2018-08-24 12:29:00 | REVIEWED PER PREVIOUS COMMENTS ONLY. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. REVISION SHOWS MAIN #1 AS 1200 AMPS. THE FEEDERS TO |
| THIS MAIN ARE SHOWN AS 3 SETS OF 400KCMIL COPPER, WHICH |
| HAS AN AMPACITY OF 1005 AMPS. PROVIDE CORRECTION. NEC |
| 240.4(C) |
| 2. NOTE 12 ON RISER DIAGRAM SHOWS THE GENERATOR AS A |
| 120/208 VOLT, 3 PHASE GENERATOR. HOWEVER, THIS |
| GENERATOR IS SHOWN FEEDING 277/480 VOLT, 3 PHASE LOADS. |
| PROVIDE CORRECTION. WPB FBC 107.2.1 |
| 3. EXPANDED VIEW OF MAIN ELECTRICAL ROOM, IN THE |
| EMERGENCY AREA, PLAN DOES NOT SHOW THE REQUIRED 4 FEET |
| OF CLEARANCE BETWEEN PANELS AND ATS. PROVIDE |
| CORRECTION. NEC 110.26(A)(1) |
| |
| ALL OTHER COMMENTS HAVE BEEN ADDRESSED SATISFACTORILY. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| SHEETS?. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |