Plan Review Notes
Plan Review Notes For Permit 17020796
Permit Number 17020796
Review Stop G
Sequence Number 4
Notes
Date Text
2018-11-14 10:47:094TH REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
 1. SHT. P-3.0.07 THE GAS RISER DIAGRAM IS LABELED
 PRESSURE 2-4 FL SOUTH. PLEASE CLARIFY WPB AMEND TO FBC
 107.2.1
 2. SHT. P-3.0.07 UNDER THE EQUIPMENT SCHEDULE #304 THE
 BTU LOAD IS ILLEGIBLE. PLEASE CLARIFY WPB AMEND TO FBC
 107.2.1
 3. SHT. P-3.0.07 UNDER THE EQUIPMENT SCHEDULE # 2011,
 2014 AND 1002 ARE NOT SHOWN ON THE RISER DIAGRAM.
 PLEASE CLARIFY WPB AMEND TO FBC 107.2.1
 4. BELOW THE EQUIPMENT SCHEDULE THERE IS A NOTE
 REFERENCING THE KITCHEN CONSULTANT?S DRAWINGS FOR
 EQUIPMENT LOCATION AND FINAL LOADS. FOR THE GAS RISER
 IT IS REQUIRED THAT THE CORRECT BTU LOAD BE INDICATED
 ON THE PLAN AND THEY SHALL MATCH THE KITCHEN
 CONSULTANTS DRAWINGS. PLEASE CLARIFY WPB AMEND TO FBC
 107.2.1.
 5. SHT. P-3.0.07 THE BTU LOAD ON THE RISER FOR THE
 BANQUET KITCHEN DETAIL #D DOES NOT MATCH THE TOTAL FROM
 WHEN I ADDED UP THE EQUIPMENT SCHEDULE. PLEASE CLARIFY
 WPB AMEND TO FBC 107.2.1.
 6. SHT. P-3.0.07 THE BTU LOAD ON THE A BRANCH OFF THE
 MAIN DOES NOT MATCH THE BTU LOAD ON THE ENLARGED
 ISOMETRIC #A . PLEASE CLARIFY WPB AMEND TO FBC 107.2.1.
 7. SHT. P-3.0.07 THE BTU LOAD ON THE C BRANCH OFF THE
 MAIN DOES NOT MATCH THE BTU LOAD ON THE ENLARGED
 ISOMETRIC #C . PLEASE CLARIFY WPB AMEND TO FBC 107.2.1.
 8. SHT. P-3.0.07 WHEN I TOTALED UP THE BTU LOADS FROM
 THE EQUIPMENT SCHEDULE IT WAS 4,783,000 THE TOTAL GAS
 LOAD UNDER THE 1ST STAGE GAS LOAD CALCULATION WAS
 4,624,000 PLEASE CLARIFY WPB AMEND TO FBC 107.2.1.
  
 PREVIOUS COMMENTS 2. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE FBC-2014
 FUEL GAS CODE SEC. 304. PLEASE PROVIDE COMBUSTION AIR
 CALC FOR
 THE KITCHEN APPLIANCES.
 RESPONSE: GAS WATER HEATER IS DIRECT VENT/INTAKE.
 PLEASE CONFIRM REQUIREMENT OF CALCULATION.
 PLEASE REFER TO KITCHEN CONSULTANT FOR KITCHEN
 EQUIPMENT INFORMATION.
 THIS RESPONSE DOES NOT COMPLY PLEASE PROVIDE COMBUSTION
 AIR CALCULATIONS FOR THE KITCHENS THEY SHALL BE
 INCLUDED IN THE GAS OR MECHANICAL PLANS.
  
 PREVIOUS COMMENT 4. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA
 58, AND FBC-2014 FUEL GAS SEC. 402.2 WE NEED THESE TO
 VERIFY BTU
 LOADS-IF THEY CAN NOT BE PROVIDED FOR PLAN REVIEW PLACE
 A
 NOTE ON THE PLAN TO BE ON JOBSITE FOR FIRST ROUGH
 INSPECTION.
 RESPONSE: PLEASE REFER TO KITCHEN EQUIPMENT CONSULTANT
 PLANS FOR REFERENCE.
 THE RESPONSE DOES NOT COMPLY THE KITCHEN CONSULTANTS
 PLANS ARE NOT INCLUDED IN SUBMITTAL AND WE REQUIRE THE
 SPECIFICATION FROM THE APPLIANCE MANUFACTURE NOT THE
 CONSULTANT.
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  