2017-05-08 12:28:541) SHT. FP-1 STATES THAT THE SYSTEM WILL NOT BE
 PRESSURIZED PER NFPA 13D SEC. 4.2.CLARIFY. 2ND REQUEST.
 2) SHT. FP-1- NOTE #14 STATES THE FLOW TEST WAS
 PERFORMED BY THE CITY OF PEMBROKE PINES. CLARIFY. 2ND
 REQUEST
 3) SHT. FP-1 - THE LOCATION NOTED IN THE LOWER LEFT
 HAND CORNER UNDER "FLOW TEST INFO" LISTS THE NAME OF
 THIS PROJECT AS PELICAN GRAND BEACH RESORT. CLARIFY.
 THE NAME OF THIS PROJECT IS PARK SLOPE. ONE SET STILL
 READS "PELICAN GRAND BEACH RESORT." 2ND REQUEST
 4) UNIT "A" CALCULATIONS DO NOT HAVE THE LOCATION OF
 THE JOB ON THEM AND THE UNIT "B" CALCULATIONS HAVE THE
 LOCATION NOTED AS LANTANA. CLARIFY. 2ND REQUEST.
 5) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR
 ALL TYPES OF SPRINKLER HEADS.WPB AMEND. TO FBC SEC.
 107.2.1. 2ND REQUEST.
 6) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE AMES
 200B BACKFLOW PREVENTER. 2ND REQUEST.
 7) CLEARLY SHOW COMPLIANCE WITH NFPA 13D SEC.7.1.1 OR
 7.1.2 FOR THE REQUIRED CONTROL VALVE. 2ND REQUEST.
 8) SUBMIT DOCUMENTATION THAT THE SPRINKLER HEAD
 DISCHARGE COMPLIES WITH NFPA 13D SEC.8.1.1.1.1,
 8.1.1.1.2 OR 8.1.1.2. 2ND REQUEST.
 9) SUBMIT AN ENLARGED PLAN SHOWING THE DESIGN AREA FOR
 UNIT B. 2ND REQUEST.
 10) THE BACKFLOW PREVENTERS SHALL BE LEAD FREE PER FPC
 605.2 7 CITY OF WPB CROSS-CONNECTION CONTROL MANUAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  