Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-02-24 11:29:52CART B2 IS OBSTRUCTING THE EGRESS PATH. RELOCATE.
  
 GENERATOR EXHAUST SHALL BE LOCATED AT LEAST 10 FEET
 FROM ANY BUILDING OPENING.