2018-09-07 14:27:42 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 17020796 |
| 3RD REVIEW: SEPTEMBER 6, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. OK |
| |
| 2. COMMENT FROM FIRST REVIEW: A1.2.01 EXIT DISCHARGE |
| NOT CLEAR; REVISE PLAN TO SHOW COMPLIANCE WITH FBC B |
| 1027. |
| |
| ON THE ELECTRICAL PAGES, I WAS NOT ABLE TO LOCATE VOICE |
| EVAC. SHEET E2.1.01 SHOWS A FIRE ALARM CONTROL PANEL, |
| DETAILS ON E3.1.02, BUT I WAS UNABLE TO LOCATE THE |
| LABEL "EVAC" ON THE FLOOR PLANS (PER ELECTRICAL LEGEND) |
| AND E3.1.02 WAS NOT CLEAR. PLEASE DIRECT WHERE THIS |
| INFORMATION CAN BE FOUND OR CLARIFY INTENT. NOTE THAT |
| FBC B 1005.3.1 REQUIRES .3" PER OCCUPANT, BUT .2" WAS |
| USED PER EXCEPTION. |
| |
| 2- 3RD REVIEW |
| MOST OF THIS IS WAS ADDRESSED IN COMMENT RESPONSE, BUT |
| NOT THE VOICE EVAC PORTION. THE FACP ON SHEET E-3.1.02 |
| DOESN'T SHOW AS A VOICE EVAC SYSTEM. |
| |
| (SEE NEW COMMENTS FROM LIFE SAFETY SHEETS PROVIDED AT |
| BOTTOM STARTING COMMENT #35) |
| |
| 3-6. OK |
| |
| 7-11. OK |
| |
| 12. 2ND REVIEW, NOT ADDRESSED. ENGINEER OF RECORD IS TO |
| REVIEW THE SOILS, EITHER WITH A SHOP DRAWING REVIEW |
| STAMP OR BY INCORPORATING A REFERENCE INTO THE PLAN. |
| THE SOILS REPORT WAS PROVIDED FOR THE FOUNDATION PERMIT |
| APPLICATION (17010911). AFTER THE FOUNDATION PERMIT IS |
| ISSUED, THE SOILS WILL BE PUBLIC RECORD AND IS NOT |
| NEEDED FOR THIS PERMIT. IF YOU RESUBMIT PRIOR TO |
| ISSUANCE OF FOUNDATION PERMIT, PLEASE INCLUDE IN YOUR |
| RESUBMITTAL. |
| |
| 12- 3RD REVIEW THE NOTES ADDED WILL REFER TO SOILS |
| REPORT FOR BEARING CAPACITY, BUT STRUCTURAL SHEETS |
| S-2.00, S-2.00A AND S-2.00B SHOW THE TOP OF FOOTERS AT |
| 12" BELOW GRADE. THE GEO TECHNICAL REPORT STATES THAT |
| TOP OF FOOTERS SHOULD BE PLACED 18" BELOW GRADE. PLEASE |
| REVIEW AND REVISE AS APPLICABLE. |
| |
| 13-37. OK (26-28 MOVED TO PROVISO) |
| |
| 38. (MOVED TO PROVISO) |
| |
| 39-40. OK |
| |
| 41. (MOVED TO PROVISO) |
| |
| 42. THIS PERMIT WILL BE ISSUED WITH PROVISOS: |
| |
| A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE |
| 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515, |
| [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN |
| THIS IS COMPLETE. |
| |
| B. SEPARATE PERMITS REQUIRED. SUB PERMITS FOR |
| MECHANICAL, ELECTRICAL, PLUMBING ARE REQUIRED. SEPARATE |
| PERMITS (APPLICATION, FEES, PLANS, REVIEWS) REQUIRED |
| FOR ALL OTHER ITEMS SUCH AS PARKING, SIGNAGE, ETC. |
| |
| C. COMPLIANCE WITH FBC B 1006, MEANS OF EGRESS |
| ILLUMINATION, INCLUDING EXIT DISCHARGE, REQUIRED. |
