2018-04-30 16:39:04FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED A RISER DIAGRAM SHOWING ALL OF THE FIREPUMP AND
 CONTROLER, PLEASE INDICATE THE SIZES HP RATING, WIRE
 SIZES, OVERCURRENT PROTECTION, ECT, ECT
  
 ARC FLASH MITIGATION REQUIRED ON MAINS PER 240.87
  
 FAULT CURRENT CALCLULATION PER 110.10 FOR THE SERVICE
 AND DOWNSTREAM PANELS.
  
 RISER SHOWS PANEL ISHB DIFFERENT THAN THE OTHER PANEL ?
 IS THIS A SPECIAL PANEL?