Plan Review Notes
Plan Review Notes For Permit 17020796
Permit Number 17020796
Review Stop M
Sequence Number 3
Notes
Date Text
2018-09-07 11:32:543RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17020796
 9/7/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE MATCH THE GUEST ROOM FC SYSTEM
 IDENTIFICATIONS ON THE AC AND ENERGY CALCULATIONS, AND
 THE SCHEDULE ON SHEET M-0.0.02. EACH DOCUMENT
 IDENTIFIES THEM DIFFERENTLY WHICH MAKES OT DIFFICULT TO
 REVIEW FOR COMPLIANCE. IT APPEARS THAT MANY OF THE
 SYSTEMS AS THEY ARE SHOWN IN THE CALCULATIONS ARE BEING
 GROUPED TOGETHER BUT THERE IS NO EXPALNATION OF HOW
 THEY ARE BEING GROUPED- PLEASE CLARIFY.
  
 2) THE PREVIOUSLY REQUESTED COMBUSTION AIR CALCULATIONS
 FOR THE GAS-FIRED COOKING APPLIANCES WERE NOT PROVIDED.
  
 3) SHEET M-1.3.01B: THE VENTILATION CA;LCULATION FOR
 THE WOMEN'S LOCKER ROOM IS INCORRECTLY LISTED AT 170
 CFMS , HOWEVER 204 CFMS ARE REQUIRED.
  
 4) M-1.3.01B & M-1.4.01: IT APPEARS THAT RECIRCULATION
 OF THE AIR FROM THE MANI/PEDI ROOM IS BEING
 RECIRCULATED TO OTHER ROOMS AND SPACES VIA THE RETURN
 TRANSFER FROM THE ROOM INTO THE PLENUM WHICH IS
 PROHIBITED PER TABLE 403.3 FOOTNOTE B.
  
 5) M-1.3.01B & M-1.4.01: THE MANI/PEDI PLAN DOES NOT
 INDICATE THAT SOURCE CAPTURE SYSTEMS ARE TO BE
 INSTALLED AT EACH MANICURE TABLE AND PEDICURE CHAIR-
 TABLE 403.3 FOOTNOTE
  
 6) M-1.3.01B: VENTILATION IS REQUIRED FOR THE FIRE PUMP
 ROOM- SECTIONS 4.12.6 & 11.3.2.1 NFPA 20.
  
 7) M-1.3.01B: FIRE DAMPERS MISSING AT: A) 20X14 SUPPLY
 DUCT PENETRATING THE BOH CORRIDOR WALL. B) THE 30X14
 SUPPLY AND RETURN DUCTS PENETRATING MECH RM 1205 WALLS-
 SECTION 607.5.2.
  
 8) PROVIDE AN AC CONDENSATE PIPING PLAN AND RISER
 DRAWING- SECTION 307.
  
 9) PROVIDE UL APPROVED FIRESTOPPING SYSTEMS FOR THE
 CHILLED WATER PIPING AND CONDENSATE PIPING.
  
 10) REFER TO SECTION 3004.1 FBC-14 BUILDING AND
 INDICATE HOW THE ELEVATOR HOISTWAYS ARE BEING VENTED.
  
 11) REFER TO SECTIONS C408.1 & C408.2 FBC-14 ENERGY
 CONSERVATION: COMMISSIONING OF THE MECHANICAL AND
 ELECTRICAL POWER AND LIGHTING SYSTEMS IS REQUIRED.
  
 C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION
 REQUIREMENTS.
 PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE
 REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE
 OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN
 ACCORDANCE THE PROVISIONS OF THIS SECTION.
  
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE
 GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE
 OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS
 C408.2.4 AND C408.2.5.
  
  
 ADVISORIES:
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOODS, KITCHEN FIRE SUPPRESSION SYSTEMS, WALKIN
 COOLERS AND FREEZERS, FIRE ALARM, FIRE SPRINKLER.
  
 2) INCLUDED WIH THE KITCHEN EXHAUST HOOD DRAWINGS SHALL
 BE: A) INSTALLATION DETAILS FOR THE MAKEUP AIR AND
 EXHAUST FANS AND DUCTS INCLUDING HOW THE ALL COMPONENTS
 WILL BE SUPPORTED INSIDE THE ROOF STRUCTURE. B)
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE EXHAUST DUCT FIREWRAPPING. C)
 CLEARANCE DISTANCE MEASUREMENTS FOR THE GREASE EXHAUST
 TERMINATION TO VERIFY COMPLIANCE WITH REQUIRED
 CLEARANCES TO PARTS OF THE BUILDING- SECTION
 506.3.13.3. D) VERIFICATION THAT THE TEMPORATURE OF THE
 MAKEUP AIR DOES NOT EXCEED 10 DEGREES OF THE AIR
 TEMPERATURE IN THE KITCHEN- SECTION 508.1.1.
  
 3) DEFERRED SUBMITTALS:
  
 A) WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 CHILLERS, PUMPS, AND OTHER ALL EXTERIOR MECHANICAL
 EQUIPMENT.
 B) MIAMI-DADE AND/OR FLORIDA PRODUCT APPROVALS FOR THE
 EXHAUST AND OUTDOOR AIR LOUVERS, INCLUDING
 MANUFACTURER'S SPECIFICATIONS.
 C) FIRE DAMPERS
 D) MOTORIZED DAMPERS.
 E) DUCT SMOKE DETECTORS.
 F) CHILLED WATER PIPING SPECIFICATIONS AND PIIPE
 INSULATIONS.
 G) FLAMEBAR DUCT INSTALLATION DETAILS.
 H) COMMISSSIONING REPORT AND ACKNOWLEDGEMENT LETTER
 FROM BUILDING OWNERSHIP.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  