2018-05-07 06:24:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 BANYAN CAY FOUR STORY HOTEL
 ***THRESHOLD BUILDING***, POST TENSION 6"-8" SLABS, FRT
 TRUSSES, TYPE IIA
 ARCHITECT - ADACHE GROUP ARCHITECTS, DANIEL E. ADACHE
 AR7073
 ENGINEER - MUE ENGINEERS, INC (29348), MARCUS O.
 UNTERWEGER, PE63860
 MEP - TLC ENGINEERING
 MECHANICAL - JORGE E. REYES, PE54904
 ELECTRICAL - RALPH BAEZA, PE42641
 PLUMBING - JORGE E. REYES, PE54904
  
  
 1. OK
  
 2. COMMENT FROM FIRST REVIEW: A1.2.01 EXIT DISCHARGE
 NOT CLEAR; REVISE PLAN TO SHOW COMPLIANCE WITH FBC B
 1027.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT FBC B 1027
 REFERENCES "EXTERIOR EXIT STARIWAYS AND RAMPS" AND
 GIVES SOME EXPLANATION ABOUT ALL STAIRS BEING INTERIOR
 STAIRS.
  
 THE FBC 2014 BUILDING, SECTION 1027, IS TITLED "EXIT
 DISCHARGE". SECTION 1022 IS INTERIOR STAIRS AND RAMPS.
 SEE PREVIOUS COMMENT; REFERENCE WAS TO FBC B 1027, NOT
 FBC B 1022, AND SPECIFICALLY REFERENCES "EXIT
 DISCHARGE". IT IS NOT CLEAR WHY RESPONSE LETTER
 EXPLAINS SOMETHING UNRELATED.
  
 SEE FBC 1027.5, EXIT DISCHARGE SHALL PROVIDE A DIRECT
 AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY, SEE ALSO
 EXCEPTIONS. ALSO SEE COMMENT #3. SHEET A1.2.00 APPEARS
 TO SHOW COMPLIANCE EXCEPT AS NOTED IN OTHER COMMENTS,
 BUT INFORMATION REGARDING ACCESSIBILITY AND SLOPES NOT
 PROVIDED.
  
 COMPLIANCE WITH REQUIREMENTS FOR EXIT DISCHARGE
 ILLUMINATION NOT CLEAR; THIS PERMIT WILL BE ISSUED WITH
 PROVISO, COMPLIANCE WITH FBC B 1006 REQUIRED.
  
 FIRST FLOOR LIFE SAFETY PLAN A1.2.01 IS NOT CLEAR ON
 NUMBER OF OCCUPANTS IN EACH ROOM AS A SUMMARY WAS
 PROVIDED. IT APPEARS THAT EXIT CAPACITY IS ADEQUATE FOR
 EACH AREA, BUT COMPLIANCE WITH REQUIREMENT FOR EXIT
 DISCHARGE IS NOT CLEAR.
  
 FOR INSTANCE: THE PATH AT THE LEFT OF THE SITE LIFE
 SAFETY PLAN INDICATES "146 OCCUPANTS". FIRST FLOOR
 SHOWS 146 OCCUPANTS EXITING FROM THE STAIR AND EXIT
 CORRIDOR. BUT NO OCCUPANT LOAD WAS PROVIDED FOR MEETING
 ROOM #1, BALLROOM #1, ETC. WHICH ALSO TRAVEL ALONG THE
 SAME PATH IN THE EXIT DISCHARGE. A SUMMARY FOR EACH
 OCCUPANCY WAS PROVIDED, BUT AS THE OCCUPANCIES ARE IN
 DIFFERENT AREAS OF THE BUILDING, THE NUMBER USING THE
 GRAPHICALLY DEPICTED EXIT DISCHARGE IS NOT CLEAR.
  
 THE CIVIL PAGES INCLUDE ELEMENTS IN THE EXIT DISCHARGE
 WHICH ARE NOT SHOWN ON THE LIFE SAFETY SHEETS (APPEARS
 TO BE FENCES, GATES). PLEASE CORRELATE. FOR INSTANCE,
 CIVIL PAGE 2 OF 9 MASTER PLAN) WHICH SHOWS GATES IN THE
 MEANS OF EGRESS, AND THE SITE LIFE SAFETY PLAN A1.2.00.
 PLEASE CORRELATE AND NOTE THAT ALL GATES WILL INCLUDE
 PANIC HARDWARE (PER FBC B 1008.2. NO INFORMATION WAS
 PROVIDED REGARDING THE WIDTH OF THESE ELEMENTS.
  
