIND FORCE RESISTING SYSTEM). |
| |
| 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |