2017-04-24 17:36:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 W. P. B. PERMIT: 17020796 (BANYAN CAY HOTEL)
 ADD: 3200 N. CONGRESS AVE. (ADDRESS TO BE ASSIGNED)
 CONT: HEDRICK BROTHERS
 TEL: 561-689-8880
 E-MAIL: [email protected]
  
 1. REVISE SITE PLAN TO SHOW DISTANCE TO PROPERTY LINE
 OR ASSUMED PROPERTY LINE BETWEEN BUIDINGS LOCATED ON
 THE SAME LOT, DISTANCE OF PROPOSED HOTEL TO PROPERTY
 LINE AND/OR ASSUMED PROPERTY LINE, DISTANCE OF ADJACENT
 STRUCTURES TO ASSUMED PROPERTY LINE (IF APPLICABLE),
 FBC B TABLE 602, 705.3.
  
 2. A1.2.01 EXIT DISCHARGE NOT CLEAR; REVISE PLAN TO
 SHOW COMPLIANCE WITH FBC B 1027.
  
 3. ACCESSIBLE MEANS OF EGRESS SELECTED NOT CLEAR; SEE
 FBC 1007, FBC A 207.1. REVISE PLAN TO STATE WHICH
 METHOD IS SELECTED AND CONFIRM COMPLIANCE WITH METHOD
 SELECTED; REVISE PLAN IF NECESSARY TO SHOW COMPLIANCE.
  
 4. A1.2.01 1ST FLOOR SQUARE FOOT AREA IS 31,750,
 PROJECT DATA SHOWS 41,956. OTHER FLOORS ALSO
 INCONSISTENT. REVISE TO CLARIFY DISCREPANCY, FBC 107.
  
 5. SOME AREAS WERE NOT INCLUDED ON THE OCCUPANT LOAD
 CHART; FOR INSTANCE, HOUSEKEEPING. ALTHOUGH OCCUPANT
 LOADS FOR THESE AREA WILL BE LOW, THEY SHOULD BE
 INCLUDED FOR AN ACCURATE TOTAL. THIS INFORMATION IS
 REQUIRED FOR CO.
  
 6. A1.2.01, CLARIFY FIRE RATED WALL AT RETAIL/COFFEE.
 THIS, AND SOME OTHER FIRE RATED WALLS ARE NOT CLEAR AS
 TO PURPOSE OR CONTINUITY, FBC 107. IF YOU WISH, PLEASE
 CONTACT ME TO DISCUSS PRIOR TO RESUBMITTAL. FOR
 INSTANCE, 2 HOUR BETWEEN MENS ROOM 1149 AND SALE &
 ADMIN 1142, 1 HR BETWEEN BOARD RM #1 AND MEETING ROOM
 #2.
  
 ALL FIRE RATED WALLS, PARTITIONS, BARRIERS SHOWN ON THE
 PLAN WILL BE ENFORCED AS SUCH AT TIME OF INSPECTION.
  
 7. A1.4.01B, FITNESS ROOM TO COMPLY WITH FBC A 1004,
 REVISE TO SHOW COMPLIANCE.
  
 IF DETAILS SUCH AS SPECIFIC TYPES OF MACHINES PROPOSED
 IS NOT AVAILABLE AT THIS TIME, REVISE THE PLAN TO SHOW
 GENERAL COMPLIANCE. INCLUDE NOTES REGARDING COMPLIANCE.
 THIS PERMIT WILL BE ISSUED WITH PROVISO, ISSUED AT
 CONTRACTOR'S RISK, PROVIDE A DETAILED PLAN AT
 INSPECTION. SUBJECT TO FIELD INSPECTOR'S DISCRETION,
 FITNESS CENTER PLAN MAY BE REQUIRED TO BE SUBMITTED FOR
 PLAN REVIEW.
  
 8. A1.4.02A WALL BETWEEN CORRIDOR AND AREA "OPEN TO
 BELOW" LACKS A WALL TAG, FBC 107.
  
 9. S2.04B, A4.2.01, OTHER PAGES, PLAN SPECS LUMBER IN
 SEVERAL LOCATIONS (T&G SHEATHING, PLYWOOD, PRESSURE
 TREATED PLYWOOD, WOOD TRUSS). FBC 603.1, REVISE PLAN TO
 SPEC FRT OR REVISE PLAN INCLUDE EXCEPTION.
  
 10. S2.04BT SPECS LIGHT GAUGE METAL TRUSSES, S2.04
 NOTES SPECS WOOD TRUSSES FOR MANSARD. REVISE PLAN TO
 CLARIFY; CHECK ALL FOR CONSISTENCY, FBC 107. SEE ALSO
 A4.2.01.
  
