Date |
Text |
2017-03-23 11:31:25 | 3200 NORTH CONGRESS AVENUE - HOTEL |
| PERMIT #17020796 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. |
| |
| NO INFORMATION SUBMITTED FOR POOL, POOL DECK, WEDDING |
| STAGE, CONCERT LAWN, EVENT TENT, PHASE II OR PARKING |
| GARAGE. THESE AREAS HAVE NOT BEEN REVIEWED OR APPROVED |
| AT THIS TIME. |
| |
| PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN |
| TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE |
| PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE |
| PROVIDED AS REQUIRED BY THE AUTHORITY HAVING |
| JURISDICTION. |
| TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS |
| WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE |
| FOLLOWING: |
| PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| |
| PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER |
| MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE |
| INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO |
| CONSTRUCTION WORK. |
| |
| PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE |
| PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND |
| SIDES AND 4'-0" TO THE BACKSIDE OF THE STEAMER CAP. |
| |
| PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT |
| ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO |
| ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 TONS. |
| ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT |
| LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL |
| CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. |
| |
| PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE |
| MARKED WITH FREESTANDING SIGNS READING, "FIRE LANE - NO |
| PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL |
| BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS |
| AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE |
| BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE |
| TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART. |
| |
| SHEET A-0.0.02: APPLICABLE CODES SECTION INDICATES, |
| "BROWARD COUNTY AMENDMENTS TO THE FLORIDA FIRE |
| PREVENTION CODE." |
| |
| SHEET A-1.2.01: EGRESS PLAN DOES NOT SHOW ENOUGH DETAIL |
| REGARDING ALL EXITS DISCHARGING TO A PUBLIC WAY. |
| SEVERAL EXIT DISCHARGE APPEAR TO TERMINATE DIRECTLY |
| OUTSIDE OF THE BUILDING AND DO NOT PROVIDE A MEANS OF |
| EGRESS TO ACHIEVE A SAFE DISTANCE AWAY FROM THE |
| BUILDING SUCH AS PRE-FUNCTION #1318, BALLROOM #2, AND |
| SALE/ADMIN TO NAME A FEW. |
| |
| SHEET A-1.2.01: NEARLY HALF THE EXITS DISCHARGE ONTO |
| THE POOL DECK IN LIEU OF A PUBLIC WAY. A LIFE SAFETY |
| PLAN IS NEEDED FOR THE FIRST FLOOR AND POOL DECK IF THE |
| DECK IS TO BE USED HOTEL OCCUPANT EGRESS. HOW WILL |
| UNOBSTRUCTED EGRESS BE PROVIDED AND MAINTAINED ON THE |
| POOL DECK LEADING TO A PUBLIC WAY? HOW DO THE |
| ADDITIONAL LARGE ASSEMBLY SPACES (TIKI BAR, WEDDING |
| STAGE, CONCERT LAWN, EVENT TENT AND PHASE II) AFFECT |
| TOTAL EGRESS PLAN? |
| |
| SHEET A-1.2.01: NO FIRE PROTECTION RATING SHOWN AROUND |
| FIRE PUMP ROOM. |
| |
| SHEET A-1.2.02: NO FIRE PROTECTION RATING SHOWN AROUND |
| STAIR #3 (TYPICAL UPPER FLOORS) AND ELEVATOR SHAFT AT |
| COLUMN INTERSECTION B/24. |
| |
| SHEET A-1.2.04 & SHEET M-1.3.04B: HOUSEKEEPING #4001 |
| NEEDS A TWO-HOUR FIRE RESISTANCE RATING AND 90 MINUTE |
| FIRE RATED DOOR. WHERE THE GREASE DUCT SYSTEM CONNECTED |
| TO THE IN-LINE EXHAUST FAN IS IN AN ENCLOSURE, THE |
| SPACE OR ROOM IN WHICH THE EXHAUST FAN IS LOCATED SHALL |
| HAVE THE SAME FIRE RESISTANCE RATING AS THE ENCLOSURE |
| (NFPA 96 SECTION 8.1.3.6) |
| |
| SHEET A-1.3.02: PLANS INDICATE GLAZING WITH A FIRE |
| RATING IN SECOND FLOOR CORRIDOR LOOKING DOWN INTO THE |
| FIRST FLOOR LOBBY; HOWEVER, NO WALL OR GLAZING DETAILS |
| FOR THIS ASSEMBLY WAS LOCATED. |
| |
| SHEET A-5.1.01: INDIVIDUAL DOORS IN SCHEDULE DO NOT |
| INDICATE THE USE OF PANIC OR FIRE EXIT HARDWARE. |
| |
| SHEET A-5.1.04: SHEET IS BLANK. |
| |
| SHEET FP-0.0.00: COULD NOT LOCATE ANY OF THE FOLLOWING |
| INFORMATION: YEAR OF STANDARD DESIGNED (NFPA 13, 14, 20 |
| ETC.0, HYDRANT FLOW TEST DATA, HAZARD AND DENSITY |
| CLASSIFICATION OF EACH AREA, FIRE DEPARTMENT |
| CONNECTION. |
| |
| SHEET FP-0.0.00: PLANS INDICATE, "100 PSI @ 500 GPM |
| REQUIRED FOR CITY OF MIAMI." |
| |
| SHEET FP-1.3.01B: PER NFPA 24 SECTION 6.2.1, ALL |
| CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE |
| PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH |
| ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| FEET FROM THE BUILDING. |
| (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| INDICATOR VALVE. |
| (2) A WALL POST INDICATOR VALVE |
| (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| ACCORDANCE WITH SECTION 6.4 |
| (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| THE WALL FACING THE BACKFLOW PREVENTER. |
| (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| ACCESSIBLE FROM THE EXTERIOR |
| (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| AUTHORITY HAVING JURISDICTION |
| |
| SHEET FP-1.3.01B: CONFIRM FIRE PUMP ROOM IS LARGE |
| ENOUGH TO ACCOMMODATE THE FIRE PUMP, JOCKEY PUMP, |
| CONTROL PANELS WITH TRANSFER SWITCH, DOMESTIC WATER |
| BOOSTER PUMP AND ALL REQUIRED WORKING CLEARANCES. |
| |
| PLUMBING/FIRE PROTECTION: NEITHER THE FIRE PROTECTION |
| DRAWINGS NOR THE PLUMBING DRAWINGS SHOW THE |
| SPRINKLER/STANDPIPE SYSTEM DRAINS OR TIE INTO THE |
| SANITARY OR SEWER SYSTEMS. |
| |
| SHEET M-1.3.04B: GREASE DUCT EXHAUST LOUVER IS LOCATED |
| CLOSER THAN 10 FEET TO THE ADJACENT PERPENDICULAR |
| CORRIDOR WALL. |
| |
| SHEET M-1.3.04B: HOUSEKEEPING #4001 NEEDS A TWO-HOUR |
| FIRE RESISTANCE RATING AND 90 MINUTE FIRE RATED DOOR. |
| WHERE THE DUCT SYSTEM CONNECTED TO THE IN-LINE EXHAUST |
| FAN IS IN AN ENCLOSURE, THE SPACE OR ROOM IN WHICH THE |
| EXHAUST FAN IS LOCATED SHALL HAVE THE SAME FIRE |
| RESISTANCE RATING AS THE ENCLOSURE (NFPA 96 SECTION |
| 8.1.3.6) |
| |
| ELECTRICAL: INSUFFICIENT EXIT SIGNAGE THROUGHOUT |
| BUILDING, ESPECIALLY THE FIRST FLOOR. NO EMERGENCY |
| LIGHTING INDICATED INSIDE OR OUTSIDE THE BUILDING |
| EXCEPT INSIDE THE EXIT STAIRS. |
| |
| SHEET E-1.4.01A: NO FIRE ALARM NOTIFICATION PROVIDED IN |
| THE FOLLOWING LOCATIONS: BUILDING EXTERIOR, MEETING |
| #1113, RESTROOM #1111, PANTRY FREEZER #1118, RESTROOM |
| #1108 (ONE TOILET). |
| |
| SHEET E-1.4.01B: NO FIRE ALARM NOTIFICATION PROVIDED IN |
| THE FOLLOWING LOCATIONS: KITCHEN #1129 (LARGER FREEZERS |
| AND DRY STORAGE), SAUNA #1206, SAUNA #1224 |
| |
| SHEET E-1.4.02: NO FIRE ALARM NOTIFICATION PROVIDED FOR |
| THE LARGE OUTSIDE KING BALCONIES (TYPICAL UPPER |
| FLOORS). |
| |
| DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT |
| RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| VIOLATIONS OF THIS CODE. |
| |
| WESLEY JOLIN |
| ASSISTANT FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| |