 THE ELECTRICAL SITE PLAN E1.1.01 APPEARS TO CONFLICT
 WITH THE EXIT DISCHARGE (GENERATOR, OTHER ITEMS);
 PLEASE CORRELATE. IF THEY DO NOT CONLICT PROVIDE ENOUGH
 DIMENSIONS ON THE PLAN TO SHOW THAT THE GENERATOR IS
 NOT INTERFEREING WITH THE HATCHED EXIT DISCHARGE SHOWN
 ON OTHER SHEETS.
  
 ADVISORY ONLY; THE LANDSCAPE PLANS APPEAR TO CONFLICT
 WITH THE EXIT DISCHARGE. LANDSCAPE PERMIT REQUIRES A
 SEPARATE SUBMITTAL; PERMIT APPLICATION, FEES, AND PLANS
 AND ARE NOT REVIEWED BY BUILDING.
  
 ON THE ELECTRICAL PAGES, I WAS NOT ABLE TO LOCATE VOICE
 EVAC. SHEET E2.1.01 SHOWS A FIRE ALARM CONTROL PANEL,
 DETAILS ON E3.1.02, BUT I WAS UNABLE TO LOCATE THE
 LABEL "EVAC" ON THE FLOOR PLANS (PER ELECTRICAL LEGEND)
 AND E3.1.02 WAS NOT CLEAR. PLEASE DIRECT WHERE THIS
 INFORMATION CAN BE FOUND OR CLARIFY INTENT. NOTE THAT
 FBC B 1005.3.1 REQUIRES .3" PER OCCUPANT, BUT .2" WAS
 USED PER EXCEPTION.
  
 3. COMMENT FROM FIRST REVIEW: ACCESSIBLE MEANS OF
 EGRESS SELECTED NOT CLEAR; SEE FBC 1007, FBC A 207.1.
 REVISE PLAN TO STATE WHICH METHOD IS SELECTED AND
 CONFIRM COMPLIANCE WITH METHOD SELECTED; REVISE PLAN IF
 NECESSARY TO SHOW COMPLIANCE.
  
 2ND REVIEW, RESPONSE LETTER GIVES INFORMATION REGARDING
 STAIRS. THIS DOES NOT ADDRESS THE COMMENT.
  
 FBC B 1007 REFERS TO FBC A 207.1.
 FBC A 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000 AND
 2001 SUPPLEMENT OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE 2003 EDITION. COMPLIANCE WITH ONE OF
 THESE TWO METHODS OF COMPLIANCE IS NOT CLEAR;
 PARTICULARLY THE EXIT DISCHARGE (SEE ALSO IBC 2003
 1007.2).
  
 THIS ITEM HAS NOT BEEN REVIEWED.
  
 AS THE FINISHED FLOOR AFFECTS THE ACCESSIBLE ROUTE,
 EXIT DISCHARGE, AND ACCESSIBLE EXIT DISCHARGE,
 COMPLIANCE SHOULD BE DEMONSTRATED PRIOR TO ISSUANCE OF
 A FOUNDATION PERMIT - RESOLUTION TO COMMENTS #2 AND #3
 NEED TO BE RESOLVED PRIOR TO FOUNDATION PERMIT
 ISSUANCE.
  
 APPLICANT MAY SEND AN EMAIL EXPLAINING COMPLIANCE AND
 HOW THIS WILL BE ADDRESSED UPON RESUBMITTAL TO GET THIS
 ISSUE RESOLVED PRIOR TO REVIEW OF FOUNDATION PERMIT.
  
 4-6. OK
  
 7. COMMENT FROM FIRST REVIEW: A1.4.01B, FITNESS ROOM TO
 COMPLY WITH FBC A 1004, REVISE TO SHOW COMPLIANCE.
  
 IF DETAILS SUCH AS SPECIFIC TYPES OF MACHINES PROPOSED
 IS NOT AVAILABLE AT THIS TIME, REVISE THE PLAN TO SHOW
 GENERAL COMPLIANCE. INCLUDE NOTES REGARDING COMPLIANCE.
 THIS PERMIT WILL BE ISSUED WITH PROVISO, ISSUED AT
 CONTRACTOR'S RISK, PROVIDE A DETAILED PLAN AT
 INSPECTION. SUBJECT TO FIELD INSPECTOR'S DISCRETION,
 FITNESS CENTER PLAN MAY BE REQUIRED TO BE SUBMITTED FOR
 PLAN REVIEW.
  
