Plan Review Notes For Permit 17020507 |
Permit Number |
17020507 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-02-24 11:36:04 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | PROVISO COMMENTS: | | | | 1. PLEASE PROVIDE DATA SHEETS REFLECTING LISTINGS FOR | | FOOD CARTS, DOCUMENTATION SUBMITTED DOES NOT REFLECT. | | FBC 107.3.5 | | 2. PROVIDE VOLTAGE DROP CALCULATIONS ON DISTRIBUTION | | PANELS. FBC 107.3.5 | | 3. PLEASE PROVIDE OVERCURRENT PROTECTION AND CONDUCTOR | | AMPACITIES BASED ON NEC 310.15B16 AND FBC 107.3.5 | | 4. PLEASE PROVIDE PORTABLE GENERATOR GROUNDING PER NEC | | 702.11A- GROUND PER NEC 250.30 | | 5. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW | | SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS. | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | |
|