Notes
Date Text
2017-03-27 13:20:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, DESIGNER OF RECORD IS TO REVIEW PRODUCT
 APPROVALS AND DELEGATED ENGINEERING PRIOR TO SUBMITTAL.
  
 2ND REVIEW, NOT ADDRESSED. THE DESIGNER OF RECORD IS TO
 REVIEW THE PRODUCT APPROVALS, EITHER WITH A SHOP
 DRAWING REVIEW STAMP OR A LETTER. A REFERENCE TO A TYPE
 OF PRODUCT ON THE PLAN, UNLESS IT SPECIFICALLY
 REFERENCES THE MANUFACTURER AND PRODUCT, DOES NOT
 DEMONSTRATE THAT DOR HAS REVIEWED THE SPECIFIC PRODUCT
 AND METHOD OF INSTALLATION PROPOSED.
  
 2.OK
  
 3. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
 2ND REVIEW, NOT CLEAR WHAT SHOULD BE REVIEWED, NOT
 CLEAR WHAT IS PROPOSED TO BE ISSUED. NOTHING WAS MARKED
 VOID.
  
 4. THIS PERMIT WILL NOT BE ISSUED UNTIL THE MASTER IS
 ISSUED.
  
  