2018-09-07 11:32:54 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| CODES |
| PERMIT #17020796 |
| 9/7/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE MATCH THE GUEST ROOM FC SYSTEM |
| IDENTIFICATIONS ON THE AC AND ENERGY CALCULATIONS, AND |
| THE SCHEDULE ON SHEET M-0.0.02. EACH DOCUMENT |
| IDENTIFIES THEM DIFFERENTLY WHICH MAKES OT DIFFICULT TO |
| REVIEW FOR COMPLIANCE. IT APPEARS THAT MANY OF THE |
| SYSTEMS AS THEY ARE SHOWN IN THE CALCULATIONS ARE BEING |
| GROUPED TOGETHER BUT THERE IS NO EXPALNATION OF HOW |
| THEY ARE BEING GROUPED- PLEASE CLARIFY. |
| |
| 2) THE PREVIOUSLY REQUESTED COMBUSTION AIR CALCULATIONS |
| FOR THE GAS-FIRED COOKING APPLIANCES WERE NOT PROVIDED. |
| |
| 3) SHEET M-1.3.01B: THE VENTILATION CA;LCULATION FOR |
| THE WOMEN'S LOCKER ROOM IS INCORRECTLY LISTED AT 170 |
| CFMS , HOWEVER 204 CFMS ARE REQUIRED. |
| |
| 4) M-1.3.01B & M-1.4.01: IT APPEARS THAT RECIRCULATION |
| OF THE AIR FROM THE MANI/PEDI ROOM IS BEING |
| RECIRCULATED TO OTHER ROOMS AND SPACES VIA THE RETURN |
| TRANSFER FROM THE ROOM INTO THE PLENUM WHICH IS |
| PROHIBITED PER TABLE 403.3 FOOTNOTE B. |
| |
| 5) M-1.3.01B & M-1.4.01: THE MANI/PEDI PLAN DOES NOT |
| INDICATE THAT SOURCE CAPTURE SYSTEMS ARE TO BE |
| INSTALLED AT EACH MANICURE TABLE AND PEDICURE CHAIR- |
| TABLE 403.3 FOOTNOTE |
| |
| 6) M-1.3.01B: VENTILATION IS REQUIRED FOR THE FIRE PUMP |
| ROOM- SECTIONS 4.12.6 & 11.3.2.1 NFPA 20. |
| |
| 7) M-1.3.01B: FIRE DAMPERS MISSING AT: A) 20X14 SUPPLY |
| DUCT PENETRATING THE BOH CORRIDOR WALL. B) THE 30X14 |
| SUPPLY AND RETURN DUCTS PENETRATING MECH RM 1205 WALLS- |
| SECTION 607.5.2. |
| |
| 8) PROVIDE AN AC CONDENSATE PIPING PLAN AND RISER |
| DRAWING- SECTION 307. |
| |
| 9) PROVIDE UL APPROVED FIRESTOPPING SYSTEMS FOR THE |
| CHILLED WATER PIPING AND CONDENSATE PIPING. |
| |
| 10) REFER TO SECTION 3004.1 FBC-14 BUILDING AND |
| INDICATE HOW THE ELEVATOR HOISTWAYS ARE BEING VENTED. |
| |
| 11) REFER TO SECTIONS C408.1 & C408.2 FBC-14 ENERGY |
| CONSERVATION: COMMISSIONING OF THE MECHANICAL AND |
| ELECTRICAL POWER AND LIGHTING SYSTEMS IS REQUIRED. |
| |
| C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION |
| REQUIREMENTS. |
| PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE |
| REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE |
| OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN |
| ACCORDANCE THE PROVISIONS OF THIS SECTION. |
| |
| CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE |
| PROVISIONS FOR COMMISSIONING AND COMPLETION |
| REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE |
| PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER |
| REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE |
| GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE |
| OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS |
| C408.2.4 AND C408.2.5. |
| |
| |
| ADVISORIES: |
| |
| 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| EXHAUST HOODS, KITCHEN FIRE SUPPRESSION SYSTEMS, WALKIN |
| COOLERS AND FREEZERS, FIRE ALARM, FIRE SPRINKLER. |
| |
| 2) INCLUDED WIH THE KITCHEN EXHAUST HOOD DRAWINGS SHALL |
| BE: A) INSTALLATION DETAILS FOR THE MAKEUP AIR AND |
| EXHAUST FANS AND DUCTS INCLUDING HOW THE ALL COMPONENTS |
| WILL BE SUPPORTED INSIDE THE ROOF STRUCTURE. B) |
| MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| INSTRUCTIONS FOR THE EXHAUST DUCT FIREWRAPPING. C) |
| CLEARANCE DISTANCE MEASUREMENTS FOR THE GREASE EXHAUST |
| TERMINATION TO VERIFY COMPLIANCE WITH REQUIRED |
| CLEARANCES TO PARTS OF THE BUILDING- SECTION |
| 506.3.13.3. D) VERIFICATION THAT THE TEMPORATURE OF THE |
| MAKEUP AIR DOES NOT EXCEED 10 DEGREES OF THE AIR |
| TEMPERATURE IN THE KITCHEN- SECTION 508.1.1. |
| |
| 3) DEFERRED SUBMITTALS: |
| |
| A) WIND LOAD ENGINEERING FOR INSTALLATION OF THE |
| CHILLERS, PUMPS, AND OTHER ALL EXTERIOR MECHANICAL |
| EQUIPMENT. |
| B) MIAMI-DADE AND/OR FLORIDA PRODUCT APPROVALS FOR THE |
| EXHAUST AND OUTDOOR AIR LOUVERS, INCLUDING |
| MANUFACTURER'S SPECIFICATIONS. |
| C) FIRE DAMPERS |
| D) MOTORIZED DAMPERS. |
| E) DUCT SMOKE DETECTORS. |
| F) CHILLED WATER PIPING SPECIFICATIONS AND PIIPE |
| INSULATIONS. |
| G) FLAMEBAR DUCT INSTALLATION DETAILS. |
| H) COMMISSSIONING REPORT AND ACKNOWLEDGEMENT LETTER |
| FROM BUILDING OWNERSHIP. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |