2017-04-15 08:38:301) SHT. FP-1 STATES THAT THE SYSTEM WILL NOT BE
 PRESSURIZED PER NFPA 13D SEC. 4.2.CLARIFY.
 2) SHT. FP-1- NOTE #14 STATES THE FLOW TEST WAS
 PERFORMED BY THE CITY OF PEMBROKE PINES. CLARIFY.
 3) SHT. FP-1 - THE LOCATION NOTED IN THE LOWER LEFT
 HAND CORNER UNDER "FLOW TEST INFO" LISTS THE NAME OF
 THIS PROJECT AS PELICAN GRAND BEACH RESORT. CLARIFY.
 THE NAME OF THIS PROJECT IS PARK SLOPE.
 4) UNIT "A" CALCULATIONS DO NOT HAVE THE LOCATION OF
 THE JOB ON THEM AND THE UNIT "B" CALCULATIONS HAVE THE
 LOCATION NOTED AS LANTANA. CLARIFY.
 5) THE LOCATION OF THE PROJECT ON THE PLANS IS LISTED
 AS LANTANA. CORRECT THE LOCATION ON THE PLANS TO WEST
 PALM BEACH. ALSO, ENSURE THE LOCATION & ADDRESS ON THE
 PERMIT APPLICATION MATCHES THE ADDRESS ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR
 ALL TYPES OF SPRINKLER HEADS.WWPB AMEND. TO FBC SEC.
 107.2.1.
 7) SHT. FP-4 - CLARIFY THE CONNECTION OF THE FIRE
 SPRINKLER SYSTEM TO THE DOMESTIC WATER SYSTEM. THE
 ISOMETRIC IS VAGUE AND CONFUSING.WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE AMES
 200B BACKFLOW PREVENTER.
 9) CLEARLY SHOW COMPLIANCE WITH NFPA 13D SEC.7.1.1 OR
 7.1.2 FOR THE REQUIRED CONTROL VALVE.
 10) SUBMIT DOCUMENTATION THAT THE SPRINKLER HEAD
 DISCHARGE COMPLIES WITH NFPA 13D SEC.8.1.1.1.1,
 8.1.1.1.2 OR 8.1.1.2.
 11) SUBMIT AN ENLARGED PLAN SHOWING THE DESIGN AREA FOR
 UNIT B.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  