Plan Review Notes
Plan Review Notes For Permit 17020796
Permit Number 17020796
Review Stop G
Sequence Number 2
Notes
Date Text
2018-05-07 09:28:262ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS: PREVIOUS COMMENTS
  
 PARTIALLY COMPLIED 1. 1. SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS ALL CUT SECTIONS OF PIPE AND
 CORRESPONDING LENGTHS PER FBC-2014 FUEL GAS, SECS.
 402.4.1, 402.4.2. AND BTU LOAD OF EACH APPLIANCE. ALSO
 SHOW ALL VALVE DRIP LEGS AND REGULATORS REFER TO THE
 FBC-2014 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(37).
 PLEASE PROVIDE THE LENGTH OF EACH CUT SECTION OF PIPE.
 PLEASE SHOW BTU LOAD FOR EACH GAS APPLIANCE.THE NUMBERS
 ON THE ENLARGE BANQUET KITCHEN ISO DO NOT ALL MATCH THE
 GAS EQUIPMENT SCHEDULE.
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304. PLEASE PROVIDE
 COMBUSTION AIR CALC FOR THE KITCHEN APPLIANCES.
  
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505. IN YOUR RESPONSE YOU NOTE VENT
 DETAILS ON SHT P-3.0.08 I COULD NOT LOCATE ANY VENT
 DETAILS ON THAT SHT PLEASE CLARIFY.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 WE NEED
 THESE TO VERIFY BTU LOADS-IF THEY CAN NOT BE PROVIDED
 FOR PLAN REVIEW PLACE A NOTE ON THE PLAN TO BE ON
 JOBSITE FOR FIRST ROUGH INSPECTION.
  
 NEW COMMENTS:
  
 1. SHT. P-3.0.08 ON THE GAS ISOMETRIC THE 2ND BRANCH
 UPSTREAM OF THE METER HAS IS LABELED AS MAIN KITCHEN
 SHT. P-1.5.07 WHICH LABELS IT AS THE BANQUET KITCHEN
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE AN ENLARGED ISOMETRIC FOR RMAIN KITCHEN. PER
 WPB AMEND TO FBC 107.2.1
  
 3. PLEASE LABEL THE BRANCHES ON THE MAIN ISOMETRIC
 DRAWING TO MATCH THE PIPING ON THE ENLARGED ISOMETRIC
 DRAWINGS. PER WPB AMEND TO FBC 107.2.1
  
 4. WHAT IS THE 3/4" BRANCH WITH THE NOTE FIX TAG PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. WHAT IS THE 2" AT THE UPSTREAM END OF THE ISOMETRIC
 WITH THE TAG XXXMBH/L.F.=XX' PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. ON THE ENLARGED ISOMETRIC DRAWING PLEASE SHOW THE
 PRESSURE REGULATORS AND THE VALVES ALSO SHOW THE LENGTH
 AND SIZE OF THE PIPING BETWEEN THE REGULATOR AND THE
 APPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. A-1.4.01A IT IS SHOWING A VENT FREE GAS FIRE
 PLACE UNVENTED GAS APPLIANCES ARE PROHIBITED IN
 ASSEMBLY OCCUPANCY'S. PER FBC FG 621.4
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  