Plan Review Notes For Permit 17020696 |
Permit Number |
17020696 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-03-06 10:18:40 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4- | | COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3- | | VOLTAGE DROP NEW FEEDERS AND BRANCH CIRCUITS. | | 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD | | MARKINGS; MODIFICATIONS SEE VERBIAGE IN CODE. | | 3. PROVIDE ACTUAL REVISED CALCULATIONS FOR THE PANEL | | BOARDS SHOWN WITH CHANGES, DP, A, B. | | 4. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL | | COMMENTS RELATED TO ELECTRICAL. | | 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | THIS PROJECT. | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|