2017-04-05 12:58:38 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| CODES |
| PERMIT #17020796 |
| 4/3/17 |
| |
| 1) THE UPLOADED DIGITAL MECHANICAL PLANS, ENERGY AND AC |
| CALCULATIONS REQUIRE ELECTRONIC SEALS AND SIGNATURES BY |
| THE ENGINEER OF RECORD IN ACCORDANCE WITH SECTION |
| 471.025 FLORIDA STATUTES, AND SECTION 61G15-23.005 |
| FLORIDA ADMINISTRATIVE CODE. |
| |
| 2) ADVISORY: SEPARATE PERMITS AND PLANS ARE REQUIRED |
| FOR THE KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION |
| SYSTEMS, AND THE WALK-IN COOLERS AND FREEZERS. |
| REGARDING THE KITCHEN HOODS PLEASE SEE SECTION 508.1.1 |
| FBC-14 MECHANICAL- MAKEUP AIR TEMPERATURE. THE CURRENT |
| PLAN IS NOT IN COMPLIANCE. |
| |
| 3) THE AC COOLING AND HEATING CALCULATIONS ARE |
| INCORRECTLY SPECIFYING MIAMI AS THE LOCATION AND ORIGIN |
| OF DESIGN DATA FOR THE PROJECT. |
| |
| 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| GUEST ROOMS AND ALL OTHER HABITABLE ROOMS SERVED BY THE |
| FAN COIL UNITS- SECTION C403.2.1 FBC-14 ENERGY |
| CONSERVATION. |
| |
| 5) REGARDING THE UPLOADED AC CALCULATIONS PLEASE NOTE |
| THE TOTAL COOLING CAPACITIES FOR AHU?S 3 & 5 SHOWN IN |
| THE SCHEDULE ON SHEET M-0.0.02- (68.6 & 63.3 MBH) DO |
| NOT MATCH THE CALCULATED LOADS OF (169.3 & 127 MBH). |
| |
| 6) REFER TO TABLE C403.2.3(7) FBC-14 ENERGY |
| CONSERVATION: IT APPEARS THE EFFICIENCY CRITERIA FOR |
| THE CHILLER SHOWN ON THE ENERGYGAUGE COMPLIANCE |
| SUBMITTAL IS INCORRECT FOR AN AIR-COOLED CHILLER. |
| |
| 7) SHEET M-0.0.0.1: PLEASE UPDATE THE SMACNA SECOND |
| EDITION REFERENCE AND PROVIDE DUCT HANGER TABLES IN |
| COMPLIANCE WITH THE 2005 THIRD EDITION. |
| |
| 8) SHEET M-0.0.03: PLEASE UPDATE THE ASHRAE 62.1-2004 |
| REFERENCE AND PROVIDE VENTILATION RATES IN ACCORDANCE |
| WITH THE CURRENT 2010 STANDARD IN EFFECT. PLEASE SEE |
| TABLE 6-1 ASHRAE 62.1-2010, OR TABLE 403.3 FBC-14 |
| MECHANICAL AND PROVIDE THE VENTILATION RATES FOR THE |
| GUESTROOMS. |
| |
| 9) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR |
| HANDLERS AND FAN COIL UNITS- SECTION 307. |
| |
| 10) PROVIDE ENLARGED KITCHEN AND FOOD SERVICE DRAWINGS. |
| |
| 11) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO |
| THE GAS-FIRE COOKING APPLIANCES AND WATER HEATERS AND |
| PROVIDE CALCULATIONS- REFER TO SECTION 304 FBC-14 FUEL |
| GAS. PROVIDE WATER HEATER VENTING DIAGRAMS THAT |
| INDICATE THE TYPE AND SIZE OF THE VENTS, TOTAL VENT |
| RUNS AND TERMINATION LOCATIONS. |
| |
| 12) M-1.3.01A: LABEL THE EXHAUST RISER LOCATIONS FOR |
| KEF-4 & 5. |
| |
| 13) M-1.3.01A: MISSING FIRE DAMPERS- A) 8X8 DUCT |
| PENETRATING THE UNISEX RESTROOM/BOARDROOM #1 WALL. B) |
| 30X14 DUCT AT CORRIDOR 1110/BANQUET PANTRY WALL. |
| |
| 14) M-1.3.01A & B: PROVIDE THE FLEX DUCT SIZES ON THE |
| PLAN. |
| |
| 15) M-1.3.01A & B: SHOW THE LOCATIONS OF ALL REQUIRED |
| ACCESS PANELS FOR ALL FAN COIL UNITS AND VAV BOXES |
| LOCATED ABOVE HARD CEILINGS- SECTION 306.1. |
| |
| 16) M-1.3.01A & B: PROVIDE DUCT SMOKE DETECTORS IN THE |
| RETURN AIR SYSTEMS OF THE AHU'S- SECTION 606.2.1. |
| |
| 17) M-1.3.01A & B: PROVIDE EXHAUST VENTILATION |
| CALCULATIONS FOR THE KITCHENS, THE TOILET AND |
| BATHROOMS, THE LOCKER ROOMS, AND THE MANICURE/PEDICURE |
| SPA- SEE TABLE 403.3. PROVIDE ENLARGED DRAWINGS OF THE |
| EXHAUST SYSTEMS THAT INDICATE THE TYPES AND SIZES OF |
| EXHAUST DUCTS, TOTAL EXHSAUST VENT RUNS, AND INLET AND |
| OUTLET LOCATIONS- SEE TABLE 403.3 FOOTNOTE B AND H. |
| |
| 18) M-1.3.01A & B: PROVIDE AIR BALANCE CALCULATIONS. |
| |
| 19) M-1.3.01A & B: DEMAND CONTROLLED VENTILATION IS |
| REQUIRED FOR THE DINING/LOUNGE, FITNESS, AND BALLROOMS |
| 1 & 2- REFER TO SECTION C403.2.5.1 AND PROVIDE A MEANS |
| OF COMPLIANCE ON THE PLAN. |
| |
| 20) M-1.3.01A & B: THE LOCATIONS AND REQUIRED CLEARANCE |
| DISTANCES FOR O/A INTAKES AND EXHAUST OUTLETS SHALL BE |
| IN COMPLIANCE WITH SECTIONS 401.4 AND 501.3.1. PLEASE |
| PLACE NOTES OR SHOW CLEARANCE DISTANCE MEASUREMENTS ON |
| THE PLAN TO VERIFY COMPLIANCE. |
| |
| 21) M-1.3.01A: CLARIFY HOW O/A IS BEING PROVIDED TO |
| AHU-5. IT APPEARS THE INLET AT MECHANICAL 11120 IS |
| LABELED MAKEUP AIR. |
| |
| 22) M-1.3.01B: MISSING FIRE DAMPERS FOR DUCTS |
| PENETRATING A) CORRIDOR 1135/SECURITY-RECEIVING WALL. |
| B) DUCT PENETRATING THE CORRIDOR 1157/F.O. ADMIN WALL. |
| |
| 23) M-1.3.01B: LABEL THE O/A INLET FOR AHU-3. |
| |
| 24) M-1.3.01C: PROVIDE AN ENLARGED DETAIL SHOWING THE |
| UNDERGROUND CHILLED WATER PIPING RUNS FROM THE CHILLER |
| AND PUMPS ETC. INTO THE BUILDING. INDICATE THE TYPE AND |
| SIZE OF PIPING, TYPE AND THICKNESS OF INSULATION. |
| |
| 25) M-1.3.01C: WIND LOAD ENGINEERING IS REQUIRED FOR |
| ANCHORING THE CHILLER, THE PUMPS, AIR SEPARATOR, |
| EXPANSION TANK, AND THE CHILLED WATER PIPING- SEE |
| SECTION 301.15 . PLEASE SEE SECTION 1609 FBC-14 |
| BUILDING AND PROVIDE DETAILS AND DESIGN CRITERIA. |
| |
| 26) M-1.3.02A, 2B, 3A, 3B, 4A, 4B: LABEL THE O/A |
| INTAKES FOR THE FC UNITS, AND PROVIDE AUTOMATIC SHUTOFF |
| DAMPERS FOR THE O/A DUCTS- SECTION C403.2.4.4 FBC-14 |
| ENERGY CONSERVATION. |
| |
| 27) M-1.5.02, 03, 04, 05: PROVIDE RETURN AIR FOR THE FC |
| UNITS IN THE GUESTROOMS, AND PROVIDE AN ENLARGED DETAIL |
| SHOWING HOW ACCESS WILL BE PROVIDED FOR MAINTENANCE AND |
| REPLACEMENT OF THE UNITS- SECTION 306.1. |
| |
| 28) M-3.0.00: PROVIDE EITHER NOTES OR DETAILS ON THE |
| RISER PLAN INDICATING THE TYPE OF O/A DUCTWORK, |
| LOCATIONS OF FIRE DAMPERS ETC. |
| |
| 29) PLEASE PROVIDE TOILET EXHAUST RISER DRAWINGS |
| INCLUDING THE TYPES AND SIZES OF EXHAUST DUCTS, |
| VERTICAL RUN LENGTHS OF SUB-DUCTS, AND EXHAUST CFMS. |
| |
| 30) M-1.3.04A, 4B, 5A & 5B: PROVIDE WIND LOAD |
| ENGINEERING FOR TIE-DOWN OF THE ROOFTOP DUCTWORK, THE |
| TOILET EXHAUST OUTLETS, AND THE O/A INTAKE HOODS. |
| PLEASE NOTE THAT FLORIDA PRODUCT APPROVALS AND/OR |
| MIAMI-DADE NOA'S ARE REQUIRED FOR ANY MANUFACTURED |
| EXTERIOR MECHANICAL EQUIPMENT SUPPORTS OR STANDS. |
| |
| 31) M-1.3.05A, 5B: IT APPEARS THAT FLAMEBAR DUCTWORK IS |
| MISSPELLED AS BAMEBAR- PLEASE CORRECT. |
| |
| 32) M-1.3.04B: THE LOCATION OF THE EXHAUST OUTLETS FOR |
| KEF- 1, 2 & 3 APPEAR TO BE NON-COMPLIANT WITH SECTION |
| 506.13.3 WHICH REQUIRES A 10' HORIZONTAL CLEARANCE |
| DISTANCE FROM THE OUTLETS TO PARTS OF THE SAME OR |
| CONTIGUOUS BUILDING. PLEASE SEE THE EXCEPTION UNDER |
| THIS SECTION FOR FURTHER INFORMATION. |
| |
| 33) M-1.3.05A: THE LOCATIONS OF THE EXHAUST OUTLETS FOR |
| KEF-4 & 5 APPEAR TO BE NON-COMPLIANT WITH SECTIONS |
| 506.3.13.1 & 506.3.13.3. PLEASE PROVIDE CLEARANCE |
| DISTANCE MEASUREMENTS. PLEASE NOTE THAT ADDITIONAL |
| COMMENTS REGARDING THE KITCHEN COOKING EXHAUST SYSTEMS |
| MAY OCCUR AFTER COMPLETE PLANS AND SPECIFICATIONS ARE |
| SUBMITTED FOR REVIEW UNDER SEPARATE PERMIT. |
| |
| 34) INDICATE HOW ACCESS IS BEING PROVIDED FOR |
| SERVICEABLE MECHANICAL EQUIPMENT LOCATED ON THE |
| BUILDING ROOFTOPS (I.E. EF-4-1, EF-5-1, KEF-4 & 5)- |
| SECTION 306.5. ADDITIONALLY PLEASE NOTE THAT ACCESS |
| SHALL NOT REQUIRE WALKING ON ROOFS WITH A SLOPE GREATER |
| THAN 4 UNITS VERTICAL IN 12 HORIZONTAL. |
| |
| 35) PROVIDE FL. PRODUCT APPROVALS AND/OR MIAMI-DADE |
| NOA'S FOR THE O/A INTAKE AND EXHAUST OUTLET LOUVERS. |
| |
| 36) PROVIDE APPROVED PRODUCT SUBMITTAL DOCUMENTS FOR |
| THE FLAMEBAR DUCT, THE MOTORIZED DAMPERS, AND THE CO2 |
| SENSORS. |
| |