| |
| D. VOICE EVAC REQUIRED (NOTE 35, SHEET E3.1.02). |
| |
| E. ADVISORY ONLY; THE LANDSCAPE PLANS APPEAR TO |
| CONFLICT WITH THE EXIT DISCHARGE. LANDSCAPE PERMIT |
| REQUIRES A SEPARATE SUBMITTAL; PERMIT APPLICATION, |
| FEES, AND PLANS AND ARE NOT REVIEWED BY BUILDING. |
| |
| F. PRODUCT APPROVALS FOR ALL COMPONENTS AND CLADDING |
| ARE TO BE SUBMITTED, REVIEWED BY DESIGNER OF RECORD, |
| REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| |
| G. SHORING/RESHORE ENGINEERING ARE REQUIRED TO BE |
| SUBMITTED, REVIEWED, AND ISSUED PRIOR TO INSTALLATION. |
| FAILURE TO DO SO WILL RESULT IN A STOP WORK ORDER. |
| |
| H. AN ENGINEERED CONSTRUCTION GUARD RAIL DETAIL IS |
| REQUIRED PRIOR TO INSTALLATION. THIS MAY BE SUBMITTED |
| AS A SUBMITTAL ALONG WITH THE SHORING/RESHORE, BUT MAY |
| BE PROVIDED IN THE FIELD TO KEN CONRAD, SUBJECT TO HIS |
| APPROVAL. |
| |
| I. RECORDED REPLAT REQUIRED PRIOR TO C.O.; PROVIDE |
| BOOK/PAGE VIA EMAIL. |
| |
| J. BUILT IN BENCHES TO COMPLY WITH FBC A 903. |
| |
| K. DRESSING, FITTING AND LOCKER ROOMS TO COMPLY WITH |
| FBC A 222, REVISE PLAN TO SHOW COMPLIANCE. |
| |
| L. SPA RECEPTION/ RETAIL DESK, ANY OTHER CHECK OUT |
| AREAS, SEE FBC A 904 NOTE ON PLAN AND PROVIDE A DETAIL |
| 2ND REVIEW: RESPONSE TO 26, 27, 28 REFERS TO D SHEETS; |
| THESE PAGES ARE NOT SIGNED AND SEALED AND IT IS NOT |
| CLEAR WHO IS TAKING RESPONSIBILITY FOR THE PAGES. |
| PLEASE REMOVE THE SHEETS AS IT APPEARS MOST OF THE |
| INFORMATION IS NOT REQUIRED. ITEMS 26, 27, AND 28 CAN |
| BE A PROVISO ITEM. |
| |
| M. FBC B 603.1, A4.4.02 DETAIL 12 SHOWS POLYSTYRENE |
| OUTRIGGER AT METAL ROOFS AND POSSIBLY OTHER LOCATIONS, |
| OTHER DETAILS. PLEASE PROVIDE MORE INFORMATION VIA |
| EMAIL REGARDING HEIGHT OF LOCATIONS PROPOSED (OVER |
| 30'?), OVER EXITS. A4.4.03 SHOWS EXTERIOR FOAM; PROVIDE |
| INFORMATION VIA EMAIL. ARE THESE PRODUCTS |
| NONCOMBUSTIBLE? |
| |
| N. ADVISORY ONLY; SHEET D0.0.00 SHOWS A PLATFORM BED. |
| IT IS NOT CLEAR IF THIS BED COMPLIES WITH FBC A |
| 806.4(II), OPEN-FRAME TYPE BEDS REQUIRED. THIS WILL BE |
| A PROVISO ITEM. |
| |
| ADDITIONAL COMMENTS: |
| |
| 43. [FBC 1011.1]SHEET A-1.2.01 EXIT SIGNS. EXIT SIGNS |
| ARE ONLY LOCATED AT THE EGRESS DOORS AND NO |
| INTERMEDIATE SIGNS ARE PROVIDED WHEN THE EGRESS DOOR |
| ISN'T VISABLE. FLOORS 2-4 DO A GOOD JOB OF THIS, BUT |
| FIRST FLOOR NEEDS REVIEW OF EXIT SIGN PLACEMENT. |
| |
| 44. [FBC 1011.2]FLOOR-LEVEL EXIT SIGNS IN GROUP R-1. |
| WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES |
| BY SECTION 1011.1, ADDITIONAL LOW-LEVEL EXIT SIGNS |
