2017-02-24 11:36:04INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PROVISO COMMENTS:
  
 1. PLEASE PROVIDE DATA SHEETS REFLECTING LISTINGS FOR
 FOOD CARTS, DOCUMENTATION SUBMITTED DOES NOT REFLECT.
 FBC 107.3.5
 2. PROVIDE VOLTAGE DROP CALCULATIONS ON DISTRIBUTION
 PANELS. FBC 107.3.5
 3. PLEASE PROVIDE OVERCURRENT PROTECTION AND CONDUCTOR
 AMPACITIES BASED ON NEC 310.15B16 AND FBC 107.3.5
 4. PLEASE PROVIDE PORTABLE GENERATOR GROUNDING PER NEC
 702.11A- GROUND PER NEC 250.30
 5. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.