2017-02-14 15:56:21INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
  
 1- PLEASE SHOW ON PLANS THE LOCATION OF THE SERVICE
 EQUIPMENT AND PANEL LOCATION. MAIN DISCONNECT CANNOT BE
 LOCATED INSIDE HOME/ UNFUSED CONDUCTORS ARE LIMITED IN
 LENGTH PER AHJ. CLARIFY LOCATION
  
 2- PROVIDE A REVISED AIC CALCULATION DUE TO NEW
 SERVICE. FBC 107.3.5
  
 3- SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 LOCATION. NEC 250.94
  