Plan Review Notes
Plan Review Notes For Permit 17020758
Permit Number 17020758
Review Stop P
Sequence Number 1
Notes
Date Text
2017-03-03 14:16:011ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A2.0.1 DETAIL #2 GRAB BAR IS NOTED AS 30" IT
 SHALL BE 36" MIN. PER FBC ACC 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 2. GRAB BARS SHALL BE MEASURED FROM THE FINISHED FLOOR
 TO THE TOP OF THE GRIPPING SURFACE. FBC ACC 609.4
  
 3. SHT. P2.1, E3.1, ALS1.1 SHOWS A PARTITION IN-THE
 BATHEOOM 407 NEXT TO WC SHT. A1.1.1, A1.1.3 DOES NOT
 SHOW THE PARTITION PLEASE CLARIFY. WPB AMEND TO FBC
 107.2.1
  
 4. ON THE ARCHITECTURAL PAGES THE LAYOUT FOR THE SINK
 IN THE CONFERENCE RM 440 DIFFERS FROM THR MEP PAGES
 PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  