2018-09-07 14:27:42****CORRECTIONS****
 W.P.B. PERMIT: 17020796
 3RD REVIEW: SEPTEMBER 6, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK
  
 2. COMMENT FROM FIRST REVIEW: A1.2.01 EXIT DISCHARGE
 NOT CLEAR; REVISE PLAN TO SHOW COMPLIANCE WITH FBC B
 1027.
  
 ON THE ELECTRICAL PAGES, I WAS NOT ABLE TO LOCATE VOICE
 EVAC. SHEET E2.1.01 SHOWS A FIRE ALARM CONTROL PANEL,
 DETAILS ON E3.1.02, BUT I WAS UNABLE TO LOCATE THE
 LABEL "EVAC" ON THE FLOOR PLANS (PER ELECTRICAL LEGEND)
 AND E3.1.02 WAS NOT CLEAR. PLEASE DIRECT WHERE THIS
 INFORMATION CAN BE FOUND OR CLARIFY INTENT. NOTE THAT
 FBC B 1005.3.1 REQUIRES .3" PER OCCUPANT, BUT .2" WAS
 USED PER EXCEPTION.
  
 2- 3RD REVIEW
 MOST OF THIS IS WAS ADDRESSED IN COMMENT RESPONSE, BUT
 NOT THE VOICE EVAC PORTION. THE FACP ON SHEET E-3.1.02
 DOESN'T SHOW AS A VOICE EVAC SYSTEM.
  
 (SEE NEW COMMENTS FROM LIFE SAFETY SHEETS PROVIDED AT
 BOTTOM STARTING COMMENT #35)
  
 3-6. OK
  
 7-11. OK
  
 12. 2ND REVIEW, NOT ADDRESSED. ENGINEER OF RECORD IS TO
 REVIEW THE SOILS, EITHER WITH A SHOP DRAWING REVIEW
 STAMP OR BY INCORPORATING A REFERENCE INTO THE PLAN.
 THE SOILS REPORT WAS PROVIDED FOR THE FOUNDATION PERMIT
 APPLICATION (17010911). AFTER THE FOUNDATION PERMIT IS
 ISSUED, THE SOILS WILL BE PUBLIC RECORD AND IS NOT
 NEEDED FOR THIS PERMIT. IF YOU RESUBMIT PRIOR TO
 ISSUANCE OF FOUNDATION PERMIT, PLEASE INCLUDE IN YOUR
 RESUBMITTAL.
  
 12- 3RD REVIEW THE NOTES ADDED WILL REFER TO SOILS
 REPORT FOR BEARING CAPACITY, BUT STRUCTURAL SHEETS
 S-2.00, S-2.00A AND S-2.00B SHOW THE TOP OF FOOTERS AT
 12" BELOW GRADE. THE GEO TECHNICAL REPORT STATES THAT
 TOP OF FOOTERS SHOULD BE PLACED 18" BELOW GRADE. PLEASE
 REVIEW AND REVISE AS APPLICABLE.
  
 13-37. OK (26-28 MOVED TO PROVISO)
  
 38. (MOVED TO PROVISO)
  
 39-40. OK
  
 41. (MOVED TO PROVISO)
  
 42. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE
 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515,
 [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN
 THIS IS COMPLETE.
  
 B. SEPARATE PERMITS REQUIRED. SUB PERMITS FOR
 MECHANICAL, ELECTRICAL, PLUMBING ARE REQUIRED. SEPARATE
 PERMITS (APPLICATION, FEES, PLANS, REVIEWS) REQUIRED
 FOR ALL OTHER ITEMS SUCH AS PARKING, SIGNAGE, ETC.
  
 C. COMPLIANCE WITH FBC B 1006, MEANS OF EGRESS
 ILLUMINATION, INCLUDING EXIT DISCHARGE, REQUIRED.
  
 D. VOICE EVAC REQUIRED (NOTE 35, SHEET E3.1.02).
  
 E. ADVISORY ONLY; THE LANDSCAPE PLANS APPEAR TO
 CONFLICT WITH THE EXIT DISCHARGE. LANDSCAPE PERMIT
 REQUIRES A SEPARATE SUBMITTAL; PERMIT APPLICATION,
 FEES, AND PLANS AND ARE NOT REVIEWED BY BUILDING.
  