 2ND REVIEW, CLEAR FLOOR SPACE WAS ADDED BUT IS ALMOST
 ILLEGIBLE. PLEASE DARKEN THESE LINES, AT LEAST TO THE
 GREY VALUE OF THE EQUIPENT. IT'S ABOUT .25 DARKNESS OF
 THE EQUIPMENT WHICH IS ABOUT .5 COMPARED TO THE
 BLACKLINES.
  
 I WAS UNABLE TO LOCATE NOTES REGARDING COMPLIANCE;
 PLEASE ADD NOTE OR PROVIDE ALL INFORMATION FOR REVIEW.
  
 8. OK
  
 9. ADVISORY; ENGINEER ADDED A NOTE RE: FRT FOR ALL
 WOOD. SEE SHEET S2.02A-R, PORTE COCHERE ROOF FRAMING
 NOTES, HEAVY TIMBER FRAMING PROPOSED. PLEASE NOTE THAT
 THIS IS ALSO REQUIRED TO BE FRT; PLAN HAS BEEN REDLINED
 IN THIS AND OTHER LOCATIONS.
  
 10-11. OK
  
 12. COMMENT FROM FIRST REVIEW: SOIL BEARING VALUES. THE
 TEST BY UNIVERSAL ENGINEERING SCIENCES REFERENCES THE
 TEST IS PRELIMINARY GEOTECHNICAL ENGINEERING REPORT
 BANYAN CAY- HOTEL PLEASE NOTE THE BORING SAMPLES TAKEN
 CH-1 AND CH-2 ARE SHOWN FOR THE CLUBHOUSE, THIS SOILS
 REPORT HAS NO BORINGS SHOWN IN THE REPORT FOR THE
 HOTEL. NOTE FOR THE TENNIS CLUB CENTER UP TO 6 FEET OF
 MUCK WAS ENCOUNTERED WITHIN THE BUILDING FOOTPRINT.
 PLEASE COMPLY WITH: 2014 FBC-B 1803.3 BASIS OF
 INVESTIGATION.
 SOIL CLASSIFICATION SHALL BE BASED ON OBSERVATION AND
 ANY NECESSARY TESTS OF THE MATERIALS DISCLOSED BY
 BORINGS, TEST PITS OR OTHER SUBSURFACE EXPLORATION MADE
 IN APPROPRIATE LOCATIONS. ADDITIONAL STUDIES SHALL BE
 MADE AS NECESSARY TO EVALUATE SLOPE STABILITY, SOIL
 STRENGTH, POSITION AND ADEQUACY OF LOAD-BEARING SOILS,
 THE EFFECT OF MOISTURE VARIATION ON SOIL-BEARING
 CAPACITY, COMPRESSIBILITY, LIQUEFACTION AND
 EXPANSIVENESS.
  
 2ND REVIEW, NOT ADDRESSED. ENGINEER OF RECORD IS TO
 REVIEW THE SOILS, EITHER WITH A SHOP DRAWING REVIEW
 STAMP OR BY INCORPORATING A REFERENCE INTO THE PLAN.
 THE SOILS REPORT WAS PROVIDED FOR THE FOUNDATION PERMIT
 APPLICATION (17010911). AFTER THE FOUNDATION PERMIT IS
 ISSUED, THE SOILS WILL BE PUBLIC RECORD AND IS NOT
 NEEDED FOR THIS PERMIT. IF YOU RESUBMIT PRIOR TO
 ISSUANCE OF FOUNDATION PERMIT, PLEASE INCLUDE IN YOUR
 RESUBMITTAL.
  
 13-15. OK
  
  
 16. SEE FBC A 209.2.1, 209.4, LABEL ALL PASSENGER
 LOADING ZONES ON THE PLAN, REVISE PLAN TO SHOW
 COMPLIANCE WITH REQUIREMENTS.
  
