2017-03-06 10:18:40INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3-
 VOLTAGE DROP NEW FEEDERS AND BRANCH CIRCUITS.
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS; MODIFICATIONS SEE VERBIAGE IN CODE.
 3. PROVIDE ACTUAL REVISED CALCULATIONS FOR THE PANEL
 BOARDS SHOWN WITH CHANGES, DP, A, B.
 4. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL
 COMMENTS RELATED TO ELECTRICAL.
 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  