 F. PRODUCT APPROVALS FOR ALL COMPONENTS AND CLADDING
 ARE TO BE SUBMITTED, REVIEWED BY DESIGNER OF RECORD,
 REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 G. SHORING/RESHORE ENGINEERING ARE REQUIRED TO BE
 SUBMITTED, REVIEWED, AND ISSUED PRIOR TO INSTALLATION.
 FAILURE TO DO SO WILL RESULT IN A STOP WORK ORDER.
  
 H. AN ENGINEERED CONSTRUCTION GUARD RAIL DETAIL IS
 REQUIRED PRIOR TO INSTALLATION. THIS MAY BE SUBMITTED
 AS A SUBMITTAL ALONG WITH THE SHORING/RESHORE, BUT MAY
 BE PROVIDED IN THE FIELD TO KEN CONRAD, SUBJECT TO HIS
 APPROVAL.
  
 I. RECORDED REPLAT REQUIRED PRIOR TO C.O.; PROVIDE
 BOOK/PAGE VIA EMAIL.
  
 J. BUILT IN BENCHES TO COMPLY WITH FBC A 903.
  
 K. DRESSING, FITTING AND LOCKER ROOMS TO COMPLY WITH
 FBC A 222, REVISE PLAN TO SHOW COMPLIANCE.
  
 L. SPA RECEPTION/ RETAIL DESK, ANY OTHER CHECK OUT
 AREAS, SEE FBC A 904 NOTE ON PLAN AND PROVIDE A DETAIL
 2ND REVIEW: RESPONSE TO 26, 27, 28 REFERS TO D SHEETS;
 THESE PAGES ARE NOT SIGNED AND SEALED AND IT IS NOT
 CLEAR WHO IS TAKING RESPONSIBILITY FOR THE PAGES.
 PLEASE REMOVE THE SHEETS AS IT APPEARS MOST OF THE
 INFORMATION IS NOT REQUIRED. ITEMS 26, 27, AND 28 CAN
 BE A PROVISO ITEM.
  
 M. FBC B 603.1, A4.4.02 DETAIL 12 SHOWS POLYSTYRENE
 OUTRIGGER AT METAL ROOFS AND POSSIBLY OTHER LOCATIONS,
 OTHER DETAILS. PLEASE PROVIDE MORE INFORMATION VIA
 EMAIL REGARDING HEIGHT OF LOCATIONS PROPOSED (OVER
 30'?), OVER EXITS. A4.4.03 SHOWS EXTERIOR FOAM; PROVIDE
 INFORMATION VIA EMAIL. ARE THESE PRODUCTS
 NONCOMBUSTIBLE?
  
 N. ADVISORY ONLY; SHEET D0.0.00 SHOWS A PLATFORM BED.
 IT IS NOT CLEAR IF THIS BED COMPLIES WITH FBC A
 806.4(II), OPEN-FRAME TYPE BEDS REQUIRED. THIS WILL BE
 A PROVISO ITEM.
  
 ADDITIONAL COMMENTS:
  
 43. [FBC 1011.1]SHEET A-1.2.01 EXIT SIGNS. EXIT SIGNS
 ARE ONLY LOCATED AT THE EGRESS DOORS AND NO
 INTERMEDIATE SIGNS ARE PROVIDED WHEN THE EGRESS DOOR
 ISN'T VISABLE. FLOORS 2-4 DO A GOOD JOB OF THIS, BUT
 FIRST FLOOR NEEDS REVIEW OF EXIT SIGN PLACEMENT.
  
 44. [FBC 1011.2]FLOOR-LEVEL EXIT SIGNS IN GROUP R-1.
 WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES
 BY SECTION 1011.1, ADDITIONAL LOW-LEVEL EXIT SIGNS
 SHALL BE PROVIDED IN ALL AREAS SERVING GUESTROOMS IN
 GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION
 1011.5.
  
