2017-02-24 08:25:03 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| |
| 1. PROVIDE FLOOR PLAN IDENTIFYING LOCATION OF WORK. |
| 2. ALL SUBMITTAL DOCUMENTS SHALL BE IN DUPLICATE. |
| 3. THE INDIVIDUAL TAKING RESPONSIBILITY SHALL PROVIDE |
| THEIR PRINTED NAME AND SIGNATURE ON THE SUBMITTED PLANS |
| AND SUPPORTING DOCUMENTS PER FBC 107. |
| 4. PROVIDE ASTM E-90 (AIRBORNE) AND E-492 (IMPACT) FOR |
| PROPOSED UNDERLAYMENT. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. |
| |
| FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| APPLICATION. |
| |
| FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E - 90-02 |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E - 492-04 |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| |
| |
| |