Plan Review Notes
Plan Review Notes For Permit 17020796
Permit Number 17020796
Review Stop E
Sequence Number 3
Notes
Date Text
2018-08-24 12:29:00REVIEWED PER PREVIOUS COMMENTS ONLY.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. REVISION SHOWS MAIN #1 AS 1200 AMPS. THE FEEDERS TO
 THIS MAIN ARE SHOWN AS 3 SETS OF 400KCMIL COPPER, WHICH
 HAS AN AMPACITY OF 1005 AMPS. PROVIDE CORRECTION. NEC
 240.4(C)
 2. NOTE 12 ON RISER DIAGRAM SHOWS THE GENERATOR AS A
 120/208 VOLT, 3 PHASE GENERATOR. HOWEVER, THIS
 GENERATOR IS SHOWN FEEDING 277/480 VOLT, 3 PHASE LOADS.
 PROVIDE CORRECTION. WPB FBC 107.2.1
 3. EXPANDED VIEW OF MAIN ELECTRICAL ROOM, IN THE
 EMERGENCY AREA, PLAN DOES NOT SHOW THE REQUIRED 4 FEET
 OF CLEARANCE BETWEEN PANELS AND ATS. PROVIDE
 CORRECTION. NEC 110.26(A)(1)
  
 ALL OTHER COMMENTS HAVE BEEN ADDRESSED SATISFACTORILY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  