Plan Review Notes For Permit 17020696 |
Permit Number |
17020696 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-02 06:59:44 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. SHT. M-2 IS THE HEATING BOILER NEW OR EXISTING. PER | | WPB AMEND TO FBC 107.2.1 | | | | 2. IF THE BOILER IS BEING REPLACEMENT IS IT SAME FOR | | SAME , IS THE BTU LOAD ON THE GAS THE SAME. PER WPB | | AMEND TO FBC 107.2.1 | | | | 3. PLEASE PROVIDE DETAIL FOR POTABLE WATER CONNECTION. | | PER WPB AMEND TO FBC 107.2.1 | | | | 4. THE EXISTING BACKFLOW FOR THE POTABLE WATER | | CONNECTION SHALL BE RECERTIFIED BY A LICENSE CERTIFIED | | BACKFLOW PREVENTION TESTER. PER CITY OF WPB CROSS | | CONNECTION CONTROL MANUAL. PROVIDE NOTE ON PLAN. PER | | WPB AMEND TO FBC 107.2.1 | | | | A NARRATIVE LISTING THE ORIGINAL REVIEW COMMENT NUMBER | | WITH A DESCRIPTION OF THE CHANGES MADE AND IDENTIFYING | | THE SHEET OR SPECIFICATION PAGE WHERE THE CHANGE CAN BE | | FOUND WILL HELP EXPEDITE THE REVIEW. | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. |
|