2017-04-19 14:00:412ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020696
 4/19/17
  
 1) THE REVISED PLANS ARE STILL INDICATING THE EXISTING
 14" BOILER FLUE VENT IS STILL UNDERSIZED. PLEASE REFER
 TO TABLE 504.2 (1) FBC-14 FUEL GAS WHICH INDICATES A
 14" FLUE AT 15' HEIGHT AND 5' LATERAL CAN ADEQUATELY
 VENT UP TO 1,327 MBH BASED ON APPLIANCE INPUT RATING.
 THIS NUMBER WILL DECREASE USING A 12' FLUE LENGTH AND
 ALSO USING A 12" CONNECTOR AS INDICATED ON THE PLANS-
 SEE SECTION 504.2.8 :
  
 504.2.8 VENT AREA AND DIAMETER.
 WHERE THE VERTICAL VENT HAS A LARGER DIAMETER THAN THE
 VENT CONNECTOR, THE VERTICAL VENT DIAMETER SHALL BE
 USED TO DETERMINE THE MINIMUM VENT CAPACITY, AND THE
 CONNECTOR DIAMETER SHALL BE USED TO DETERMINE THE
 MAXIMUM VENT CAPACITY. THE FLOW AREA OF THE VERTICAL
 VENT SHALL NOT EXCEED SEVEN TIMES THE FLOW AREA OF THE
 LISTED APPLIANCE CATEGORIZED VENT AREA, FLUE COLLAR
 AREA OR DRAFT HOOD OUTLET AREA UNLESS DESIGNED IN
 ACCORDANCE WITH APPROVED ENGINEERING METHODS.
  
 2) COMMENTS #5 & 6 FROM THE PREVIOUS REVIEW STILL
 EXIST. PLEASE REVISE SHEET M-5 TO SHOW THE DETAILS AND
 DIMENSIONS THAT ARE INDICATED IN THE NARRATIVE REPONSE.
 PLEASE NOTE THAT THE 8-1/2 X 11" SUBMITTAL DOES NOT
 PROVIDE: A) ATTACHMENT DETAILS FOR THE COOLING TOWER TO
 THE STRUCTURE. B) THE CLEARANCE DISTANCE HEIGHT FROM
 THE ROOF SURFACE. C) DOES NOT BEAR THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL WHO DREW THE PLAN.
  