Notes
Date Text
2017-04-05 12:58:381ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17020796
 4/3/17
  
 1) THE UPLOADED DIGITAL MECHANICAL PLANS, ENERGY AND AC
 CALCULATIONS REQUIRE ELECTRONIC SEALS AND SIGNATURES BY
 THE ENGINEER OF RECORD IN ACCORDANCE WITH SECTION
 471.025 FLORIDA STATUTES, AND SECTION 61G15-23.005
 FLORIDA ADMINISTRATIVE CODE.
  
 2) ADVISORY: SEPARATE PERMITS AND PLANS ARE REQUIRED
 FOR THE KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION
 SYSTEMS, AND THE WALK-IN COOLERS AND FREEZERS.
 REGARDING THE KITCHEN HOODS PLEASE SEE SECTION 508.1.1
 FBC-14 MECHANICAL- MAKEUP AIR TEMPERATURE. THE CURRENT
 PLAN IS NOT IN COMPLIANCE.
  
 3) THE AC COOLING AND HEATING CALCULATIONS ARE
 INCORRECTLY SPECIFYING MIAMI AS THE LOCATION AND ORIGIN
 OF DESIGN DATA FOR THE PROJECT.
  
 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 GUEST ROOMS AND ALL OTHER HABITABLE ROOMS SERVED BY THE
 FAN COIL UNITS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 5) REGARDING THE UPLOADED AC CALCULATIONS PLEASE NOTE
 THE TOTAL COOLING CAPACITIES FOR AHU?S 3 & 5 SHOWN IN
 THE SCHEDULE ON SHEET M-0.0.02- (68.6 & 63.3 MBH) DO
 NOT MATCH THE CALCULATED LOADS OF (169.3 & 127 MBH).
  
 6) REFER TO TABLE C403.2.3(7) FBC-14 ENERGY
 CONSERVATION: IT APPEARS THE EFFICIENCY CRITERIA FOR
 THE CHILLER SHOWN ON THE ENERGYGAUGE COMPLIANCE
 SUBMITTAL IS INCORRECT FOR AN AIR-COOLED CHILLER.
  
 7) SHEET M-0.0.0.1: PLEASE UPDATE THE SMACNA SECOND
 EDITION REFERENCE AND PROVIDE DUCT HANGER TABLES IN
 COMPLIANCE WITH THE 2005 THIRD EDITION.
  
 8) SHEET M-0.0.03: PLEASE UPDATE THE ASHRAE 62.1-2004
 REFERENCE AND PROVIDE VENTILATION RATES IN ACCORDANCE
 WITH THE CURRENT 2010 STANDARD IN EFFECT. PLEASE SEE
 TABLE 6-1 ASHRAE 62.1-2010, OR TABLE 403.3 FBC-14
 MECHANICAL AND PROVIDE THE VENTILATION RATES FOR THE
 GUESTROOMS.
  
 9) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR
 HANDLERS AND FAN COIL UNITS- SECTION 307.
  
 10) PROVIDE ENLARGED KITCHEN AND FOOD SERVICE DRAWINGS.
  
 11) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO
 THE GAS-FIRE COOKING APPLIANCES AND WATER HEATERS AND
 PROVIDE CALCULATIONS- REFER TO SECTION 304 FBC-14 FUEL
 GAS. PROVIDE WATER HEATER VENTING DIAGRAMS THAT
 INDICATE THE TYPE AND SIZE OF THE VENTS, TOTAL VENT
 RUNS AND TERMINATION LOCATIONS.
  
 12) M-1.3.01A: LABEL THE EXHAUST RISER LOCATIONS FOR
 KEF-4 & 5.
  
 13) M-1.3.01A: MISSING FIRE DAMPERS- A) 8X8 DUCT
 PENETRATING THE UNISEX RESTROOM/BOARDROOM #1 WALL. B)
 30X14 DUCT AT CORRIDOR 1110/BANQUET PANTRY WALL.
  
 14) M-1.3.01A & B: PROVIDE THE FLEX DUCT SIZES ON THE
 PLAN.
  
 15) M-1.3.01A & B: SHOW THE LOCATIONS OF ALL REQUIRED
 ACCESS PANELS FOR ALL FAN COIL UNITS AND VAV BOXES
 LOCATED ABOVE HARD CEILINGS- SECTION 306.1.
  
 16) M-1.3.01A & B: PROVIDE DUCT SMOKE DETECTORS IN THE
 RETURN AIR SYSTEMS OF THE AHU'S- SECTION 606.2.1.
  
 17) M-1.3.01A & B: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE KITCHENS, THE TOILET AND
 BATHROOMS, THE LOCKER ROOMS, AND THE MANICURE/PEDICURE
 SPA- SEE TABLE 403.3. PROVIDE ENLARGED DRAWINGS OF THE
 EXHAUST SYSTEMS THAT INDICATE THE TYPES AND SIZES OF
 EXHAUST DUCTS, TOTAL EXHSAUST VENT RUNS, AND INLET AND
 OUTLET LOCATIONS- SEE TABLE 403.3 FOOTNOTE B AND H.
  
 18) M-1.3.01A & B: PROVIDE AIR BALANCE CALCULATIONS.
  
 19) M-1.3.01A & B: DEMAND CONTROLLED VENTILATION IS
 REQUIRED FOR THE DINING/LOUNGE, FITNESS, AND BALLROOMS
 1 & 2- REFER TO SECTION C403.2.5.1 AND PROVIDE A MEANS
 OF COMPLIANCE ON THE PLAN.
  
 20) M-1.3.01A & B: THE LOCATIONS AND REQUIRED CLEARANCE
 DISTANCES FOR O/A INTAKES AND EXHAUST OUTLETS SHALL BE
 IN COMPLIANCE WITH SECTIONS 401.4 AND 501.3.1. PLEASE
 PLACE NOTES OR SHOW CLEARANCE DISTANCE MEASUREMENTS ON
 THE PLAN TO VERIFY COMPLIANCE.
  
 21) M-1.3.01A: CLARIFY HOW O/A IS BEING PROVIDED TO
 AHU-5. IT APPEARS THE INLET AT MECHANICAL 11120 IS
 LABELED MAKEUP AIR.
  
 22) M-1.3.01B: MISSING FIRE DAMPERS FOR DUCTS
 PENETRATING A) CORRIDOR 1135/SECURITY-RECEIVING WALL.
 B) DUCT PENETRATING THE CORRIDOR 1157/F.O. ADMIN WALL.
  
 23) M-1.3.01B: LABEL THE O/A INLET FOR AHU-3.
  
 24) M-1.3.01C: PROVIDE AN ENLARGED DETAIL SHOWING THE
 UNDERGROUND CHILLED WATER PIPING RUNS FROM THE CHILLER
 AND PUMPS ETC. INTO THE BUILDING. INDICATE THE TYPE AND
 SIZE OF PIPING, TYPE AND THICKNESS OF INSULATION.
  
 25) M-1.3.01C: WIND LOAD ENGINEERING IS REQUIRED FOR
 ANCHORING THE CHILLER, THE PUMPS, AIR SEPARATOR,
 EXPANSION TANK, AND THE CHILLED WATER PIPING- SEE
 SECTION 301.15 . PLEASE SEE SECTION 1609 FBC-14
 BUILDING AND PROVIDE DETAILS AND DESIGN CRITERIA.
  
 26) M-1.3.02A, 2B, 3A, 3B, 4A, 4B: LABEL THE O/A
 INTAKES FOR THE FC UNITS, AND PROVIDE AUTOMATIC SHUTOFF
 DAMPERS FOR THE O/A DUCTS- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
 27) M-1.5.02, 03, 04, 05: PROVIDE RETURN AIR FOR THE FC
 UNITS IN THE GUESTROOMS, AND PROVIDE AN ENLARGED DETAIL
 SHOWING HOW ACCESS WILL BE PROVIDED FOR MAINTENANCE AND
 REPLACEMENT OF THE UNITS- SECTION 306.1.
  
 28) M-3.0.00: PROVIDE EITHER NOTES OR DETAILS ON THE
 RISER PLAN INDICATING THE TYPE OF O/A DUCTWORK,
 LOCATIONS OF FIRE DAMPERS ETC.
  
 29) PLEASE PROVIDE TOILET EXHAUST RISER DRAWINGS
 INCLUDING THE TYPES AND SIZES OF EXHAUST DUCTS,
 VERTICAL RUN LENGTHS OF SUB-DUCTS, AND EXHAUST CFMS.
  
 30) M-1.3.04A, 4B, 5A & 5B: PROVIDE WIND LOAD
 ENGINEERING FOR TIE-DOWN OF THE ROOFTOP DUCTWORK, THE
 TOILET EXHAUST OUTLETS, AND THE O/A INTAKE HOODS.
 PLEASE NOTE THAT FLORIDA PRODUCT APPROVALS AND/OR
 MIAMI-DADE NOA'S ARE REQUIRED FOR ANY MANUFACTURED
 EXTERIOR MECHANICAL EQUIPMENT SUPPORTS OR STANDS.
  
 31) M-1.3.05A, 5B: IT APPEARS THAT FLAMEBAR DUCTWORK IS
 MISSPELLED AS BAMEBAR- PLEASE CORRECT.
  
 32) M-1.3.04B: THE LOCATION OF THE EXHAUST OUTLETS FOR
 KEF- 1, 2 & 3 APPEAR TO BE NON-COMPLIANT WITH SECTION
 506.13.3 WHICH REQUIRES A 10' HORIZONTAL CLEARANCE
 DISTANCE FROM THE OUTLETS TO PARTS OF THE SAME OR
 CONTIGUOUS BUILDING. PLEASE SEE THE EXCEPTION UNDER
 THIS SECTION FOR FURTHER INFORMATION.
  
 33) M-1.3.05A: THE LOCATIONS OF THE EXHAUST OUTLETS FOR
 KEF-4 & 5 APPEAR TO BE NON-COMPLIANT WITH SECTIONS
 506.3.13.1 & 506.3.13.3. PLEASE PROVIDE CLEARANCE
 DISTANCE MEASUREMENTS. PLEASE NOTE THAT ADDITIONAL
 COMMENTS REGARDING THE KITCHEN COOKING EXHAUST SYSTEMS
 MAY OCCUR AFTER COMPLETE PLANS AND SPECIFICATIONS ARE
 SUBMITTED FOR REVIEW UNDER SEPARATE PERMIT.
  
 34) INDICATE HOW ACCESS IS BEING PROVIDED FOR
 SERVICEABLE MECHANICAL EQUIPMENT LOCATED ON THE
 BUILDING ROOFTOPS (I.E. EF-4-1, EF-5-1, KEF-4 & 5)-
 SECTION 306.5. ADDITIONALLY PLEASE NOTE THAT ACCESS
 SHALL NOT REQUIRE WALKING ON ROOFS WITH A SLOPE GREATER
 THAN 4 UNITS VERTICAL IN 12 HORIZONTAL.
  
 35) PROVIDE FL. PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR THE O/A INTAKE AND EXHAUST OUTLET LOUVERS.
  
 36) PROVIDE APPROVED PRODUCT SUBMITTAL DOCUMENTS FOR
 THE FLAMEBAR DUCT, THE MOTORIZED DAMPERS, AND THE CO2
 SENSORS.
  