 45. [FBC 701]GENERAL COMMENT-CHECK THAT LIFE SAFETY
 SHEET FOR 1ST FLOOR SHOWS DESIGNATED LINES TO CORESPOND
 WITH FIRE RATED WALLS AND THAT FLOORS PLAN WALL TYPES
 MATCH THE REQ?D FIRE RATINGS. MAINLY ON SHEET A-1.2.01
 THE CORRIDORS DON?T SHOW THE 1 HOUR RATED DASHED LINES
 (SEE BELOW FOR EXAMPLES ON THE FLOOR PLANS)
  
 46. [FBC 701]SHEET A-1.4.01B WALLS IN WOMENS LOUNGE AND
 SPA THAT DEFINE COORIDOR ARE LABLED TYPE C4 WHICH IS
 NON-RATED, BUT LIFE SAFETY STATES ALL CORRIDORS ARE TO
 BE 1 HR WHICH WOULD BE TYPE C1 ACCORDING TO SHEET
 A-6.6.02.
  
 47. [FBC 701]SHEET A-1.4.01A MECH RM 116 SHOWS C1 ON
 CORRIDOR WALL, BUT THE REST OF ROOM IS 2 HR.
 SAME FOR RM 1112C. ALSO, MECH ROOM 1103A BACK WALL IS
 NOT LABELED WITH WALL TYPE.
  
 48. [FBC 701]SHEET A-1.4.01A WHY ARE FIRE RATED WALLS
 IN RM 1107 & 1108 CALLED OUT FOR THE BATHROOM
 PARTITIONS? ARE THEY SUPPOSED TO BE C4 FOR SOUND ONLY?
 ALSO, FOR RESTROOMS 1149 & 1150 NO WALL TYPES ARE
 SHOWN.
 IN GENERAL PLEASE LOOK AT RESTROOMS AND PROVIDE
 INTENDED WALL TYPES.
  
 49. WHAT IS THE RATING, ASSEMBLY AND GLASS TYPE FOR
 WALLS/WINDOWS ATDINING BOOTHS THAT LOOK INTO CORRIDOR
 1122?
  
 50. [NO CODE REF]CHECK SHEET A-1.3.01 1ST FLOOR PLAN.
 THE PERIMETER HAS A LIGHTER OFF-SET LAYER THAT SHOWS
 ITEMS ON A LAYER THAT I THINK SHOULD BE TURNED OFF.
  
 51. [FBC ACCESSIBILITY 233.3.1]MINIMUM NUMBER: NEW
 CONSTRUCTION.
 IN FACILITIES WITH RESIDENTIAL DWELLING UNITS, AT LEAST
 5 PERCENT, BUT NO FEWER THAN ONE UNIT, OF THE TOTAL
 NUMBER OF RESIDENTIAL DWELLING UNITS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 809.2 THROUGH 809.4
 AND SHALL BE ON AN ACCESSIBLE ROUTE AS REQUIRED BY 206.
 I SEE 5 ROOMS PROVIDED, BUT 5% OF 150 ROOMS WOULD BE 8
 ROOMS NEEDED TO COMPLY WITH REQUIRED AMOUNT.
  
 52. [FBC ACCESSIBILITY 233.3.1.2]RESIDENTIAL DWELLING
 UNITS WITH COMMUNICATION FEATURES.
 IN FACILITIES WITH RESIDENTIAL DWELLING UNITS, AT LEAST
 2 PERCENT, BUT NO FEWER THAN ONE UNIT, OF THE TOTAL
 NUMBER OF RESIDENTIAL DWELLING UNITS SHALL PROVIDE
 COMMUNICATION FEATURES COMPLYING WITH 809.5.
 I SEE 11 ROOMS PROVIDED WHICH EXCEEDS THE RE'D 2% (3
 ROOMS). THIS EXCEEDS CODE AND I ONLY MENTION BECAUSE I
 WONDER IF SOME OF THESE WERE INTENED TO PROVIDE
 MOBILITY FEATURES INSTEAD OF COMMUNICATION FEATURES.
  
  
  