2018-11-13 12:47:27 | MECHANICAL PROVISOS: | | | | 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN | | EXHAUST HOODS, KITCHEN FIRE SUPPRESSION SYSTEMS, AND | | WALKIN COOLERS AND FREEZERS. | | | | 2) INCLUDED WITH THE KITCHEN EXHAUST HOOD DRAWINGS | | SHALL BE: A) INSTALLATION DETAILS FOR THE MAKEUP AIR | | AND EXHAUST FANS AND DUCTS INCLUDING HOW THE ALL | | COMPONENTS WILL BE SUPPORTED INSIDE THE ROOF STRUCTURE. | | B) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | INSTRUCTIONS FOR THE EXHAUST DUCT FIREWRAPPING. C) | | CLEARANCE DISTANCE MEASUREMENTS FOR THE GREASE EXHAUST | | TERMINATION TO VERIFY COMPLIANCE WITH REQUIRED | | CLEARANCES TO PARTS OF THE BUILDING- SECTION | | 506.3.13.3. D) VERIFICATION THAT THE TEMPORATURE OF THE | | MAKEUP AIR DOES NOT EXCEED 10 DEGREES OF THE AIR | | TEMPERATURE IN THE KITCHEN- SECTION 508.1.1. | | | | 3) DEFERRED SUBMITTALS: | | | | A) WIND LOAD ENGINEERING FOR INSTALLATION OF THE | | CHILLERS, PUMPS, AND OTHER ALL EXTERIOR MECHANICAL | | EQUIPMENT. | | B) MIAMI-DADE AND/OR FLORIDA PRODUCT APPROVALS FOR THE | | EXHAUST AND OUTDOOR AIR LOUVERS, INCLUDING | | MANUFACTURER'S SPECIFICATIONS. | | C) FIRE DAMPERS | | D) MOTORIZED DAMPERS. | | E) DUCT SMOKE DETECTORS. | | F) CHILLED WATER PIPING SPECIFICATIONS AND PIIPE | | INSULATIONS. | | G) FLAMEBAR DUCT INSTALLATION DETAILS. | | H) COMMISSSIONING REPORT AND ACKNOWLEDGEMENT LETTER | | FROM BUILDING OWNERSHIP. | | | | |
|