Date |
Text |
2018-05-08 17:07:22 | 2ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| CODES |
| PERMIT #17020796 |
| 5/8/18 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| THIS FOLLOW-UP REVIEW IS BASED ON THE RESUBMITTED |
| PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE |
| ENGINEER OF RECORD. ALL 1ST REVIEW COMMENTS NOT |
| COMPLETELY RESOLVED ARE LISTED BELOW IN THEIR ORIGINAL |
| NUMERICAL ORDER. |
| |
| |
| 1) THE FOLLOWING LIST OF NEW UPLOADED PLAN SHEETS NEED |
| TO BE ELECTRONICALLY SIGNED AND SEALED: M-1.3.01C, |
| M-1.3.03A, M4.0.00, M-5.0.01, M-5.0.02, M-5.0.03, |
| M-5.0.05 |
| |
| 1A) THE REVISED ENERGY CALCULATIONS ARE INDICATING |
| CAPACITIES FOR AHU 3 & 5, AND OA-1 THAT DON'T MATCH THE |
| SCHEDULE ON SHEET M-0.0.02. B) THE FC TYPICAL-345 |
| IDENTIFICATION AND THE NO. OF UNITS SHOWN IN THE ENERGY |
| CALCULATIONS DOES NOT MATCH THE FC SCHEDULE- SHEET |
| M-0.0.02. C) THE ENERGY CALCULATIONS DO NOT PROVIDE ANY |
| HEATING COMPLIANCE DATA. |
| |
| 4) THE 19.8 BTUH FC SYSTEMS SELECTED FOR THE GUEST |
| ROOMS ARE OVERSIZED PER THE SUBMITTED AC CALCULATIONS |
| WHICH SHOW ALL THE SYSTEMS CALCULATED AT 1-TON OR LESS- |
| SECTION C403.2.2 FBC-14 ENERGY CONSERVATION. |
| |
| 10) THE REQUESTED ENLARGED FOOD SERVICE DRAWINGS AND |
| EQUIPMENT SCHEDULE NOT PROVIDED. PLEASE NOTE THE |
| SUBMITTAL PACKAGE FROM CHENEY INCLUDES A WOOD-FIRED |
| GRILL WHICH MUST BE UL 2162 LISTED AND LABELED PER |
| SECTION 917.1. |
| |
| 11) THE REQUESTED COMBUSTION AIR CALCULATIONS FOR THE |
| GAS-FIRED COOKING APPLIANCES AND WATER HEATERS WERE NOT |
| PROVIDED. PLEASE SEE SECTION 304 FBC-14 FUEL GAS AND |
| COMPLY. |
| |
| 14) THE REQUESTED FLEX DUCT SIZES WERE NOT PROVIDED. |
| |
| 16) THE REQUESTED DUCT SMOKE DETECTOR SYMBOLS TO BE |
| PLACED ON THE PLAN WERE NOT PROVIDED. |
| |
| 17) THE REQUESTED EXHAUST VENTILATION AND AIR BALANCE |
| CALCULATIONS FOR THE LOCKER ROOMS AND THE MANI-PEDI |
| ROOM WERE NOT PROVIDED. |
| |
| A) THE NEW TOILET EXHAUST RISER FOR THE GUEST ROOMS ON |
| SHEET M-3.0.002 INDICATES AN ERV WILL BE REQUIRED FOR |
| THE SYSTEMS- SEE TABLE C403.2.6 FBC-14 ENERGY |
| CONSERVATION AND REVISE THE PLANS. |
| |
| B) SPORTS LOCKER ROOMS ARE CALCULATED AT 0.50 CFMS PER |
| SQ. FT. PER TABLE 403.3. ASHRAE 62.1-10 IS A STANDARD |
| HOWEVER, PER FLORIDA STATURE 553, THE PLANS SHALL BE |
| DESIGNED IN ACCORDANCE WITH THE FBC-14 MECHANICAL CODE. |
| PLEASE REVISE THE CALCULATIONS AND EXHAUST SYSTEMS, AND |
| INCLUDE AN AIR BALANCE CALCULATION THAT INCLUDES THE |
| MAKEUP AIR. |
| |
| C) THE REQUESTED ENLARGED DRAWINGS FOR THE MANI-PEDI |
