Plan Review Notes For Permit 17020696 |
Permit Number |
17020696 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-27 14:35:52 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: | | | | 1. SHT. M2A IS SHOWING A 1.5" MOTORIZED GAS VALVE THE | | THE GAS INLET FOR THE BOILER IS 2" PER MANUFACTURE THE | | VALVE S SHOULD BE THE SAME SIZE OR LARGER THAN THE | | INLET. PER WPB AMEND TO FBC 107.2.1 | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | 3. THE 12" VENT IS UNDERSIZED SHOULD BE 14" FOR 20' | | VENT. PER FBC FUEL GAS TABLE 504.2(1) | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|