Plan Review Notes
Plan Review Notes For Permit 17020696
Permit Number 17020696
Review Stop B
Sequence Number 3
Notes
Date Text
2017-04-25 07:49:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 FROM PREVIOUS LIST:
  
 4. FBC 1609, PROVIDE WIND DESIGN CRITERIA FBC 1603.1.4.
  
 5. OK
  
 6. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
 A RESPONSE LETTER STATING HOW EACH ITEM WAS ADDRESSED
 WILL HELP TO EXPEDITE YOUR PLAN REVIEW.
  
  
  