 2ND REVIEW, PLEASE SUBMIT REQUEST FOR AN ALTERNATE
 DESIGN TO BE ACCEPTED VIA EMAIL. THE LETTER SHOULD
 INCLUDE A PLAN SHOWING WHAT IS PROPOSED ALONG WITH THE
 HOTEL SOP FOR THE LOADING ZONE ALONG WITH RATIONALE.
  
 17-24. OK
  
 25. COMMENT FROM FIRST REVIEW: SHEET A5.1.04 IS BLANK,
 FBC 107 PROVIDE INFORMATION INCLUDING PANIC HARDWARE
 FBC B 1008.1.10.
  
 2ND REVIEW: A5.1.04 HAS BEEN UPDATED, BUT REFERS TO
 HARDWARE SETS. HARDWARE SETS ARE DESCRIBED ON SHEET
 A5.1.05. A SEARCH OF THE WORD "PANIC" AND "FIRE"
 YIELDED NO RESULTS.
  
 TO EXPEDITE PLAN REVIEW: IF AN ADDITIONAL COLUMN WITH
 "PANIC BAR" OR "FIRE EXIT HARDWARE" IS ADDED, AND A
 MARK TO INDICATE WHICH DOORS WILL HAVE PANIC BARS, IN
 PLAN REVIEW A SPOT CHECK WILL BE DONE, AND A PROVISO
 ADDED (ALL DOORS AND GATES IN THE MEANS OF EGRESS FOR
 ASSEMBLY OCCUPANCY, ELECTRICAL ROOMS, STAIRS, AND OTHER
 LOCATIONS REQUIRED ARE TO HAVE PANIC BARS OR FIRE EXIT
 HARDWARE IN ACCORDANCE WITH FBC B 1008.1.10).
  
 26. BUILT IN BENCHES TO COMPLY WITH FBC A 903.
 27. DRESSING, FITTING AND LOCKER ROOMS TO COMPLY WITH
 FBC A 222, REVISE PLAN TO SHOW COMPLIANCE.
 28. SPA RECEPTION/ RETAIL DESK, ANY OTHER CHECK OUT
 AREAS, SEE FBC A 904 NOTE ON PLAN AND PROVIDE A DETAIL
 2ND REVIEW: RESPONSE TO 26, 27, 28 REFERS TO D SHEETS;
 THESE PAGES ARE NOT SIGNED AND SEALED AND IT IS NOT
 CLEAR WHO IS TAKING RESPONSIBILITY FOR THE PAGES.
 PLEASE REMOVE THE SHEETS AS IT APPEARS MOST OF THE
 INFORMATION IS NOT REQUIRED. ITEMS 26, 27, AND 28 CAN
 BE A PROVISO ITEM.
  
 29. OK
  
 30. ARCHITECT'S TITLE BLOCK LACKS THE ARCHITECT
 BUSINESS NUMBER, REVISE TO INCLUDE, FS481, FAC 61G16.
  
 2ND REVIEW, AR7073 IS THE ARCHITECT'S LICENSE NUMBER AS
 AN INDIVIDUAL. THE FIRM, ADACHE GROUP ARCHITECTS, IS
 REQUIRED TO HAVE A ARCHITECT BUSINESS NUMBER. PER DBPR
 WEBSITE, THIS IS AA26002281. PLEASE ADD THIS NUMBER TO
 ALL SHEETS, BUT ONLY UPLOAD PAGES WHICH CHANGE DUE TO
 COMMENTS TO AVOID A LENGTHY 3RD REVIEW CYCLE.
  
 31. SEE SIGNATURE REVIEW.
  
 32. 2ND REVIEW; THE CERTIFICATE OF AUTHORIZATION IS
 LACKING (FMEP), FS471, FAC61G15-23. PLEASE ADD TO ALL
 SHEETS, BUT ONLY UPLOAD PAGES WHICH CHANGE DUE TO
 COMMENTS.
  
 33. OK
  
 34. SEE SIGNATURE REVIEW.
  
 35. SEE IMPACT FEE REVIEW.
  
 NEW COMMENTS
  
 37. 05.31.2017 BCR FOOD SERVICE SPECIFICATIONS AND
 11.25.2016 BCR FOOD SERVICE PROPOSED LAYOUT WERE
 UPLOADED INTO THE "DRAWINGS" FOLDER RATHER THAN
 "SUPPORTING DOCUMENTS"; PLEASE MOVE (OR REMOVE) FROM
 DRAWINGS FOLDER AND ENSURE THAT ALL REQUIRED
 INFORMATION IS IN THE SUPPORTING DOCUMENTS FOLDER.
  