 11. THRESHOLD BLDG., REQUIRED STATEMENT:
 FS553.79(7)(D), W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
 COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY
 THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND
 CHAPTER 633.
  
 SEE ALSO THRESHOLD REVIEW FOR ADDITIONAL REQUIREMENTS
 (SI AGREEMENT, RESUMES, ETC.).
  
 12. SOIL BEARING VALUES. THE TEST BY UNIVERSAL
 ENGINEERING SCIENCES REFERENCES THE TEST IS PRELIMINARY
 GEOTECHNICAL ENGINEERING REPORT BANYAN CAY- HOTEL
 PLEASE NOTE THE BORING SAMPLES TAKEN CH-1 AND CH-2 ARE
 SHOWN FOR THE CLUBHOUSE, THIS SOILS REPORT HAS NO
 BORINGS SHOWN IN THE REPORT FOR THE HOTEL. NOTE FOR THE
 TENNIS CLUB CENTER UP TO 6 FEET OF MUCK WAS ENCOUNTERED
 WITHIN THE BUILDING FOOTPRINT. PLEASE COMPLY WITH: 2014
 FBC-B 1803.3 BASIS OF INVESTIGATION.
 SOIL CLASSIFICATION SHALL BE BASED ON OBSERVATION AND
 ANY NECESSARY TESTS OF THE MATERIALS DISCLOSED BY
 BORINGS, TEST PITS OR OTHER SUBSURFACE EXPLORATION MADE
 IN APPROPRIATE LOCATIONS. ADDITIONAL STUDIES SHALL BE
 MADE AS NECESSARY TO EVALUATE SLOPE STABILITY, SOIL
 STRENGTH, POSITION AND ADEQUACY OF LOAD-BEARING SOILS,
 THE EFFECT OF MOISTURE VARIATION ON SOIL-BEARING
 CAPACITY, COMPRESSIBILITY, LIQUEFACTION AND
 EXPANSIVENESS.
  
 13. SHEET 019-S-4.10, PRESSURES MAY BE LOW; PROVIDE
 CALCULATIONS FBC B 1609. REVISE PLAN TO INCLUDE PITCH
 AND MEAN ROOF HEIGHT. WILL DESIGN PRESSURES SPECIFIED
 APPLY TO ALL ROOF AREAS, REGARDLESS OF PITCH? ROOF PLAN
 APPEARS TO INCLUDE ROOF AREAS OVER THE 4TH LEVEL, BUT
 OTHER ROOF AREAS ARE NOT INCLUDED - FOR EXAMPLE, THE
 PORTE COCHERE. REVISE PLAN TO INCLUDE ALL ROOF AREAS.
  
 14. SOME SECTION DETAIL MARKERS APPEAR TO BE LABELED
 INCORRECTLY AND DETAILS DO NOT CORRELATE WITH FLOOR
 PLANS; FOR INSTANCE, SEE SHEET S2.00A. DETAIL MARKERS
 REFERENCE PAGES S3.40, S3.41, UNABLE TO LOCATE; S4.08
 AND OTHER PAGES ALSO HAVE THIS ERROR. SEE SHEETS S3.42
 AND OTHER PAGES, UNABLE TO LOCATE THE SHEARWALL
 LOCATIONS ON THE PLAN, REVISE OR DIRECT.
  
 15. A1.8.01 AND OTHER PAGES PROVIDE A LEGEND FOR THE
 FLOOR PLAN NOTE (THE BOX IN THE MIDDLE OF EACH FLOOR
 PLAN). IT IS NOT CLEAR WHAT "P-1" MENAS. SOME AREAS
 HAVE A "?"; CLARIFY.
  
 16. SEE FBC A 209.2.1, 209.4, LABEL ALL PASSENGER
 LOADING ZONES ON THE PLAN, REVISE PLAN TO SHOW
 COMPLIANCE WITH REQUIREMENTS.
  
 17. FBC A 806, REVISE PLAN TO SHOW COMPLIANCE. SOME ADA
 ROOMS HAVE ACCESSIBILITY CLEAR FLOOR SPACE (4-1.5.02),
 OTHERS DO NOT (3-1.5.02).
  
 18. FBC 107, NO DETAILS FOR TUB, SHOWER, LAV, TOILETS,
 URINALS PROVIDED. SEE PLUMBING REVIEW; ALL ARE
 APPLICABLE FOR BUILDING REVIEW.
  
