2018-11-14 10:47:09 | 4TH REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| GAS COMMENTS: |
| 1. SHT. P-3.0.07 THE GAS RISER DIAGRAM IS LABELED |
| PRESSURE 2-4 FL SOUTH. PLEASE CLARIFY WPB AMEND TO FBC |
| 107.2.1 |
| 2. SHT. P-3.0.07 UNDER THE EQUIPMENT SCHEDULE #304 THE |
| BTU LOAD IS ILLEGIBLE. PLEASE CLARIFY WPB AMEND TO FBC |
| 107.2.1 |
| 3. SHT. P-3.0.07 UNDER THE EQUIPMENT SCHEDULE # 2011, |
| 2014 AND 1002 ARE NOT SHOWN ON THE RISER DIAGRAM. |
| PLEASE CLARIFY WPB AMEND TO FBC 107.2.1 |
| 4. BELOW THE EQUIPMENT SCHEDULE THERE IS A NOTE |
| REFERENCING THE KITCHEN CONSULTANT?S DRAWINGS FOR |
| EQUIPMENT LOCATION AND FINAL LOADS. FOR THE GAS RISER |
| IT IS REQUIRED THAT THE CORRECT BTU LOAD BE INDICATED |
| ON THE PLAN AND THEY SHALL MATCH THE KITCHEN |
| CONSULTANTS DRAWINGS. PLEASE CLARIFY WPB AMEND TO FBC |
| 107.2.1. |
| 5. SHT. P-3.0.07 THE BTU LOAD ON THE RISER FOR THE |
| BANQUET KITCHEN DETAIL #D DOES NOT MATCH THE TOTAL FROM |
| WHEN I ADDED UP THE EQUIPMENT SCHEDULE. PLEASE CLARIFY |
| WPB AMEND TO FBC 107.2.1. |
| 6. SHT. P-3.0.07 THE BTU LOAD ON THE A BRANCH OFF THE |
| MAIN DOES NOT MATCH THE BTU LOAD ON THE ENLARGED |
| ISOMETRIC #A . PLEASE CLARIFY WPB AMEND TO FBC 107.2.1. |
| 7. SHT. P-3.0.07 THE BTU LOAD ON THE C BRANCH OFF THE |
| MAIN DOES NOT MATCH THE BTU LOAD ON THE ENLARGED |
| ISOMETRIC #C . PLEASE CLARIFY WPB AMEND TO FBC 107.2.1. |
| 8. SHT. P-3.0.07 WHEN I TOTALED UP THE BTU LOADS FROM |
| THE EQUIPMENT SCHEDULE IT WAS 4,783,000 THE TOTAL GAS |
| LOAD UNDER THE 1ST STAGE GAS LOAD CALCULATION WAS |
| 4,624,000 PLEASE CLARIFY WPB AMEND TO FBC 107.2.1. |
| |
| PREVIOUS COMMENTS 2. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR PER THE FBC-2014 |
| FUEL GAS CODE SEC. 304. PLEASE PROVIDE COMBUSTION AIR |
| CALC FOR |
| THE KITCHEN APPLIANCES. |
| RESPONSE: GAS WATER HEATER IS DIRECT VENT/INTAKE. |
| PLEASE CONFIRM REQUIREMENT OF CALCULATION. |
| PLEASE REFER TO KITCHEN CONSULTANT FOR KITCHEN |
| EQUIPMENT INFORMATION. |
| THIS RESPONSE DOES NOT COMPLY PLEASE PROVIDE COMBUSTION |
| AIR CALCULATIONS FOR THE KITCHENS THEY SHALL BE |
| INCLUDED IN THE GAS OR MECHANICAL PLANS. |
| |
| PREVIOUS COMMENT 4. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA |
| 58, AND FBC-2014 FUEL GAS SEC. 402.2 WE NEED THESE TO |
| VERIFY BTU |
| LOADS-IF THEY CAN NOT BE PROVIDED FOR PLAN REVIEW PLACE |
| A |
| NOTE ON THE PLAN TO BE ON JOBSITE FOR FIRST ROUGH |
| INSPECTION. |
| RESPONSE: PLEASE REFER TO KITCHEN EQUIPMENT CONSULTANT |
| PLANS FOR REFERENCE. |
| THE RESPONSE DOES NOT COMPLY THE KITCHEN CONSULTANTS |
| PLANS ARE NOT INCLUDED IN SUBMITTAL AND WE REQUIRE THE |
| SPECIFICATION FROM THE APPLIANCE MANUFACTURE NOT THE |
| CONSULTANT. |
| |
| |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |