Plan Review Notes For Permit 17020445
Permit Number 17020445
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-07 10:42:22****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, THE SUBMITTAL WAS NOT FOUND ACCEPTABLE BY
 EOR. REVISE SUBMITTAL PACKAGE ACCORDINGLY.
  
 2. PRODUCT APPROVALS FOR COMPONENTS AND CLADDING ARE
 REQUIRED TO BE SUBMITTED FOR REVIEW. DOCUMENTS SUCH AS
 THE ONES SUBMITTED ARE TO BE PROVIDED IN THE FIELD AT
 INSPECTION. IF THE INSPECTOR REQUESTS THAT THEY BE
 SUBMITTED FOR PLAN REVIEW, THEN THEY SHOULD BE
 SUBMITTED. ANY CHANGES TO THE DESIGN OF THE PROJECT ARE
 TO BE SUBMITTED AS A REVISION.
  
 IF THIS IS NOT A DESIGN CHANGE, AND IF THE INSPECTOR
 DID NOT REQUEST PLAN REVIEW FOR THIS ITEM, THIS SHOULD
 NOT BE RESUBMITTED.
  
  
  
  