2017-03-23 11:31:253200 NORTH CONGRESS AVENUE - HOTEL
 PERMIT #17020796
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 NO INFORMATION SUBMITTED FOR POOL, POOL DECK, WEDDING
 STAGE, CONCERT LAWN, EVENT TENT, PHASE II OR PARKING
 GARAGE. THESE AREAS HAVE NOT BEEN REVIEWED OR APPROVED
 AT THIS TIME.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
 TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS
 WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.
  
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND
 SIDES AND 4'-0" TO THE BACKSIDE OF THE STEAMER CAP.
  
 PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE
 MARKED WITH FREESTANDING SIGNS READING, "FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL
 BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 SHEET A-0.0.02: APPLICABLE CODES SECTION INDICATES,
 "BROWARD COUNTY AMENDMENTS TO THE FLORIDA FIRE
 PREVENTION CODE."
  
 SHEET A-1.2.01: EGRESS PLAN DOES NOT SHOW ENOUGH DETAIL
 REGARDING ALL EXITS DISCHARGING TO A PUBLIC WAY.
 SEVERAL EXIT DISCHARGE APPEAR TO TERMINATE DIRECTLY
 OUTSIDE OF THE BUILDING AND DO NOT PROVIDE A MEANS OF
 EGRESS TO ACHIEVE A SAFE DISTANCE AWAY FROM THE
 BUILDING SUCH AS PRE-FUNCTION #1318, BALLROOM #2, AND
 SALE/ADMIN TO NAME A FEW.
  
 SHEET A-1.2.01: NEARLY HALF THE EXITS DISCHARGE ONTO
 THE POOL DECK IN LIEU OF A PUBLIC WAY. A LIFE SAFETY
 PLAN IS NEEDED FOR THE FIRST FLOOR AND POOL DECK IF THE
 DECK IS TO BE USED HOTEL OCCUPANT EGRESS. HOW WILL
 UNOBSTRUCTED EGRESS BE PROVIDED AND MAINTAINED ON THE
 POOL DECK LEADING TO A PUBLIC WAY? HOW DO THE
 ADDITIONAL LARGE ASSEMBLY SPACES (TIKI BAR, WEDDING
 STAGE, CONCERT LAWN, EVENT TENT AND PHASE II) AFFECT
 TOTAL EGRESS PLAN?
  
 SHEET A-1.2.01: NO FIRE PROTECTION RATING SHOWN AROUND
 FIRE PUMP ROOM.
  
 SHEET A-1.2.02: NO FIRE PROTECTION RATING SHOWN AROUND
 STAIR #3 (TYPICAL UPPER FLOORS) AND ELEVATOR SHAFT AT
 COLUMN INTERSECTION B/24.
  
 SHEET A-1.2.04 & SHEET M-1.3.04B: HOUSEKEEPING #4001
 NEEDS A TWO-HOUR FIRE RESISTANCE RATING AND 90 MINUTE
 FIRE RATED DOOR. WHERE THE GREASE DUCT SYSTEM CONNECTED
 TO THE IN-LINE EXHAUST FAN IS IN AN ENCLOSURE, THE
 SPACE OR ROOM IN WHICH THE EXHAUST FAN IS LOCATED SHALL
 HAVE THE SAME FIRE RESISTANCE RATING AS THE ENCLOSURE
 (NFPA 96 SECTION 8.1.3.6)
  
 SHEET A-1.3.02: PLANS INDICATE GLAZING WITH A FIRE
 RATING IN SECOND FLOOR CORRIDOR LOOKING DOWN INTO THE
 FIRST FLOOR LOBBY; HOWEVER, NO WALL OR GLAZING DETAILS
 FOR THIS ASSEMBLY WAS LOCATED.
  
 SHEET A-5.1.01: INDIVIDUAL DOORS IN SCHEDULE DO NOT
 INDICATE THE USE OF PANIC OR FIRE EXIT HARDWARE.
  
 SHEET A-5.1.04: SHEET IS BLANK.
  
 SHEET FP-0.0.00: COULD NOT LOCATE ANY OF THE FOLLOWING
 INFORMATION: YEAR OF STANDARD DESIGNED (NFPA 13, 14, 20
 ETC.0, HYDRANT FLOW TEST DATA, HAZARD AND DENSITY
 CLASSIFICATION OF EACH AREA, FIRE DEPARTMENT
 CONNECTION.
  
 SHEET FP-0.0.00: PLANS INDICATE, "100 PSI @ 500 GPM
 REQUIRED FOR CITY OF MIAMI."
  
 SHEET FP-1.3.01B: PER NFPA 24 SECTION 6.2.1, ALL
 CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET FP-1.3.01B: CONFIRM FIRE PUMP ROOM IS LARGE
 ENOUGH TO ACCOMMODATE THE FIRE PUMP, JOCKEY PUMP,
 CONTROL PANELS WITH TRANSFER SWITCH, DOMESTIC WATER
 BOOSTER PUMP AND ALL REQUIRED WORKING CLEARANCES.
  
 PLUMBING/FIRE PROTECTION: NEITHER THE FIRE PROTECTION
 DRAWINGS NOR THE PLUMBING DRAWINGS SHOW THE
 SPRINKLER/STANDPIPE SYSTEM DRAINS OR TIE INTO THE
 SANITARY OR SEWER SYSTEMS.
  
 SHEET M-1.3.04B: GREASE DUCT EXHAUST LOUVER IS LOCATED
 CLOSER THAN 10 FEET TO THE ADJACENT PERPENDICULAR
 CORRIDOR WALL.
  
 SHEET M-1.3.04B: HOUSEKEEPING #4001 NEEDS A TWO-HOUR
 FIRE RESISTANCE RATING AND 90 MINUTE FIRE RATED DOOR.
 WHERE THE DUCT SYSTEM CONNECTED TO THE IN-LINE EXHAUST
 FAN IS IN AN ENCLOSURE, THE SPACE OR ROOM IN WHICH THE
 EXHAUST FAN IS LOCATED SHALL HAVE THE SAME FIRE
 RESISTANCE RATING AS THE ENCLOSURE (NFPA 96 SECTION
 8.1.3.6)
  
 ELECTRICAL: INSUFFICIENT EXIT SIGNAGE THROUGHOUT
 BUILDING, ESPECIALLY THE FIRST FLOOR. NO EMERGENCY
 LIGHTING INDICATED INSIDE OR OUTSIDE THE BUILDING
 EXCEPT INSIDE THE EXIT STAIRS.
  
 SHEET E-1.4.01A: NO FIRE ALARM NOTIFICATION PROVIDED IN
 THE FOLLOWING LOCATIONS: BUILDING EXTERIOR, MEETING
 #1113, RESTROOM #1111, PANTRY FREEZER #1118, RESTROOM
 #1108 (ONE TOILET).
  
 SHEET E-1.4.01B: NO FIRE ALARM NOTIFICATION PROVIDED IN
 THE FOLLOWING LOCATIONS: KITCHEN #1129 (LARGER FREEZERS
 AND DRY STORAGE), SAUNA #1206, SAUNA #1224
  
 SHEET E-1.4.02: NO FIRE ALARM NOTIFICATION PROVIDED FOR
 THE LARGE OUTSIDE KING BALCONIES (TYPICAL UPPER
 FLOORS).
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE