Plan Review Notes
Plan Review Notes For Permit 17020796
Permit Number 17020796
Review Stop M
Sequence Number 2
Notes
Date Text
2018-05-08 17:07:222ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17020796
 5/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS FOLLOW-UP REVIEW IS BASED ON THE RESUBMITTED
 PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE
 ENGINEER OF RECORD. ALL 1ST REVIEW COMMENTS NOT
 COMPLETELY RESOLVED ARE LISTED BELOW IN THEIR ORIGINAL
 NUMERICAL ORDER.
  
  
 1) THE FOLLOWING LIST OF NEW UPLOADED PLAN SHEETS NEED
 TO BE ELECTRONICALLY SIGNED AND SEALED: M-1.3.01C,
 M-1.3.03A, M4.0.00, M-5.0.01, M-5.0.02, M-5.0.03,
 M-5.0.05
  
 1A) THE REVISED ENERGY CALCULATIONS ARE INDICATING
 CAPACITIES FOR AHU 3 & 5, AND OA-1 THAT DON'T MATCH THE
 SCHEDULE ON SHEET M-0.0.02. B) THE FC TYPICAL-345
 IDENTIFICATION AND THE NO. OF UNITS SHOWN IN THE ENERGY
 CALCULATIONS DOES NOT MATCH THE FC SCHEDULE- SHEET
 M-0.0.02. C) THE ENERGY CALCULATIONS DO NOT PROVIDE ANY
 HEATING COMPLIANCE DATA.
  
 4) THE 19.8 BTUH FC SYSTEMS SELECTED FOR THE GUEST
 ROOMS ARE OVERSIZED PER THE SUBMITTED AC CALCULATIONS
 WHICH SHOW ALL THE SYSTEMS CALCULATED AT 1-TON OR LESS-
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 10) THE REQUESTED ENLARGED FOOD SERVICE DRAWINGS AND
 EQUIPMENT SCHEDULE NOT PROVIDED. PLEASE NOTE THE
 SUBMITTAL PACKAGE FROM CHENEY INCLUDES A WOOD-FIRED
 GRILL WHICH MUST BE UL 2162 LISTED AND LABELED PER
 SECTION 917.1.
  
 11) THE REQUESTED COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES AND WATER HEATERS WERE NOT
 PROVIDED. PLEASE SEE SECTION 304 FBC-14 FUEL GAS AND
 COMPLY.
  
 14) THE REQUESTED FLEX DUCT SIZES WERE NOT PROVIDED.
  
 16) THE REQUESTED DUCT SMOKE DETECTOR SYMBOLS TO BE
 PLACED ON THE PLAN WERE NOT PROVIDED.
  
 17) THE REQUESTED EXHAUST VENTILATION AND AIR BALANCE
 CALCULATIONS FOR THE LOCKER ROOMS AND THE MANI-PEDI
 ROOM WERE NOT PROVIDED.
  
 A) THE NEW TOILET EXHAUST RISER FOR THE GUEST ROOMS ON
 SHEET M-3.0.002 INDICATES AN ERV WILL BE REQUIRED FOR
 THE SYSTEMS- SEE TABLE C403.2.6 FBC-14 ENERGY
 CONSERVATION AND REVISE THE PLANS.
  
 B) SPORTS LOCKER ROOMS ARE CALCULATED AT 0.50 CFMS PER
 SQ. FT. PER TABLE 403.3. ASHRAE 62.1-10 IS A STANDARD
 HOWEVER, PER FLORIDA STATURE 553, THE PLANS SHALL BE
 DESIGNED IN ACCORDANCE WITH THE FBC-14 MECHANICAL CODE.
 PLEASE REVISE THE CALCULATIONS AND EXHAUST SYSTEMS, AND
 INCLUDE AN AIR BALANCE CALCULATION THAT INCLUDES THE
 MAKEUP AIR.
  
