2017-03-21 13:59:052ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020696
 3/21/17
  
 1) SHEET M-1: SHOW THE LOCATION OF EF-11.
  
 2) M-1: INDICATE HOW THE CURB ADAPTERS WILL BE ATTACHED
 TO THE CURBS, AND INDICATE THE LENGTH OF THE #10
 FASTENERS USED TO MOUNT THE FANS.
  
 3) M-2A: INDICATE HOW COMBUSTION AIR IS BEING PROVIDED
 FOR THE BOILER AND PROVIDE A CALCULATION- SEE SECTION
 304 FBC-14 FUEL GAS.
  
 4) M-2A & M5: REFER TO TABLE 504.2.(1): THE 12" BOILER
 FLUE IS UNDERSIZED FOR THE TOTAL 1435 MBTU INPUT.
 PLEASE INDICATE THE TOTAL LENGTH OF THE FLUE FROM THE
 BOILER VENT OUTLET TO THE TERMINATION CAP. A 12"
 DOUBLE-WALL FLUE AT 20' RUN LENGTH WITH A 0" LATERAL
 CAN ADEQUATELY VENT GAS-FIRED EQUIPMENT UP TO1350 MBTU
 INPUT CAPACITY.
  
 5) M-5: AS PREVIOUSLY REQUESTED PROVIDE STRUCTURAL
 DETAILS FOR ANCHORING THE COOLING TOWER TO THE EXISTING
 SUPPORT BASE,
  
 6) M-5: REFER TO TABLE 1509.6.5 FBC-14 BUILDING AND
 INDICATE CLEARANCE HEIGHT BELOW THE COOLING TOWER
 SUPOPORT BASE TO THE FINISHED ROOF SURFACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719