2018-05-08 12:31:12 | 2ND REVIEW |
| FBC 2014 5TH EDITION |
| PERMIT# 17020796 |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| |
| !!!! IN ORDER TO TO EXPIDITE AN APPROVAL FOR THIS |
| PERMIT I SUGEST A MEETING BE SCHDULED TO GO OVER THE |
| PLAN PLEASE CONNTACT ME @ 561-805-6711 !!! |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED SEE |
| NEW COMMENTS |
| |
| 10. PLEASE PROVIDE SLOPE OF PIPE ON RISER DIAGRAMS. PER |
| FBC PL 704. |
| |
| 12. PLEASE LABEL THE STACKS ON THE RISER TO MATCH THE |
| FLOOR PLAN, WATER AND SANITARY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 17. SOME OF THE SOIL STACK ARE NOTE SIZED OR LABELED |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 24. SHT. P-3.0.03 AND P-3.0.01 SHOW BRANCH LINES FOR |
| EACH UNIT AND SHOW FLOOR LEVEL. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| NEW COMMENTS: |
| |
| 1. ALL THE ACCESSIBILITY SHALL COMPLY WITH FLORIDA |
| BUILDING CODE ACCESSIBILITY 2014 5TH EDITION PLEASE |
| NOTE ON THE PLAN. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. SHT. P-3.0.05 THE 1" HOT WATER RECIRCULATION LINE |
| DOES NOT SHOW UP ON THIS SHEET PLEASE CLARIFY. PER FBC |
| PL 607.2 |
| |
| 3. SHT. P- 1.5.10 THE SANITARY PIPING DID NOT SHOW UP |
| ON THIS SHEET PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 4. SHT. P-3.0.00 AND P-3.0.02 PLEASE SHOW THE SIZE AND |
| SLOPE ON THE ISOMETRIC WE NEED THIS TO CHECK SIZING THE |
| TABLE THAT WAS PROVIDED DOES NOT SPECIFY THE SLOPE IT |
| ONLY GIVES A MINIMUM THE SIZING TABLE FBC PL TABLE |
| 710.1(1) USES SPECIFIC SLOPE TO SIZE THE PIPE. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 5. SHT. P-1.1.00 THE SOUTH GREASE INTERCEPTOR DID NOT |
| SHOW UP ON THE SHEET IT IS ALSO MISSING THE GREASE AND |
| SANITARY PIPING PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 6. SHT. P-3.0.02 TWOWAY CLEANOUTS ARE REQUIRED BETWEEN |
| EACH INTERCEPTOR PLEASE SHOW ON PLAN. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 7. ON THE SANITARY ISOMETRIC DRAWINGS GOING FROM THE |
| FIRST FLOOR TO THE 2ND, 3RD, AND 4TH FLOOR SOME OF THE |
| ID TAGS ARE NOT MATCHING UP SOME ARE MISSING AND ON THE |
| DRAWING FOR THE UPPER FLOOR IT APPEARS THE BRANCHES ARE |
| MISSING THESE ISOMETRIC DRAWING ARE TO CONFUSING TO |
| DETERMINE CODE COMPLIANCE PLEASE CLARIFY. PER WPB AMEND |
| TO FBC 107.2.1 |
| |
| 8. THE FLOOR PLANS ARE MISSING THE ID TAGS TO MATCH UP |
| THE SANITARY STACKS TO THE ISOMETRIC DRAWINGS PLEASE |
| CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 9. IN YOUR RESPONSE TO COMMENT #21 YOU REFER TO DETAIL |
| ON SHT. P-4.0.04 THIS SHEET IS MISSING FROM THIS |
| SUBMITTAL PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 10. SHT. P- 1.4.07 PLEASE REMOVE THE GAS ISOMETRIC FROM |
| THE WATER ISO IT SHOULD BE ON SHT. P-3.0.08 AND LABEL |
| ALL FIXTURE SOME ARE MISSING LABELS. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 11. SHT. P-3.0.07 PLEASE LABEL ALL THE FIXTURES AND |
| BRANCHES FOR THE UNITS ALSO SHOW THE SIZE ON ALL THE |
| PIPING. PER WPB AMEND TO FBC 107.2.1 |
| |
| |
| WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| |