 C) THE REQUESTED ENLARGED DRAWINGS FOR THE MANI-PEDI
 HVAC SYSTEM WAS NOT PROVIDED. PLEASE SEE TABLE 403.3
 AND FOOTNOTES B AND H. RECIRCULATION OF AIR FROM THE
 SPACE IS PROHIBITED AND A SOURCE CAPTURE SYSTEM MUST BE
 INSTALLED AT EACH MANICURE AND PEDICURE STATION. REVISE
 THE DRAWINGS, AND EXHAUST AND AIR BALANCE CALCULATIONS.
 THE CURRENT PLAN APPEARS TO INDICATE
  
 MAKEUP AIR FOR EXHAUST BEING TRANSFERRED FROM THE
 CORRIDOR. THIS IS NOT PERMITTED BECAUSE THE CORRIDOR IS
 NOT BEING DIRECTLY SUPPLIED WITH OUTDOOR AIR AT A RATE
 HIGHER THAN THE RATE OF MAKEUP AIR TAKEN FROM THE
 CORRIDOR- SECTION 601.2(1). THIS RESTRICTION ALSO
 APPLIES TO THE TRANSFERS AT THE ADJACENT LOCKER ROOMS
 AND RESTROOMS.
  
 D) SHEETS M1.301A & M1-301B: THERE ARE TRANSFER DUCTS
 SHOWN INTO THE CORRIDORS FROM ROOMS 1112, 1112B, 1113,
 AND 1114. PLEASE CLARIFY IF THESE ARE TRANSFERS INTO AN
 ABOVE CEILING PLENUM, OR DIRECTLY INTO THE CORRIDORS.
 INDICATE WITH DOTTED LINES THE AREAS OF ABOVE-CEILING
 PLENUM SPACES AND IDENTIFY THEM USING KEYED NOTE #1.
 PLEASE NOTE THAT CORRIDORS CANNOT BE USED AS
  
 RETURN DUCTS PER SECTION 601.2, HOWEVER THE CEILINGS
 ABOVE ARE PERMITTED UNDER SECTION 601.2.1.
  
 20) PROVIDE MIAMI-DADE NOA'S OR FLORIDA PRODUCT
 APPROVALS FOR THE EXHAUST AND O/A INTAKE LOUVERS. CAN
 BE A DEFERRED SUBMITTAL. PLEASE PROVIDE A LIST OF ALL
 DEFERRED SUBMITTALS ON THE PLANS OR IN THE DOCUMENTS.
  
 25) ACKNOWLEDGED THAN WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE CHILLER, PUMPS ETC. WILL BE A
 DEFERRED SUBMITTAL.
  
 26) LABEL THE GRAVITY DAMPERS AT THE GUEST ROOM FAN
 COIL UNITS, AND PROVIDE A SUBMITTAL FOR THE FAN-COIL
 UNITS. CAN BE DEFERRED.
  
 29) ACKNOWLEDGED THAT THE TOILET EXHAUST DUCTWORK WILL
 BE FLAMEBAR. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION DETAILS REVIEWED AND
 STAMPED BY THE EOR. CAN BE A DEFERRED SUBMITTAL.
  
 32 & 33) ACKNOWLEDGED THAT THE DISCHARGE LOCATIONS FOR
 THE KITCHEN EXHAUST FANS WILL BE IN COMPLIANCE WITH THE
 CLEARANCES REQUIRED UNDER SECTIONS 506.13.1 &
 506.3.13.3, AND THE PLANS AND DETAILS WILL BE REVIEWED
 UNDER SEPARATE PERMIT. A) SHEETS M1.3.01A & B, M1.3.02A
 & B, M1.3.03A & B, AND M1.3.04A & B: THE GREASE EXHAUST
 DUCTS FROM THE KITCHEN HOODS ARE NOT
  
 PERMITTED TO BE LOCATED IN THE SAME SHAFTS- SEE SECTION
 506.3.11. PLEASE NOTE THAT THE REQUIRED SHAFT FOR HOOD
 4 & 5 GREASE DUCTS IS NOT SHOWN ON THE SECOND FLOOR
 MECHANICAL PLAN SHEET M-1.3.02A.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  