| HVAC SYSTEM WAS NOT PROVIDED. PLEASE SEE TABLE 403.3 |
| AND FOOTNOTES B AND H. RECIRCULATION OF AIR FROM THE |
| SPACE IS PROHIBITED AND A SOURCE CAPTURE SYSTEM MUST BE |
| INSTALLED AT EACH MANICURE AND PEDICURE STATION. REVISE |
| THE DRAWINGS, AND EXHAUST AND AIR BALANCE CALCULATIONS. |
| THE CURRENT PLAN APPEARS TO INDICATE |
| |
| MAKEUP AIR FOR EXHAUST BEING TRANSFERRED FROM THE |
| CORRIDOR. THIS IS NOT PERMITTED BECAUSE THE CORRIDOR IS |
| NOT BEING DIRECTLY SUPPLIED WITH OUTDOOR AIR AT A RATE |
| HIGHER THAN THE RATE OF MAKEUP AIR TAKEN FROM THE |
| CORRIDOR- SECTION 601.2(1). THIS RESTRICTION ALSO |
| APPLIES TO THE TRANSFERS AT THE ADJACENT LOCKER ROOMS |
| AND RESTROOMS. |
| |
| D) SHEETS M1.301A & M1-301B: THERE ARE TRANSFER DUCTS |
| SHOWN INTO THE CORRIDORS FROM ROOMS 1112, 1112B, 1113, |
| AND 1114. PLEASE CLARIFY IF THESE ARE TRANSFERS INTO AN |
| ABOVE CEILING PLENUM, OR DIRECTLY INTO THE CORRIDORS. |
| INDICATE WITH DOTTED LINES THE AREAS OF ABOVE-CEILING |
| PLENUM SPACES AND IDENTIFY THEM USING KEYED NOTE #1. |
| PLEASE NOTE THAT CORRIDORS CANNOT BE USED AS |
| |
| RETURN DUCTS PER SECTION 601.2, HOWEVER THE CEILINGS |
| ABOVE ARE PERMITTED UNDER SECTION 601.2.1. |
| |
| 20) PROVIDE MIAMI-DADE NOA'S OR FLORIDA PRODUCT |
| APPROVALS FOR THE EXHAUST AND O/A INTAKE LOUVERS. CAN |
| BE A DEFERRED SUBMITTAL. PLEASE PROVIDE A LIST OF ALL |
| DEFERRED SUBMITTALS ON THE PLANS OR IN THE DOCUMENTS. |
| |
| 25) ACKNOWLEDGED THAN WIND LOAD ENGINEERING FOR |
| INSTALLATION OF THE CHILLER, PUMPS ETC. WILL BE A |
| DEFERRED SUBMITTAL. |
| |
| 26) LABEL THE GRAVITY DAMPERS AT THE GUEST ROOM FAN |
| COIL UNITS, AND PROVIDE A SUBMITTAL FOR THE FAN-COIL |
| UNITS. CAN BE DEFERRED. |
| |
| 29) ACKNOWLEDGED THAT THE TOILET EXHAUST DUCTWORK WILL |
| BE FLAMEBAR. PLEASE SUBMIT MANUFACTURER'S |
| SPECIFICATIONS AND INSTALLATION DETAILS REVIEWED AND |
| STAMPED BY THE EOR. CAN BE A DEFERRED SUBMITTAL. |
| |
| 32 & 33) ACKNOWLEDGED THAT THE DISCHARGE LOCATIONS FOR |
| THE KITCHEN EXHAUST FANS WILL BE IN COMPLIANCE WITH THE |
| CLEARANCES REQUIRED UNDER SECTIONS 506.13.1 & |
| 506.3.13.3, AND THE PLANS AND DETAILS WILL BE REVIEWED |
| UNDER SEPARATE PERMIT. A) SHEETS M1.3.01A & B, M1.3.02A |
| & B, M1.3.03A & B, AND M1.3.04A & B: THE GREASE EXHAUST |
| DUCTS FROM THE KITCHEN HOODS ARE NOT |
| |
| PERMITTED TO BE LOCATED IN THE SAME SHAFTS- SEE SECTION |
| 506.3.11. PLEASE NOTE THAT THE REQUIRED SHAFT FOR HOOD |
| 4 & 5 GREASE DUCTS IS NOT SHOWN ON THE SECOND FLOOR |
| MECHANICAL PLAN SHEET M-1.3.02A. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |