Plan Review Notes For Permit 17020636 |
Permit Number |
17020636 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-17 17:11:58 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17020636 | | 2/17/17 | | | | 1) SUBMIT AN AC CHANGEOUT FORM FOR EACH OF THE SEVEN | | UNITS TO BE REPLACED. PLEASE NOTE THAT TWO COPIES ARE | | REQUIRED FOR EACH UNIT. | | | | 2) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | THE THREE 27-1/2- 50 TON UNITS- TCD480B40 & TCD600B40. | | | | 3) THE SUBMITTED ENGINEERING FROM BENCHMARK ENGINNERING | | FOR RTU'S 1-4 (3-10 TON UNITS) DOES NOT APPEAR TO SHOW | | HOW THE ADAPTERS WILL BE ATTACHED TO THE EXISTING | | CURBS. | | | | 4) SUBMIT CUT SHEETS FOR THE CURB ADAPTERS. | | | | 5) COMMISSIONING OF THE REPLACED AC SYSTEMS IS REQUIRED | | PER SECTION C408.2 FBC-14 ENERGY CONSERVATION. PLEASE | | PROVIDE A COMMISSIONING PLAN AS OUTLINED IN SECTION | | C408.2.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|