Plan Review Notes
Plan Review Notes For Permit 17020796
Permit Number 17020796
Review Stop P
Sequence Number 2
Notes
Date Text
2018-05-08 12:31:122ND REVIEW
 FBC 2014 5TH EDITION
 PERMIT# 17020796
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 !!!! IN ORDER TO TO EXPIDITE AN APPROVAL FOR THIS
 PERMIT I SUGEST A MEETING BE SCHDULED TO GO OVER THE
 PLAN PLEASE CONNTACT ME @ 561-805-6711 !!!
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED SEE
 NEW COMMENTS
  
 10. PLEASE PROVIDE SLOPE OF PIPE ON RISER DIAGRAMS. PER
 FBC PL 704.
  
 12. PLEASE LABEL THE STACKS ON THE RISER TO MATCH THE
 FLOOR PLAN, WATER AND SANITARY. PER WPB AMEND TO FBC
 107.2.1
  
 17. SOME OF THE SOIL STACK ARE NOTE SIZED OR LABELED
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 24. SHT. P-3.0.03 AND P-3.0.01 SHOW BRANCH LINES FOR
 EACH UNIT AND SHOW FLOOR LEVEL. PER WPB AMEND TO FBC
 107.2.1
  
 NEW COMMENTS:
  
 1. ALL THE ACCESSIBILITY SHALL COMPLY WITH FLORIDA
 BUILDING CODE ACCESSIBILITY 2014 5TH EDITION PLEASE
 NOTE ON THE PLAN. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. P-3.0.05 THE 1" HOT WATER RECIRCULATION LINE
 DOES NOT SHOW UP ON THIS SHEET PLEASE CLARIFY. PER FBC
 PL 607.2
  
 3. SHT. P- 1.5.10 THE SANITARY PIPING DID NOT SHOW UP
 ON THIS SHEET PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. SHT. P-3.0.00 AND P-3.0.02 PLEASE SHOW THE SIZE AND
 SLOPE ON THE ISOMETRIC WE NEED THIS TO CHECK SIZING THE
 TABLE THAT WAS PROVIDED DOES NOT SPECIFY THE SLOPE IT
 ONLY GIVES A MINIMUM THE SIZING TABLE FBC PL TABLE
 710.1(1) USES SPECIFIC SLOPE TO SIZE THE PIPE. PER WPB
 AMEND TO FBC 107.2.1
  
 5. SHT. P-1.1.00 THE SOUTH GREASE INTERCEPTOR DID NOT
 SHOW UP ON THE SHEET IT IS ALSO MISSING THE GREASE AND
 SANITARY PIPING PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 6. SHT. P-3.0.02 TWOWAY CLEANOUTS ARE REQUIRED BETWEEN
 EACH INTERCEPTOR PLEASE SHOW ON PLAN. PER WPB AMEND TO
 FBC 107.2.1
  
 7. ON THE SANITARY ISOMETRIC DRAWINGS GOING FROM THE
 FIRST FLOOR TO THE 2ND, 3RD, AND 4TH FLOOR SOME OF THE
 ID TAGS ARE NOT MATCHING UP SOME ARE MISSING AND ON THE
 DRAWING FOR THE UPPER FLOOR IT APPEARS THE BRANCHES ARE
 MISSING THESE ISOMETRIC DRAWING ARE TO CONFUSING TO
 DETERMINE CODE COMPLIANCE PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 8. THE FLOOR PLANS ARE MISSING THE ID TAGS TO MATCH UP
 THE SANITARY STACKS TO THE ISOMETRIC DRAWINGS PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. IN YOUR RESPONSE TO COMMENT #21 YOU REFER TO DETAIL
 ON SHT. P-4.0.04 THIS SHEET IS MISSING FROM THIS
 SUBMITTAL PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 10. SHT. P- 1.4.07 PLEASE REMOVE THE GAS ISOMETRIC FROM
 THE WATER ISO IT SHOULD BE ON SHT. P-3.0.08 AND LABEL
 ALL FIXTURE SOME ARE MISSING LABELS. PER WPB AMEND TO
 FBC 107.2.1
  
 11. SHT. P-3.0.07 PLEASE LABEL ALL THE FIXTURES AND
 BRANCHES FOR THE UNITS ALSO SHOW THE SIZE ON ALL THE
 PIPING. PER WPB AMEND TO FBC 107.2.1
  
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  