| SHALL BE PROVIDED IN ALL AREAS SERVING GUESTROOMS IN |
| GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION |
| 1011.5. |
| |
| 45. [FBC 701]GENERAL COMMENT-CHECK THAT LIFE SAFETY |
| SHEET FOR 1ST FLOOR SHOWS DESIGNATED LINES TO CORESPOND |
| WITH FIRE RATED WALLS AND THAT FLOORS PLAN WALL TYPES |
| MATCH THE REQ?D FIRE RATINGS. MAINLY ON SHEET A-1.2.01 |
| THE CORRIDORS DON?T SHOW THE 1 HOUR RATED DASHED LINES |
| (SEE BELOW FOR EXAMPLES ON THE FLOOR PLANS) |
| |
| 46. [FBC 701]SHEET A-1.4.01B WALLS IN WOMENS LOUNGE AND |
| SPA THAT DEFINE COORIDOR ARE LABLED TYPE C4 WHICH IS |
| NON-RATED, BUT LIFE SAFETY STATES ALL CORRIDORS ARE TO |
| BE 1 HR WHICH WOULD BE TYPE C1 ACCORDING TO SHEET |
| A-6.6.02. |
| |
| 47. [FBC 701]SHEET A-1.4.01A MECH RM 116 SHOWS C1 ON |
| CORRIDOR WALL, BUT THE REST OF ROOM IS 2 HR. |
| SAME FOR RM 1112C. ALSO, MECH ROOM 1103A BACK WALL IS |
| NOT LABELED WITH WALL TYPE. |
| |
| 48. [FBC 701]SHEET A-1.4.01A WHY ARE FIRE RATED WALLS |
| IN RM 1107 & 1108 CALLED OUT FOR THE BATHROOM |
| PARTITIONS? ARE THEY SUPPOSED TO BE C4 FOR SOUND ONLY? |
| ALSO, FOR RESTROOMS 1149 & 1150 NO WALL TYPES ARE |
| SHOWN. |
| IN GENERAL PLEASE LOOK AT RESTROOMS AND PROVIDE |
| INTENDED WALL TYPES. |
| |
| 49. WHAT IS THE RATING, ASSEMBLY AND GLASS TYPE FOR |
| WALLS/WINDOWS ATDINING BOOTHS THAT LOOK INTO CORRIDOR |
| 1122? |
| |
| 50. [NO CODE REF]CHECK SHEET A-1.3.01 1ST FLOOR PLAN. |
| THE PERIMETER HAS A LIGHTER OFF-SET LAYER THAT SHOWS |
| ITEMS ON A LAYER THAT I THINK SHOULD BE TURNED OFF. |
| |
| 51. [FBC ACCESSIBILITY 233.3.1]MINIMUM NUMBER: NEW |
| CONSTRUCTION. |
| IN FACILITIES WITH RESIDENTIAL DWELLING UNITS, AT LEAST |
| 5 PERCENT, BUT NO FEWER THAN ONE UNIT, OF THE TOTAL |
| NUMBER OF RESIDENTIAL DWELLING UNITS SHALL PROVIDE |
| MOBILITY FEATURES COMPLYING WITH 809.2 THROUGH 809.4 |
| AND SHALL BE ON AN ACCESSIBLE ROUTE AS REQUIRED BY 206. |
| I SEE 5 ROOMS PROVIDED, BUT 5% OF 150 ROOMS WOULD BE 8 |
| ROOMS NEEDED TO COMPLY WITH REQUIRED AMOUNT. |
| |
| 52. [FBC ACCESSIBILITY 233.3.1.2]RESIDENTIAL DWELLING |
| UNITS WITH COMMUNICATION FEATURES. |
| IN FACILITIES WITH RESIDENTIAL DWELLING UNITS, AT LEAST |
| 2 PERCENT, BUT NO FEWER THAN ONE UNIT, OF THE TOTAL |
| NUMBER OF RESIDENTIAL DWELLING UNITS SHALL PROVIDE |
| COMMUNICATION FEATURES COMPLYING WITH 809.5. |
| I SEE 11 ROOMS PROVIDED WHICH EXCEEDS THE RE'D 2% (3 |
| ROOMS). THIS EXCEEDS CODE AND I ONLY MENTION BECAUSE I |
| WONDER IF SOME OF THESE WERE INTENED TO PROVIDE |
| MOBILITY FEATURES INSTEAD OF COMMUNICATION FEATURES. |
| |
| |
| |