 19. FBC A 806, PROVIDE A DETAIL TO SHOW COMPLIANCE,
 ACCESSIBLE ROUTE TO GUEST ROOM BALCONY. THIS SHOULD
 CORRELATE WITH THE SLIDING GLASS DOOR PRODUCT APPROVAL.
 THE DETAIL ON A5.2.01 DOES NOT INCLUDE DIMENSIONS TO
 SHOW COMPLIANCE WITH FBC A 303. ALSO PROVIDE THE
 SLIDING GLASS DOOR PRODUCT APPROVAL.
  
 20. 4-A1.5.05, REVISE PLAN TO CLARIFY WHAT "ELEV #5"
 AND "ELEV #3" ARE.
  
 21. A1.2.02, THE RATED WALL REQUIRED BY FBC B 708.1 IS
 NOT CONTINUOUS FOR SOME ROOMS (ROOMS NOT NUMBERED, SEE
 LINES C8 THROUGH C10).
  
 22. COMPLIANCE WITH FBC 1509.6.4 (ROOFTOP EQUIPMENT)
 NOT CLEAR, REVISE PLAN TO CLARIFY.
  
 23. ADVISE AS TO WHERE THE DOOR MARKERS FOR THE UNITS
 CAN BE FOUND, FBC 107. LOCATION OF "BARN" DOORS IN THE
 UNITS IS NOT CLEAR.
  
 24. REVISE PLAN TO INCLUDE ASSEMBLIES FOR THE FIRE
 RATED ELEMENTS REQUIRED BY FBC B TABLE 601.
  
 25. SHEET A5.1.04 IS BLANK, FBC 107 PROVIDE INFORMATION
 INCLUDING PANIC HARDWARE FBC B 1008.1.10.
  
 26. BUILT IN BENCHES TO COMPLY WITH FBC A 903.
  
 27. DRESSING, FITTING AND LOCKER ROOMS TO COMPLY WITH
 FBC A 222, REVISE PLAN TO SHOW COMPLIANCE.
  
 28. SPA RECEPTION/ RETAIL DESK, ANY OTHER CHECK OUT
 AREAS, SEE FBC A 904 NOTE ON PLAN AND PROVIDE A DETAIL.
  
 29. CIVIL SHEETS USE NGVD29 VERTICAL DATUM. A0.0.02
 PROPOSES A FINISHED FLOOR OF 22'0' NAVD88. THERE IS A
 CONFLICT OF APPROXIMATELY 18"; REVISE TO BE CONSISTENT.
 NGVD29 IS RECOMMENDED AT THIS TIME.
  
 30. ARCHITECT'S TITLE BLOCK LACKS THE ARCHITECT
 BUSINESS NUMBER, REVISE TO INCLUDE, FS481, FAC 61G16.
  
 31. CIVIL, STRUCTURAL, AND ARCHITECTURAL (AND OTHER)
 SHEETS ARE NOT DIGITALLY SIGNED. A SHEETS APPEAR TO BE
 DIGITALLY SIGNED BUT LACK THE CERTIFICATE. PRIOR TO
 RESUBMITTAL, PLEASE DIGITALLY SIGN EACH SHEET. IF
 UNSURE AS TO ACCEPTABLE (PER FS471/FS481) FORMAT,
 PLEASE SEND TEST PAGES TO ME VIA EMAIL FOR PRELIMINARY
 REVIEW. FAILURE TO PROVIDE INDIVIDUALLY SIGNED PAGES
 WILL RESULT IN A SEPARATE SIGNATURE REVIEW AFTER ALL
 REVIEWS HAVE PASSED. THIS REVIEW MAY TAKE UP TO A WEEK
 TO COMPLETE. INDIVIDUALLY SIGNED PAGES IS STRONGLY
 ENCOURAGED IN ORDER TO TIMELY PROCESS THIS PERMIT.
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS
 OPTIONS.
  
 32. IT IS NOT CLEAR WHICH OF THE ENGINEERING COMPANIES
 IN THE COMPANY BLOCK IS TO SERVE AS THE TITLE BLOCK FOR
 THE VARIOUS ENGINEERS (FMEP). ALSO, THE CERTIFICATE OF
 AUTHORIZATION IS LACKING, FS471, FAC61G15-23.
  
 33. OK
  
 34. SEE SIGNATURE REVIEW.
  
 35. SEE IMPACT FEE REVIEW.
  
 36. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE
 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515,
 [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN
 THIS IS COMPLETE.
  
 B. SEPARATE PERMITS REQUIRED. SUB PERMITS FOR
 MECHANICAL, ELECTRICAL, PLUMBING ARE REQUIRED. SEPARATE
 PERMITS (APPLICATION, FEES, PLANS, REVIEWS) REQUIRED
 FOR ALL OTHER ITEMS SUCH AS PARKING, SIGNAGE, ETC.
  