Plan Review Notes
Plan Review Notes For Permit 17020796
Permit Number 17020796
Review Stop P
Sequence Number 4
Notes
Date Text
2018-11-14 08:45:11PLUMBING PROVISOO:
  
 1. SHT. P-3.0.01 IN PROJECT DOX IS LABELED RISER
 DIAGRAM GRAVITY 2-4 FL NORTH THE PLAN SHEET IS THE
 RISER DIAGRAM 1ST FL SOUTH PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 2. SHT. P- 3.0.03 IN PROJECT DOX IS LABELED RISER
 DIAGRAM GRAVITY 2-4 FL SOUTH THE PLAN SHEET IT PLUMBING
 RISER PRESSURE 1ST FL SOUTH PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 3. SHT. P-3.0.04 IN PROJECT DOX IS LABELED RISER
 DIAGRAM PRESSURE 1ST FL NORTH THE PLAN SHEET IS THE
 SOUTH SIDE RISERS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 4. SHT P-1.3.01B LABEL THE SOIL STACKS IN THESE ROOMS
 TO MATCH SANITARY ISOMETRIC SOME ARE NOT LABELED SOME
 ARE LABELED AS WCO THE FOLLOWING ROOMS MAIN ELECTRICAL
 1151, NEXT TO CORRIDOR 1138, IN FRONT OF LIQUOR ROOM
 1129D, 1137, 1221 TOILET STALL, 223 TRIPLE SINK. . PER
 WPB AMEND TO FBC 107.2.1
 5. SHT. P-3.0.02A ON THE LEFT SIDE OF THE ISOMETRIC
 THERE IS A SOIL STACK LABELED S30 I COULD NOT FIND THAT
 RISER ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
 6. SHTS. P-3.0.01 AND P-3.0.02 ARE THE SAME DRAWING
 JUST DIFFERENT VERSIONS BOTH ISOMETRICS HAVE SOIL
 STACKS THAT ARE NOT LABELED AND FIXTURES THAT ARE NOT
 LABELED THESE ISSUES SHALL BE CLEARED UP BEFORE A
 PLUMBING PERMIT CAN BE ISSUED.
 7. SHTS. P-1.3.02A AND B THESE SHEETS WERE JUST
 UPLOADED TO SHOW THE CONDENSATE DRAIN IT APPEARS THAT
 THEY ARE SHOWING THE UNDERGROUND PIPING ON THE SECOND
 FLOOR IT SHOULD BE SHOWN ON THE 1ST FLOOR. PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 8. SHT. P-3.0.08 THE CONDENSATE ISOMETRIC DRAWING NORTH
 SIDE IS LABELED AS THE NATURAL GAS RISER . PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  