 38. FBC B 603.1, A4.4.02 DETAIL 12 SHOWS POLYSTYRENE
 OUTRIGGER AT METAL ROOFS AND POSSIBLY OTHER LOCATIONS,
 OTHER DETAILS. PLEASE PROVIDE MORE INFORMATION VIA
 EMAIL REGARDING HEIGHT OF LOCATIONS PROPOSED (OVER
 30'?), OVER EXITS. A4.4.03 SHOWS EXTERIOR FOAM; PROVIDE
 INFORMATION VIA EMAIL. ARE THESE PRODUCTS
 NONCOMBUSTIBLE?
  
 39. ADVISORY ONLY, NEW SHEET A4.5.03 DETAIL 8 SHOWS A 1
 HOUR GLASS WALL AND REFERS TO WATER CURTAIN WALL. NOTE
 THAT THE GLASS DETAIL SHOWS HORIZONTAL MULL BARS.
 PLEASE NOTE THAT, IF THIS OPTION IS ELECTED VIA A
 REVISION, EITHER THE HORIZONTAL MULL BARS ARE TO BE
 REMOVED OR DOR IS REQUIRED TO REVIEW SPRINKLER HEAD
 SPEC SHEETS TO CONFIRM THAT HORIZONTAL MULLIONS ARE
 PERMITTED. IF THIS OPTION IS ELECTED VIA A REVISION,
 PLANS ARE TO BE REVISED AND THE WINDOW SPRINKLER SPEC
 SHEET IS TO BE SUBMITTED.
  
 40. FBC 107, NEW SHEET 3-A4.5.04 SHOWS "CONTENTIOUS
 WOOD BLOCKING", CLARIFY OR REVISE (DO YOU MEAN
 CONTINUOUS?).
  
 41. ADVISORY ONLY; SHEET D0.0.00 SHOWS A PLATFORM BED.
 IT IS NOT CLEAR IF THIS BED COMPLIES WITH FBC A
 806.4(II), OPEN-FRAME TYPE BEDS REQUIRED. THIS WILL BE
 A PROVISO ITEM.
  
 42. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE
 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515,
 [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN
 THIS IS COMPLETE.
  
 B. SEPARATE PERMITS REQUIRED. SUB PERMITS FOR
 MECHANICAL, ELECTRICAL, PLUMBING ARE REQUIRED. SEPARATE
 PERMITS (APPLICATION, FEES, PLANS, REVIEWS) REQUIRED
 FOR ALL OTHER ITEMS SUCH AS PARKING, SIGNAGE, ETC.
  
 C. COMPLIANCE WITH FBC B 1006, MEANS OF EGRESS
 ILLUMINATION, INCLUDING EXIT DISCHARGE, REQUIRED.
  
 D. VOICE EVAC REQUIRED (NOTE 35, SHEET E3.1.02).
  
 E. ADVISORY ONLY; THE LANDSCAPE PLANS APPEAR TO
 CONFLICT WITH THE EXIT DISCHARGE. LANDSCAPE PERMIT
 REQUIRES A SEPARATE SUBMITTAL; PERMIT APPLICATION,
 FEES, AND PLANS AND ARE NOT REVIEWED BY BUILDING.
  
 F. PRODUCT APPROVALS FOR ALL COMPONENTS AND CLADDING
 ARE TO BE SUBMITTED, REVIEWED BY DESIGNER OF RECORD,
 REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 G. SHORING/RESHORE ENGINEERING ARE REQUIRED TO BE
 SUBMITTED, REVIEWED, AND ISSUED PRIOR TO INSTALLATION.
 FAILURE TO DO SO WILL RESULT IN A STOP WORK ORDER.
  
 H. AN ENGINEERED CONSTRUCTION GUARD RAIL DETAIL IS
 REQUIRED PRIOR TO INSTALLATION. THIS MAY BE SUBMITTED
 AS A SUBMITTAL ALONG WITH THE SHORING/RESHORE, BUT MAY
 BE PROVIDED IN THE FIELD TO KEN CONRAD, SUBJECT TO HIS
 APPROVAL.
  
 I. RECORDED REPLAT REQUIRED PRIOR TO C.O.; PROVIDE
 BOOK/PAGE VIA EMAIL.
  
  
  
  