 GAS COMMENTS:
  
 1. SHT. M2A IS SHOWING A 1.5" MOTORIZED GAS VALVE THE
 THE GAS INLET FOR THE BOILER IS 2" PER MANUFACTURE THE
 VALVE S SHOULD BE THE SAME SIZE OR LARGER THAN THE
 INLET. PER WPB AMEND TO FBC 107.2.1
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 3. THE 12" VENT IS UNDERSIZED SHOULD BE 14" FOR 20'
 VENT. PER FBC FUEL GAS TABLE 504.2(1)
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  