Date |
Text |
2017-05-23 12:53:43 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 5TH EDITION (2014) |
| |
| 1- ORIGINAL COMMENT: SPECIFY CARBON MONOXIDE ALARMS AS |
| REQUIRED BY SEC. R315 FBC-RESIDENTIAL. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- ORIGINAL COMMENT: VALUATION DECLARED IN THE PERMIT |
| APPLICATION IS TOO LOW BASED ON ALL THE SCOPE OF WORK. |
| VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| OVERHEAD AND PROFIT AND ALL DESIGN PROFESSIONAL FEES AS |
| REQUIRED BY SEC. 109.3 CITY AMENDMENTS. CONTRACTOR TO |
| REVISE THE VALUE. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| DECLARED VALUE IS EXTREMELY LOW FOR THE SCOPE OF WORK. |
| PROVIDE COPIES OF ALL SIGNED CONTRACTS, INCLUDING |
| DESIGN PROFESSIONAL FEES FOR BUILDING OFFICIAL REVIEW. |
| VALUES MAY BE ADJUSTED ACCORDINGLY. |
| |
| 3- ORIGINAL COMMENT: PROVIDE COMPLETE AND CORRECT |
| ENERGY CALCULATIONS. SEC. R103.1 FBC-ENERGY |
| CONSERVATION. REVISE THE FOLLOWING INFORMATION: "SINGLE |
| FAMILY" IS NOT A CONSTRUCTION TYPE. REVISE AS REQUIRED. |
| PROVIDE THE ACTUAL ORIENTATION OF THE BUILDING. CLIMATE |
| ZONE FOR PALM BEACH COUNTY IS 1 NOT 2. REVISE AS |
| REQUIRED. OWNER OR LEGALLY AGENT TO CERTIFY FORM |
| SUBMITTED. PROVIDE THE DESIGNER INFORMATION. ACCORDING |
| TO CITY RECORDS, THIS HOUSE DIDN'T HAVE A/C. PROVIDE |
| THE FLOOR, WALLS AND CEILING R-VALUES. PROVIDE CORRECT |
| FLOOR AREA. PROVIDE CEILING AREA. PROVIDE WALLS AREA. |
| WINDOWS ON WALL #3 AND #4 DON'T MATCH PLANS. REVISE AS |
| REQUIRED. PERSON WHO PREPARED THE CALCULATIONS TO |
| PROVIDE THE DOORS AND WINDOWS MANUFACTURER'S |
| SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR |
| USED ON THE CALCULATIONS. THIS HOUSE DOESN'T HAVE SLAB |
| ON GRADE. SEE PLANS AND REVISE AS REQUIRED. PROVIDE |
| COMPLETE INFORMATION FOR HEATING, COOLING, WATER |
| HEATER, ETC. |
| RESPONSE: THERE WAS NOT RESPONSE TO THIS ITEM BUT I |
| FOUND THAT THIS HOUSE IS CONSIDERED A CONTRIBUTING |
| HISTORIC BUILDING. THEREFORE, THE ENERGY CALCULATIONS |
| ARE NOT REQUIRED. IF CONTRACTOR WANTS TO SUBMIT ENERGY |
| CALCULATIONS, THEN THE ABOVE REVISIONS ARE REQUIRED. |
| |
| 4- ORIGINAL COMMENT: ENGINEER OF RECORD TO SPECIFY HOW |
| THE NEW "S" CLAY TILE IS GOING TO BE INSTALLED AS |
| REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF |
| SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF |
| SCREWS. IF SPECIFYING ADHESIVE, THEN PROVIDE PRODUCT |
| APPROVAL. |
| RESPONSE: SCOPE OF WORK WAS REVISED. EXTERIOR |
| ELEVATIONS NOS CALL FOR "EXISTING ROOFING NO WORK". |
| ACCORDING TO ROOFING PERMIT #15040718 THE ROOFING |
| MATERIAL OF THE FRONT PORCH IS SHINGLES NOT CONCRETE |
| TILE. THIS IS A CONTRIBUTING HISTORIC HOUSE. COORDINATE |
| WITH THE HISTORIC PLAN REVIEWER. NOTE: EXTERIOR |
| ELEVATIONS ELEVATIONS NEED TO SHOW THE CORRECT ROOFING |
| MATERIAL SHINGLES OR CONCRETE TILE SPECIALLY FOR A |
| CONTRIBUTING HISTORIC BUILDING. PUBLIC RECORDS NEED TO |
| SHOW CORRECT INFORMATION. |
| |
| 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) ORIGINAL COMMENT: NEW "S" CLAY TILE AS SPECIFIED ON |
| PLANS. |
| RESPONSE: NO PRODUCT APPROVAL WAS SUBMITTED AT THIS |
| TIME. THIS NEEDS TO BE COORDINATED WITH THE HISTORIC |
| REVIEWER AND ITEM #4 ABOVE. |
| |
| B) ORIGINAL COMMENT: CLAY TILE ADHESIVE (IF SPECIFIED |
| BY THE ENGINEER OF RECORD). SEE ROOF TILE PRODUCT |
| APPROVAL FOR LISTED ADHESIVES. |
| RESPONSE: COORDINATE WITH ITEM #5(A) ABOVE. |
| |
| C) ORIGINAL COMMENT: HURRICANE SHUTTERS. AND, PROVIDE |
| COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| D) ORIGINAL COMMENT: ALL SIMPSON STRUCTURAL CONNECTORS |
| SPECIFIED ON ALL DETAILS. PROVIDE ONLY THE FLORIDA |
| PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| SPECIFIED CONNECTOR OR ENGINEER OF RECORD TO LIST THE |
| FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| CONNECTOR. |
| RESPONSE: REPEAT COMMENT. ENGINEER TO SPECIFY THE |
| FLORIDA PRODUCT APPROVAL NEXT TO ALL SPECIFIED |
| CONNECTORS ON ALL DETAILS SUBMITTED NOT JUST ON THE |
| TYPICAL WALL SECTION. |
| |
| 6- ORIGINAL COMMENT: ENGINEER OF RECORD TO REVIEW AND |
| APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL |
| PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| |
| 7- ORIGINAL COMMENT: CLARIFY WHY SUBMITTING NOA |
| 14-0908.17 FOR FIXED WINDOWS. PLANS DON'T SHOW ANY |
| FIXED WINDOW. IN ADDITION THE WINDOWS DON'T MEET THE |
| CALCULATED DESIGN PRESSURES SHOWN ON SHEET S-2. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| RESPONSE: REPEAT COMMENT. NOW SUBMITTING NOA 14-0908.18 |
| FOR FIXED WINDOWS, BUT THERE ARE NO FIXED WINDOWS |
| SPECIFIED ON PLANS. |
| |
| 8- NEW WINDOW SCHEDULE SHOWN ON SHEET S-1: ENGINEER OF |
| RECORD SPECIFIES WINDOWS WITH IMPACT GLASS. PRODUCT |
| APPROVAL SUBMITTED IS FOR NON-IMPACT GLASS. REVISE AS |
| REQUIRED TO MATCH. IT'S NOT CLEAR WHAT TYPE OF WINDOWS |
| ARE GOING TO BE INSTALLED. COORDINATE WITH OWNER AND |
| CONTRACTOR. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 9- SINCE WINDOW PRODUCT APPROVAL SUBMITTED IS FOR |
| NON-IMPACT SINGLE HUNG WINDOWS, THEN NEED TO SPECIFY |
| SAFETY GLASS FOR THE BATHROOM WINDOW AS REQUIRED BY |
| SEC. R308.4.5 FBC-RESIDENTIAL. |
| |
| 10- ORIGINAL COMMENT: ACCORDING TO CITY RECORDS AND |
| PALM BEACH COUNTY PROPERTY APPRAISER THE PROPOSED |
| UTILITY ROOM WAS A PORCH. AFTER PLANS ARE REVISED, |
| BRING THEM TO PALM BEACH COUNTY (2300 N. JOG RD) FOR |
| IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED PLANS |
| AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT |
| FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| RESPONSE: REPEAT COMMENT. NOT ADDRESSED. |
| |
| |
| IMPORTANT TO EXPEDITE REVIEW PROCESS: |
| *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| *****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| FOR REFERENCE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |