2017-02-22 07:17:25 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 17020758 |
| ADD: 501 S. FLAGLER DR. SUITE # 400 |
| CONT: ANDERSON-MOORE |
| TEL: 561-308-1590 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 22/ 2017 |
| ACTION: DENIED |
| |
| 1) SHEET A1.1.1: |
| 1A) DOOR MARKED ETR FROM THE LOBBY TO CORRIDOR 452 IS |
| MISSING THE 18 INCHES ON THE LATCHSIDE OF THE DOOR. |
| DOES NOT COMPLY WITH 2014 FBC-ACCESS. CODE SECTION |
| 404.2.4 MANEUVERING CLEARANCES AT DOORS. MINIMUM |
| MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY |
| WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE |
| FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE |
| OR HINGE SIDE CLEARANCE. FIGURE 404.2.4.1(A). |
| |
| 1B) ENTRY DOOR FROM THE ELEVATOR LOBBY TO CORRIDOR 448 |
| IS MISSING THE 18 INCHES ON THE LATCHSIDE OF THE DOOR. |
| DOES NOT COMPLY WITH 2014 FBC-ACCESS. CODE SECTION |
| 404.2.4 MANEUVERING CLEARANCES AT DOORS. MINIMUM |
| MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY |
| WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE |
| FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE |
| OR HINGE SIDE CLEARANCE. FIGURE 404.2.4.1(A). WHILE THE |
| DOOR IS CONTRAVERSIAL AS TO LANDLORD OR TENANT |
| RESPONSIBILITY THE VIOLATION IS ON THE TENANT SIDE AND |
| CAN BE MADE CODE COMPLIANT WITH AN ELECTRIC PUSH BUTTON |
| AND DOOR ACTUATOR. |
| FBC-ACCESS. CODE 404.3 AUTOMATIC AND POWER-ASSISTED |
| DOORS AND GATES. |
| |
| 1C) DOOR 436 MAY OR MAY NOT MEET THE 18 INCHES ON THE |
| LATCHSIDE OF THE DOOR THE PLAN IS IN 1/8 INCH SCALE AND |
| THIS AREA IS NOT DIMENSIONED. DOES NOT COMPLY WITH 2014 |
| FBC-ACCESS. CODE SECTION 404.2.4 MANEUVERING CLEARANCES |
| AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND |
| GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES |
| SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE |
| REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE. FIGURE |
| 404.2.4.1(A). |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| 2) THE PERMIT APPLICATION INDICATES THE DECLARED VALUE |
| OF THE PERMIT TO BE $500,000.00 IN VALUE. THE |
| FBC-ACCESS. CODE ALLOW UP TO 20% OF THE VALUE OF THE |
| PERMIT BEFORE DISPROPORTIONATE COST ARE MET. 202.4.2 |
| ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONALITY. |
| PLEASE ITEMIZE WHERE THESE FUNDS ARE SPENT AND THE |
| ORDER IN WHICH THEY ARE SPENT TO ACHIEVE CODE |
| COMPLIANCE OR DISPROPORTIONALITY. 2014 FBC-ACCESS. CODE |
| 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| DISPROPORTIONALITY. |
| |
| 3) SHEET A2.0.1 DETAIL # 4 SHOWS A HIGH/ LOW DRINKING |
| FONTAIN BUT THE DETAIL DOES NOT INDICATE AT WHAT LEVEL |
| THE SPOUT HEIGHT COMPLING WITH ACCESS. CODE 602.4 & |
| 602.7. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. |
| WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |