2017-02-17 09:04:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020645
 2/17/17
  
 1) PLEASE REFER TO SECTION 306.5. ACCESS TO THE BDD
 WILL STILL BE REQUIRED BECAUSE IT MEETS THE DEFINITION
 OF EQUIPMENT PER SECTION 202. PLEASE PROVIDE A
 PERMANENT LADDER AND ACCESS PLATFORM PER THE
 INSPECTOR'S REQUEST.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER